Study of indoor local thermal comfort for impinging jet ventilation combined with ductless personalized ventilation under different cooling loads

被引:1
|
作者
Duan, Tao [1 ]
Ye, Xiao [1 ]
Du, Peng [1 ]
Qi, Hechuang [1 ,3 ]
Kang, Yanming [2 ]
Zhong, Ke [2 ]
机构
[1] Shanghai Univ Engn Sci, Sch Mech & Automobile Engn, Shanghai 201620, Peoples R China
[2] Donghua Univ, Sch Environm Sci & Engn, Shanghai 201620, Peoples R China
[3] China Acad Bldg Res, Beijing 100020, Peoples R China
基金
中国国家自然科学基金;
关键词
Impinging jet ventilation; Ductless personalized ventilation; Local thermal comfort; High cooling load; Optimization; Design chart; MIXING VENTILATION; SYSTEMS; FLOW; AIR; PERFORMANCE; OPTIMIZATION; BEHAVIOR; OFFICE; SPACES;
D O I
10.1016/j.buildenv.2024.112013
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Excessive temperature stratification and draught are two prominent drawbacks for impinging jet ventilation (IJV). Using IJV together with ductless personalized ventilation (DPV) (i.e., IJV + DPV) has been proved to be an effective way to reduce temperature stratification, but the draught rate around occupant would be increased. In the current work, an in-depth study on the characteristics of indoor local thermal comfort for IJV + DPV operating with different scenarios is done. Predictive models for the local thermal comfort indicators are developed to optimize the operating parameters (including supply velocity of IJV (Vs) and intake airflow rate of DPV (Df)) with different room cooling loads (Q). The results show that the application of IJV can be extended to spaces with high cooling loads (e.g., larger than 60 W/m2) by using together with DPV, but the risk of thermal discomfort increases. To avoid local thermal discomfort, the combination relationship between Vs and Df should be properly matched and this relation becomes more stricter with the increase of Q. It also obtains that the maximum cooling load that IJV + DPV can eliminate is less than 170 W/m2. At last, to ensure the IJV + DPV create a good local thermal comfort environment, design chart about the feasible ranges of Vs and Df are established for different values of Q. On the whole, the current study not only can provide a basis for the application of IJV + DPV in spaces with high cooling load, but also can provide theoretical guidance for the operation control and optimization design of the IJV + DPV.
引用
收藏
页数:15
相关论文
共 50 条
  • [31] A review of integrated radiant heating/cooling with ventilation systems- Thermal comfort and indoor air quality
    Zhang, Chen
    Pomianowski, Michal
    Heiselberg, Per Kvols
    Yu, Tao
    ENERGY AND BUILDINGS, 2020, 223
  • [32] Effectiveness of intermittent personalized ventilation assisting a chilled ceiling for enhanced thermal comfort and acceptable indoor air quality
    Al Assaad, Douaa
    Ghali, Kamel
    Ghaddar, Nesreen
    BUILDING AND ENVIRONMENT, 2018, 144 : 9 - 22
  • [33] Comparison study of thermal comfort and energy saving under eight different ventilation modes for space heating
    Kong, Xiangfei
    Chang, Yufan
    Li, Nana
    Li, Han
    Li, Wei
    BUILDING SIMULATION, 2022, 15 (07) : 1323 - 1337
  • [34] Comparison study of thermal comfort and energy saving under eight different ventilation modes for space heating
    Xiangfei Kong
    Yufan Chang
    Nana Li
    Han Li
    Wei Li
    Building Simulation, 2022, 15 : 1323 - 1337
  • [35] Passive cooling assessment of natural ventilation by windcatchers for enhancing thermal comfort and indoor air quality in European schools
    Nejat, Payam
    Fekri, Yashar
    Pourghasemian, Mohammad Hossein
    Alsaad, Hayder
    Voelker, Conrad
    BUILDING AND ENVIRONMENT, 2025, 276
  • [36] Effect of ventilation patterns on indoor thermal comfort and air-conditioning cooling and heating load using simulation
    Dian Sekartaji
    Yuji Ryu
    Didit Novianto
    City and Built Environment , 1 (1):
  • [37] A comparison of the thermal comfort performances of a radiation floor cooling system when combined with a range of ventilation systems
    Liu, Jiying
    Li, Zhuangzhuang
    Kim, Moon Keun
    Zhu, Shengwei
    Zhang, Linhua
    Srebric, Jelena
    INDOOR AND BUILT ENVIRONMENT, 2020, 29 (04) : 527 - 542
  • [38] Study of thermal and humidity environment and prediction model in impinging jet ventilation rooms based on thermal and moisture coupling
    Xi, Wentao
    Ye, Xiao
    Du, Peng
    Kang, Yanming
    Zhong, Ke
    BUILDING AND ENVIRONMENT, 2025, 267
  • [39] Impact of impinging jet ventilation on thermal comfort and aerosol transmission: A numerical investigation in a densely-occupied classroom with solar effect
    Li, Xueren
    Chen, Ziqi
    Tu, Jiyuan
    Yu, Hang
    Tang, Yin
    Qin, Chao
    JOURNAL OF BUILDING ENGINEERING, 2024, 94
  • [40] Methods for controlling airflow in and around a building under cross-ventilation to improve indoor thermal comfort
    Mochida, A
    Yoshino, H
    Takeda, T
    Kakegawa, T
    Miyauchi, S
    JOURNAL OF WIND ENGINEERING AND INDUSTRIAL AERODYNAMICS, 2005, 93 (06) : 437 - 449