Effects of building load characteristics on heating performance of the medium-deep U-type borehole heat exchanger coupled heat pumps: A coupled dynamic simulation

被引:0
|
作者
Huang, Shuai [1 ,2 ]
Lin, Duotong [1 ,2 ]
Dong, Jiankai [1 ,2 ]
Li, Ji [3 ]
机构
[1] Harbin Inst Technol, Sch Architecture & Design, Harbin 150090, Peoples R China
[2] Minist Ind & Informat Technol, Key Lab Cold Reg Urban & Rural Human Settlement En, Harbin 150090, Peoples R China
[3] China Acad Bldg Res, Inst Bldg Environm & Energy, Beijing 100013, Peoples R China
基金
中国国家自然科学基金;
关键词
Deep geothermal energy; Building loads; Heat pumps; Coupling simulation; MDUBHE; BEND PIPE; EFFICIENCY; CAPACITY;
D O I
10.1016/j.apenergy.2024.124405
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The medium-deep U-type borehole heat exchanger (MDUBHE) coupled ground source heat pump to extract deep geothermal energy for heating buildings is a novel and efficient system. However, the current research focuses on the heat transfer of the main apparatus MDUBHE and ignores the dynamic coupling and matching between the system and the building load, resulting in the effect of the building load characteristics on the system performance and the rock-soil temperature is still unclear. Therefore, this study first integrated the MDUBHE model into the Trnsys platform to realize the coupled simulation of building loads with the MDUBHE system. Based on the integrated novel platform, the effect mechanism of building load characteristics on the system's operation and the rock-soil temperature is revealed. The results show that the water temperature, flow rate, heating capacity, and system efficiency under dynamic actual load conditions are significantly different compared to constant building loads. The inlet and outlet temperatures varied in the ranges of 15.4-34.5 degrees C and 20.7-40.5 degrees C, respectively, and the flow rates on the user side and the ground source side varied in the ranges of 4.6x10(4)-2.2x10(5) kg/h and 3.7x10(4)-1.6x10(5) kg/h, respectively. In addition, the heating capacity varies from 0.1x10(3)-3.6x10(3) GJ, and the unit performance varies hourly. Furthermore, the soil temperatures also respond to changes in the actual building loads, but the variation is insignificant with increasing radial distance due to heat conduction. This study provides a foundation for matching the system capacity with the building loads.
引用
收藏
页数:15
相关论文
共 45 条
  • [41] Comprehensive thermal performance analysis and optimization study on U-type deep borehole ground source heat pump systems based on a new analytical model
    Shen, Junhao
    Zhou, Chaohui
    Luo, Yongqiang
    Tian, Zhiyong
    Zhang, Shicong
    Fan, Jianhua
    Ling, Zhang
    ENERGY, 2023, 274
  • [42] Thermal performance analysis of the novel medium-depth borehole heat exchanger (MDBHE) coupled photovoltaic photothermal (PV/T) heat pump domestic hot water supply system
    Zhu, Chao
    Cao, Min
    Zhang, Tuo
    Li, Biao
    Quan, Chen
    Wang, Yueshe
    ENERGY SOURCES PART A-RECOVERY UTILIZATION AND ENVIRONMENTAL EFFECTS, 2024, 46 (01) : 15841 - 15864
  • [43] 3D dynamic numerical programming and calculation of vertical buried tube heat exchanger performance of ground-source heat pumps under coupled heat transfer inside and outside of tube
    Guan, Yanling
    Zhao, Xiaoli
    Wang, Guanjun
    Dai, Jun
    Zhang, Hao
    ENERGY AND BUILDINGS, 2017, 139 : 186 - 196
  • [44] Thermal Performance Analysis and Multi-Factor Optimization of Middle-Deep Coaxial Borehole Heat Exchanger System for Low-Carbon Building Heating
    Liang, Mingshan
    Tu, Jianhua
    Zeng, Lingwen
    Zhang, Zhaoqing
    Cheng, Nan
    Luo, Yongqiang
    SUSTAINABILITY, 2023, 15 (21)
  • [45] A FEASIBILITY ANALYSIS ON NUMERICAL SIMULATION OF U-SHAPED TUBE BUNDLE HEAT EXCHANGER USING DUAL-MESH METHOD COUPLED WITH POROUS MEDIUM MODEL
    Zhao, Bi
    Zhang, Jing-zhou
    Lian, Wen-lei
    HEAT TRANSFER RESEARCH, 2021, 52 (02) : 75 - 95