Thermal behaviour of a transformer mineral oil-tank surface under incipient turn-to-turn short-circuit fault

被引:0
|
作者
Chen, Si [1 ]
Luo, Yingting [2 ]
Sheng, Gehao [1 ]
Jiang, Junfei [2 ]
机构
[1] Shanghai Jiao Tong Univ, Dept Elect Engn, 800 Dongchuan Rd, Shanghai 200240, Peoples R China
[2] Guangdong Power Grid Co Ltd, Elect Power Res Inst, Guangzhou, Peoples R China
关键词
temperature distribution; temperature measurement; thermal analysis; transformer windings; AGING ASSESSMENT MODEL; FUNDAMENTAL APPROACH;
D O I
10.1049/smt2.12200
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A slight turn-to-turn short-circuit fault in the incipient stage does not trigger fuse protection, and the regular transmission and transformation functions of the transformer within the power grid are not affected very much by the incipient turn-to-turn short-circuit fault. Therefore, the incipient turn-to-turn short-circuit faults are often undetected, resulting in massive accidents. Incipient turn-to-turn short-circuit faults lead to localized overheating in the transformer, which changes the transformer's oil-tank surface temperature (OTST). A thermal simulation model (TSM) is presented. Based on the TSM, OTST data with different load rates and fault parameters are collected. The steady-state and transient characteristics of OTST are analysed by extracting the OTST feature vector and the temperature difference of specific regions. The results show that the growth of the heat production value of faulty coils causes a rise in the OTST; higher faulty coils' locations lead to wider OTST differences; the temperature difference's area S can follow the incipient short-circuit fault in the first 20 min after it occurs, which is faster than the top oil temperature. This study gives insight into the thermal behaviour of OTST, assisting in fault detection and location at the incipient fault stage. This paper proposed a thermal simulation model of the oil-immersed transformer and analysed the oil-tank surface's steady-state and transient thermal behaviours under incipient turn-to-turn short-circuit faults. The oil-tank surface temperature (OTST) feature vector b is proposed to show the overall thermal behaviour of the oil-tank surface, and the temperature difference of the specific regions TF(S, hF) is analysed to show the local thermal behaviour. The proposed dynamic analysis and steady-state methods of analysing the thermal behaviour of OTST can help guide online monitoring and fault detection of transformers. image
引用
收藏
页码:310 / 323
页数:14
相关论文
共 50 条
  • [41] Compensation of Demagnetization Characteristics to Improve the Turn-to-Turn Short-Circuit Insulation Resistance Estimation in PMSG Using Moving Horizon Estimation Method
    Kumar, Logesh
    Nadarajan, Sivakumar
    Gupta, Amit K.
    Nguyen, Hung Dinh
    IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN INDUSTRIAL ELECTRONICS, 2024, 5 (01): : 242 - 252
  • [42] Analysis and Monitoring Method for Inter-Turn Short-Circuit Fault for PMSM
    Liu, Chengsi
    Xiao, Lijun
    Zou, Jibin
    Xu, Yongxiang
    Li, Shaobin
    IEEE TRANSACTIONS ON MAGNETICS, 2023, 59 (11)
  • [43] Fault diagnosis of stator inter-turn short-circuit in synchronous condensers
    Jiang, Meng-Yao
    Ma, Hong-Zhong
    Chen, Zhen-Fei
    Tang, Xiao-Zheng
    Liu, Yi-Dan
    Dianji yu Kongzhi Xuebao/Electric Machines and Control, 2021, 25 (07): : 75 - 86
  • [44] Asynchronous motor stator turn-to-turn short circuit fault diagnosis based on d - q transform and WOA-LSTM
    Wang, Xilian
    Qin, Jiayi
    Geng, Min
    Dianji yu Kongzhi Xuebao/Electric Machines and Control, 2024, 28 (06): : 56 - 65
  • [45] Active power optimisation for wind farms under generator inter-turn short-circuit fault
    Ma, Kuichao
    Soltani, Mohsen
    Hajizadeh, Amin
    Zhu, Jiangsheng
    Chen, Zhe
    IET RENEWABLE POWER GENERATION, 2020, 14 (12) : 2079 - 2088
  • [46] Analysis of primary side turn-to-turn short circuit fault in PT at the generator outlet and diagnosis using CSSA-GMM
    Wei, Yang
    Li, Chen
    Ai, Yuangao
    Shen, Hongwan
    Zeng, Shai
    Sun, Yue
    Frontiers in Energy Research, 2024, 12
  • [47] Thermal effects of short-circuit current on winding in transformer oil
    Gutten, Miroslav
    Trunkvalter, Milan
    PRZEGLAD ELEKTROTECHNICZNY, 2010, 86 (03): : 242 - 246
  • [48] Wind Farm Power Optimization and Fault Ride-Through under Inter-Turn Short-Circuit Fault
    Ma, Kuichao
    Soltani, Mohsen
    Hajizadeh, Amin
    Zhu, Jiangsheng
    Chen, Zhe
    ENERGIES, 2021, 14 (11)
  • [49] Transformer winding inter turn short circuit fault analysis and corrective measures
    Dong, Like
    Jin, Tao
    Guan, Shaoping
    Zheng, Zhihong
    Pei, Chu
    PROCEEDINGS OF 2018 IEEE 4TH INFORMATION TECHNOLOGY AND MECHATRONICS ENGINEERING CONFERENCE (ITOEC 2018), 2018, : 1102 - 1105
  • [50] Analysis of Physical Characteristics of Power Transformer Windings Under Inter-turn Short Circuit Fault
    Zhang B.
    Xian R.
    Yu Y.
    Xie T.
    Gao H.
    Chen L.
    Gaodianya Jishu/High Voltage Engineering, 2021, 47 (06): : 2177 - 2185