A review of switching overvoltage modeling in UHV AC transmission lines

被引:1
|
作者
Reddy, Sheri Abhishek [1 ]
Kumari, M. Sailaja [1 ]
机构
[1] Natl Inst Technol Warangal, Warangal 506004, Telangana, India
关键词
Fault clearing; Fault initiation; Line energization; Line re-energization; Switching overvoltages; UHV AC transmission line; IMPULSE TESTS; INSULATION COORDINATION; STATISTICAL-ANALYSIS; TRANSFORMER MODEL; SURGE ARRESTERS; RISK ANALYSIS; FAILURE RISK; TRANSIENTS; SIMULATION; VOLTAGE;
D O I
10.1016/j.epsr.2024.110902
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This review article on switching overvoltage modelling in UHV AC Transmission lines, provides a state-of-theart analysis of switching overvoltages and their impact on insulation coordination in UHV AC transmission lines. Switching overvoltages, insulation coordination, switching transient modelling tools, and switching surge flashover rate mathematical models are examined in the paper. It also examines modelling concepts, transmission models, insulation coordination for Ultra High Voltage (UHV) versus Extra High Voltage (EHV) lines, simulation scenarios and platforms, and best practices for insulation coordination limited to transmission lines. The methodology involved extensive research, consulting academic journals and conference papers, and modelling switching overvoltages with a case study. Key findings show that transmission tower insulation decreases because actual switching overvoltages take longer time to reach their peak than the critical wave. Every switching action generates a switching overvoltage with a characteristic waveform, which impacts insulation coordination. The work reveals a gap in existing research, which often focuses on overvoltages generated by a few switching events. This review suggests considering overvoltages from primary switching operations for better assessment of insulation coordination. These aspects must be considered in insulation coordination to improve UHV AC transmission line reliability and security.
引用
收藏
页数:20
相关论文
共 50 条
  • [41] Investigation on the "combined" live working method for tension towers of the UHV AC/DC Transmission lines
    Fang, Yuqun
    Qian, Liqun
    Wu, Tian
    Xiao, Bin
    Liu, Kai
    Liu, Ting
    Lei, Xinglie
    2016 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2016,
  • [42] Improving the Outdoor Insulation Performance of Chinese EHV and UHV AC and DC Overhead Transmission Lines
    Liang, Xidong
    Li, Shaohua
    Gao, Yanfeng
    Su, Zhiyi
    Zhou, Jun
    IEEE ELECTRICAL INSULATION MAGAZINE, 2020, 36 (04) : 7 - 25
  • [43] Design of UHV AC transmission line in China
    Liang, Zheng-ping
    Li, Yong-shuang
    Hu, Hong-chun
    Jia, Jiang-bo
    EUROPEAN TRANSACTIONS ON ELECTRICAL POWER, 2012, 22 (01): : 4 - 16
  • [44] Phase shift compensation method for the line differential protection on UHV-AC transmission lines
    Habib, Md Zakaria
    Wang, Jianping
    Li, Youyi
    Taylor, Nathaniel
    JOURNAL OF ENGINEERING-JOE, 2018, (15): : 876 - 880
  • [45] Key Technology Research of GFRP Cross Arm Tower of AC UHV Project on the Transmission Lines
    Zhang Y., Sr.
    Yu X.
    Li F.
    Lü D.
    Li X.
    Zhang J.
    Wang C.
    Chen H.
    Gaodianya Jishu/High Voltage Engineering, 2018, 44 (07): : 2402 - 2409
  • [46] EHV/UHV AC transmission capability analysis
    Xu, Z
    Gao, Z
    Zhou, CC
    2002 IEEE POWER ENGINEERING SOCIETY WINTER MEETING, VOLS 1 AND 2, CONFERENCE PROCEEDINGS, 2002, : 1344 - 1349
  • [47] Study on the difference of chemical composition of insulator contamination on UHV-AC and -DC transmission lines
    Li, Lee
    Jiang, Yunpeng
    Lu, Ming
    Liu, Zehui
    Hua, Kui
    Li, Zhe
    IET SCIENCE MEASUREMENT & TECHNOLOGY, 2018, 12 (01) : 17 - 24
  • [48] Field strength of body surface during the live working on the UHV AC and DC transmission lines
    Hu, Yi
    Hu, Jian-Xun
    Liu, Kai
    Liu, Ting
    Xiao, Bing
    Wu, Tian
    Gaodianya Jishu/High Voltage Engineering, 2010, 36 (01): : 13 - 18
  • [49] Corona loss characteristics of bundle conductors in UHV AC transmission lines at 2200 m altitude
    Huang Shilong
    Liu Yunpeng
    Chen Shaoshuai
    He Wangling
    Wan Baoquan
    Xu Lihua
    Li Yongjie
    ELECTRIC POWER SYSTEMS RESEARCH, 2019, 166 : 83 - 87
  • [50] Modeling and Simulation Analysis of Power Frequency Electric Field of UHV AC Transmission Line
    Han, Chen
    Chen, Yuchen
    INTERNATIONAL JOURNAL OF ADVANCED COMPUTER SCIENCE AND APPLICATIONS, 2015, 6 (01) : 77 - 81