PERFORMANCE OF PARTITIONED-BED SORPTION HEAT-PUMP SYSTEMS

被引:3
|
作者
ZHENG, W
WOREK, WM
NOWAKOWSKI, G
机构
[1] UNIV ILLINOIS,DEPT MECH ENGN MC251,CHICAGO,IL 60607
[2] GAS RES INST,CHICAGO,IL 60631
关键词
D O I
10.1615/JEnhHeatTransf.v2.i4.40
中图分类号
O414.1 [热力学];
学科分类号
摘要
Traditional two-bed solid-sorbent sorption heat pumps have no partitions within the beds. During the operation of a solid-sorbent sorption heat pump, ammonia readsorption (i.e., ammonia reallocation from one end of a bed to the other) occurs within the beds, which is detrimental to system performance. One way to reduce the ammonia reallocation within a bed is to put partitions in a bed to divide the bed into several segments and reduce the cross-communication of ammonia within a bed. In this paper, the effect of the partitions on the performance of a sorption heat pump system is investigated.
引用
收藏
页码:283 / 293
页数:11