EXPERIMENTAL-ANALYSIS OF A DC BUCKING MOTOR BLOCKING GEOMAGNETICALLY INDUCED CURRENTS

被引:8
|
作者
FARDOUN, AA
FUCHS, EF
MASOUM, MAS
机构
[1] Department of Electrical and Computer Engineering, University of Colorado, Boulder
关键词
NEUTRAL BLOCKING DEVICE; TRANSFORMER SATURATION; TRANSFORMER MODELING;
D O I
10.1109/61.277683
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
An experimental study investigates the performance of a dc bucking motor for the blocking of geomagnetically induced currents (GICs) within a 3 kVA/416 V three-phase distribution feeder. This blocking method consists of connecting a separately excited de motor between neutral and ground of a Y-grounded transformer consisting of a bank of three single-phase transformers. Losses and currents of the transformer and the blocking device are measured at no-load, rated-load, unbalanced-load and line-to-neutral short circuit conditions without and with GICs. Thereafter, the dc, ad and total lambda-iota characteristics of one single-phase transformer of the above-mentioned transformer bank are simultaneously measured using an arbitrary waveform generator, a power amplifier and a digital data acquisition network. These lambda-iota characteristics -where the dc bias current is a parameter- are then used to model a single-phase transformer under de bias current conditions (e.g., assumed GICs) and to calculate voltages and currents of a single-phase transformer when subjected to GICs. The simulated signals are then compared with measured time functions.
引用
收藏
页码:88 / 95
页数:8
相关论文
共 50 条