The heat-recovery power unit of a gas-piston mini cogeneration station

被引:0
|
作者
A. V. Dzhulii
L. B. Direktor
V. M. Zaichenko
A. V. Markov
机构
[1] OOO Elektro-LT,Joint Institute of High Temperatures
[2] Russian Academy of Sciences,undefined
关键词
Heat Exchanger; Heat Load; Internal Circuit; Bypass Line; Thermal Operating Condition;
D O I
10.1134/S0040601510010118
中图分类号
学科分类号
摘要
The specific features of the thermal operating conditions of the internal combustion engine and the design circuits of a mini cogeneration station’s heat-recovery unit are considered. The basic scheme of the heat-recovery unit’s thermal parameters automatic control system is proposed, the use of which makes it possible to maintain the design temperatures of coolants and heating agents (cooling liquid and oil, combustion products, and heat network water) during variations of the electrical and heat loads of consumers. The results from rig tests of the 450-kW(t) heat-recovery unit for a mini cogeneration station equipped with a YaMZ-8401 gaspiston engine are presented.