Switching transients caused by vacuum circuit breakers in collection grids of offshore wind farms

被引:5
|
作者
Tao, Jiayuan [1 ]
Yang, Qing [2 ]
Zheng, Xuena [3 ]
He, Yanxiao [4 ]
Wang, Ruixue [3 ]
Lv, Hefei [5 ]
Zhang, Jie [6 ]
机构
[1] Chongqing Coll Elect Engn, Chongqing, Peoples R China
[2] Chongqing Univ, State Key Lab Power Transmiss Equipment & Syst Se, Chongqing, Peoples R China
[3] Chongqing Metropolitan Coll Sci & Technol, Chongqing, Peoples R China
[4] Chongqing Univ Technol, Liangjiang Int Coll, Chongqing, Peoples R China
[5] NR Elect Co Ltd, Nanjing, Peoples R China
[6] State Grid Chongqing Elect Power Co, Chongqing, Peoples R China
关键词
multiple prestrike and reignition; offshore wind farms; overvoltage; suppression measure; switching transients; vacuum circuit breaker;
D O I
10.1002/we.2643
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In this study, transients that can occur in the collection grids of offshore wind farms were investigated. On the basis of the multiple prestrike and reignition model that can reflect the actual operation of a vacuum circuit breaker (VCB), a switching transient simulation model of a typical offshore wind farm was built. The developed model included a VCB, a transformer, a cable, and an arrester. Issues concerning the closing time, length of the feeder, and topology of the collection grid were discussed. Results showed that the relationship between overvoltage amplitude and closing time was approximately sinusoidal and the maximum value was obtained when the closing time was near the peak of the power source. In addition, the overvoltage at the end of a feeder terminal was the largest among all of the transformer overvoltages of the same feeder. The overvoltage of the main transformer and that of the transformer located at the end of a feeder decreased slowly with the increase in feeder length during the closing of VCB. However, these overvoltages were positively related to feeder length during the opening of VCB. The star topology was superior to the other topologies in terms of coping with the overvoltage caused by switching transients. The effectiveness of a suppression measure, namely, installation of a resistance-capacitor filter, was also verified.
引用
收藏
页码:1501 / 1516
页数:16
相关论文
共 50 条
  • [1] Overvoltage and Its Protection of Switching Shunt Reactors by Vacuum Circuit Breakers in Offshore Wind Farms
    Zhou W.
    Tang W.
    Xin Y.
    Zhou J.
    Wu Q.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2018, 42 (03): : 77 - 83
  • [2] Investigation on Overvoltage caused by Connecting Shunt Reactors with Vacuum Circuit Breakers in Offshore Wind Farms
    Zhou, W. T.
    Xin, Y. L.
    Tang, W. H.
    Huang, J. J.
    Wu, Q. H.
    2018 3RD ASIA CONFERENCE ON POWER AND ELECTRICAL ENGINEERING (ACPEE 2018), 2018, 366
  • [3] Influence of RC snubbers on the Steepness of Switching Transients caused by Vacuum Circuit Breakers
    Nilges, Matthias
    Schegner, Peter
    2018 IEEE POWER & ENERGY SOCIETY GENERAL MEETING (PESGM), 2018,
  • [4] Investigation on Reignition Probability of Switching Overvoltage Caused by Vacuum Circuit Breaker in Offshore Wind Farms
    Sun, Qiuqin
    Zheng, Zhi
    Huang, Lei
    Wang, Feng
    Zhong, Lipeng
    Chen, She
    IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (05) : 4438 - 4447
  • [5] Development of Improved Suppression Measures Against Reignition Overvoltages Caused by Vacuum Circuit Breakers in Offshore Wind Farms
    Xin, Yanli
    Zhao, Baining
    Liang, Qiheng
    Zhou, Jiujiang
    Qian, Tong
    Yu, Zeyuan
    Tang, Wenhu
    IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (01) : 517 - 527
  • [6] Reignition overvoltages induced by vacuum circuit breakers and its suppression in offshore wind farms
    Guo, Yaxun
    Jiang, Xiaofeng
    Chen, Yun
    Zheng, Ming
    Liu, Gang
    Li, Xiaohua
    Tang, Wenhu
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2020, 122
  • [7] Investigation on overvoltage caused by vacuum circuit breaker switching off shunt reactor in offshore wind farms
    Zheng, Zhi
    Sun, Qiuqin
    Yang, Jianlan
    Chen, She
    Wang, Feng
    Zhong, Lipeng
    HIGH VOLTAGE, 2022, 7 (05) : 936 - 949
  • [8] Transients in collection grids of large offshore wind parks
    Liljestrand, Lars
    Sannino, Ambra
    Breder, Henrik
    Thorburn, Stefan
    WIND ENERGY, 2008, 11 (01) : 45 - 61
  • [9] General Analysis of Vacuum Circuit Breaker Switching Overvoltages in Offshore Wind Farms
    Ghafourian, S. M.
    Arana, I.
    Holboll, J.
    Sorensen, T.
    Popov, M.
    Terzija, V.
    IEEE TRANSACTIONS ON POWER DELIVERY, 2016, 31 (05) : 2351 - 2359
  • [10] Analysis of Restrike Overvoltage of Circuit Breakers in Offshore Wind Farms
    Zhou, Qibin
    Cheng, Yu
    Bian, Xiaoyan
    Liu, Feifan
    Zhao, Yang
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2016, 26 (07)