Problems with modern air-cooled generator stator windings

被引:0
|
作者
Tucker, S [1 ]
Milsom, J [1 ]
Griffith, G [1 ]
Stone, G [1 ]
机构
[1] Natl Power PLC, Selby, England
关键词
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The widespread use of air-cooled turbine generators has reduced the capital cost of modern gas-fired and combined cycle plants. However problems have recently been experienced in some of the stator windings in such generators. These problems include deterioration and failure of the insulation in the stator slot due to coil vibration. This has occurred in both conventional and global VPI stators. In addition, some machines have seen problems with partial discharge in the endwinding and lead area due to insufficient spacing between high voltage components. This paper presents examples of these problems, and discusses some repair alternatives.
引用
收藏
页码:137 / 144
页数:8
相关论文
共 50 条
  • [1] Problems with modern air-cooled generator stator winding insulation
    Griffith, G
    Tucker, S
    Milsom, J
    Stone, G
    IEEE ELECTRICAL INSULATION MAGAZINE, 2000, 16 (06) : 6 - 10
  • [2] Analysis of Insulation Diagnosis and Failure in Stator Windings of Air-Cooled Gas Turbine Generator
    Kim, Hee-Dong
    Kong, Tae-Sik
    2014 IEEE ENERGY CONVERSION CONGRESS AND EXPOSITION (ECCE), 2014, : 1472 - 1475
  • [3] Stator coil insulation for modern air-cooled generators
    Emery, FT
    ELECTRICAL INSULATION CONFERENCE AND ELECTRICAL MANUFACTURING & COIL WINDING CONFERENCE, PROCEEDINGS, 2001, : 185 - 188
  • [4] Power losses and heat extraction in a stator with directly air-cooled laminated windings
    Reinap, A.
    Hogmark, C.
    Marquez-Fernandez, F. J.
    Alakula, M.
    Andersson, M.
    2018 XIII INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES (ICEM), 2018, : 2675 - 2681
  • [5] Numerical Studies on the Flow Field of Stator and Air Gap for Large Air-cooled Turbo-generator
    Han, Jiade
    Hong, Guangyu
    Tang, Lu
    Lu, Yiping
    ELECTRICAL POWER & ENERGY SYSTEMS, PTS 1 AND 2, 2012, 516-517 : 970 - 975
  • [6] SLOT DISCHARGE DAMAGE IN AIR COOLED STATOR WINDINGS
    WILSON, A
    IEE PROCEEDINGS-A-SCIENCE MEASUREMENT AND TECHNOLOGY, 1991, 138 (03): : 153 - 160
  • [7] Influence of a Novel Stator Teeth Internal Ventilation Structure on Air-Cooled Turbo-Generator Parameters and Stator Temperature
    Liu, Wenmao
    Li, Weili
    Luo, Shifan
    Huang, Xuelian
    Li, Dan
    Li, Zhiqiang
    Xu, Guorui
    IEEE ACCESS, 2020, 8 : 122422 - 122433
  • [8] Evolution of air-cooled turbine generator design
    Jarczynski, E
    Wetzel, T
    Fealey, J
    IEEE IEMDC'03: IEEE INTERNATIONAL ELECTRIC MACHINES AND DRIVES CONFERENCE, VOLS 1-3, 2003, : 117 - 123
  • [9] CORRECTING AIR-COOLED EXCHANGER PROBLEMS
    SHIPES, K
    CHEMICAL ENGINEERING PROGRESS, 1983, 79 (07) : 56 - 57
  • [10] Heat transfer in an air-cooled rotor-stator system
    Chen, JX
    Gan, X
    Owen, JM
    JOURNAL OF TURBOMACHINERY-TRANSACTIONS OF THE ASME, 1996, 118 (03): : 444 - 451