Macrofouling in the cooling water conduits of a coastal power station

被引:0
|
作者
Thiyagarajan, V [1 ]
Venugopalan, VP [1 ]
Subramoniam, T [1 ]
Nair, KVK [1 ]
机构
[1] Univ Madras, Dept Zool, Madras 600025, Tamil Nadu, India
来源
INDIAN JOURNAL OF MARINE SCIENCES | 1997年 / 26卷 / 03期
关键词
D O I
暂无
中图分类号
P7 [海洋学];
学科分类号
0707 ;
摘要
Macrofouling incidence at six different locations experiencing different environmental conditions in the cooling conduits of the Madras Atomic Power Station (MAPS) was studied. Samples were analyzed for biomass and species abundance. Fouling biomass was significantly (t=3.95, P=0.0016) higher on concrete surface than on carbon steel surface. Flow velocity, temperature and substratum type were the main factors which determined community structure in different sections of the cooling conduits. These factors as well as the fouling control regime adopted in cooling systems make fouling more intense in some places than in others.