Criteria Revision of Dissolved Gas Analysis for Oil-Filled Transformers in Korea

被引:0
|
作者
Cho, Sung-Min [1 ]
Kim, Jae-Chul [1 ]
机构
[1] Soongsil Univ, Dept Elect Engn, Seoul 156743, South Korea
关键词
Fault diagnosis; Maintenance; Oil insulation; Power transformers;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The story on revising criteria of Dissolved Gases Analysis (DGA) at KEPCO was introduced. Because of differences in operating environments, construction type, oil volume, and other factors, the interpretative criteria of DGA at KEPCO should be different from other standards such as IEC-60599, or Rogers and Doernenburg. We tried to improve efficiency of DGA by considering accumulated data during twenty-five years. To establish the most appropriate criteria, the DGA results were collected from healthy power transformers as well as transformers which have an incipient fault. The criteria were revised newly using cumulative distribution of concentration of 3,585 healthy power transformers. Although the criteria are revised strictly, work load doesn't increase by controlling analysis interval and condition level.
引用
收藏
页码:4057 / 4060
页数:4
相关论文
共 50 条
  • [1] A Spreadsheet Based Dissolved Gas Analysis Diagnostic Tool For Oil-Filled Transformers
    Mekkayil, Anju
    Pillai, Gobind
    Malcolm, Marc
    2020 55TH INTERNATIONAL UNIVERSITIES POWER ENGINEERING CONFERENCE (UPEC), 2020,
  • [2] Testing and approval standard development of online dissolved gas analysis monitors for oil-filled transformers-Part I hydrogen monitors
    Su, Paul
    Madan, Rajni
    Purushothaman, Sujit
    PROCESS SAFETY PROGRESS, 2024, 43 (04) : 686 - 694
  • [3] On-line diagnostics of oil-filled transformers
    Varl, A
    PROCEEDINGS OF THE 2002 IEEE 14TH INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS, 2002, : 253 - 257
  • [4] THE ANALYSIS OF GASES IN TRANSFORMERS AND OTHER OIL-FILLED ELECTRICAL-EQUIPMENT
    KAWADA, H
    ISHII, T
    JOURNAL OF JAPAN SOCIETY OF LUBRICATION ENGINEERS, 1980, 25 (11): : 734 - 739
  • [5] Fault Analysis of Oil-Filled Power Transformers Using Spectroscopy Techniques
    Kalathiripi, Hussain
    Karmakar, Subrata
    2017 IEEE 19TH INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS (ICDL), 2017,
  • [6] Rapid Assessment of the Operational Status of the Oil-filled Transformers
    Levin, Vladimir
    Kerimkulov, Nurzhan
    2016 11TH INTERNATIONAL FORUM ON STRATEGIC TECHNOLOGY (IFOST), PTS 1 AND 2, 2016,
  • [7] Model for Predictive Control of Temperature in Oil-filled Transformers
    Mastorakis, Nikos E.
    Bulucea, Cornelia Aida
    Manolea, Gheorghe
    Popescu, Marius Constantin
    Perescu-Popescu, Liliana
    PROCEEDINGS OF THE 11TH WSEAS INTERNATIONAL CONFERENCE ON AUTOMATIC CONTROL, MODELLING AND SIMULATION: CONTROLLING, MODELLING AND SIMULATION, 2009, : 157 - +
  • [8] DE-SLUDGING ENERGIZED OIL-FILLED TRANSFORMERS
    PARRISH, RH
    KELLY, JJ
    PLANT ENGINEERING, 1979, 33 (20) : 101 - 105
  • [9] Preliminary Results for Dissolved Gas Levels in a Vegetable Oil-Filled Power Transformer
    Martin, Daniel
    Lelekakis, Nick
    Davydov, Valery
    Odarenko, Yuriy
    IEEE ELECTRICAL INSULATION MAGAZINE, 2010, 26 (05) : 41 - 48
  • [10] Improvement for diagnosing internal abnormalities in oil-filled transformers
    Zama, Shigeyuki
    Kobayashi, Takayuki
    Ikeda, Jiro
    Eto, Atsushi
    PROCEEDINGS OF 2008 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS, 2007, : 941 - 944