Experimental study on the flame extension and risk analysis of a diffusion impinging flame in confined compartment

被引:5
|
作者
Wang, Aijuan [1 ]
Manescau, Brady [1 ]
Chetehouna, Khaled [1 ]
Rudz, Steve [2 ]
Lamoot, Ludovic [1 ]
机构
[1] Univ Orleans, INSA Ctr Val Loire, PRISME, EA 4229, 88 Blvd Lahitolle, F-18000 Bourges, France
[2] Univ Orleans, CNRS, UMR 7344, GREMI, Bourges, France
关键词
Impinging flame; flame extension; confined compartment; equivalence ratio; auto-ignition; CEILING JETS; FIRE DETECTION; LENGTHS; WALL; GAS;
D O I
10.1177/07349041211015766
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
In this work, an experimental investigation on a diffusion impinging flame in a confined compartment was performed. The objective was to study the influence of confinement on the behavior of a flame impinging the ceiling and to deduce the auto-ignition risk of the smoke produced in the confined compartment. For this, configurations with five confinement levels were constructed by the condition of windows and/or door in the compartment and the variation of the heat release rates was made between 0.5 and 18.6 kW. To evaluate the flame morphology and flame extension length, an image processing method based on the direct linear transformation algorithm and the fire segmentation algorithm was adopted. From the experimental data, it was shown that the heat release rate of 4.6 kW presents a critical value for the flame extension in confined configurations, which corresponds to the equivalence ratio of the enclosure greater than 1, highlighting an under-ventilated environment. In addition, an auto-ignition risk analysis of smoke with unburnt gas in the compartment was carried out. The concentration and temperature of these gases were compared to the lower flammability limits and the auto-ignition temperature. It was observed that there was auto-ignition risk of the smoke under the ceiling, especially in the confined compartment of equivalence ratio greater than 1. Under these conditions, it is possible to have a fire spread to another compartment.
引用
收藏
页码:285 / 308
页数:24
相关论文
共 50 条
  • [21] Entropy generation in a confined laminar diffusion flame
    Datta, A
    COMBUSTION SCIENCE AND TECHNOLOGY, 2000, 159 : 39 - 56
  • [22] The experimental study on the flame extension length and maximum temperature of ceiling jet flame in the curved tunnel
    Gao, Yang
    Fang, Yuhao
    Gong, Lunlun
    Yang, Shenlin
    Tao, Changfa
    Xu, Wei
    TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2025, 161
  • [23] Experimental study of diffusion flame oscillations and empirical correlations
    Yilmaz, Nadir
    Donaldson, A. Burl
    Lucero, R. Edward
    ENERGY CONVERSION AND MANAGEMENT, 2008, 49 (11) : 3287 - 3291
  • [24] Computational and experimental study of NO in an axisymmetric laminar diffusion flame
    Smooke, MD
    Ern, A
    Tanoff, MA
    Valdati, BA
    Mohammed, RK
    Marran, DF
    Long, MB
    TWENTY-SIXTH SYMPOSIUM (INTERNATIONAL) ON COMBUSTION, VOLS 1 AND 2, 1996, : 2161 - 2170
  • [25] EXPERIMENTAL-STUDY ON STABILITY OF JET DIFFUSION FLAME
    TAKENO, T
    KOTANI, Y
    ACTA ASTRONAUTICA, 1975, 2 (11-1) : 999 - 1008
  • [26] Nitrogen Dilution and Extinction Effects for Methane Impinging Diffusion Flame
    Ghiti, Nadjib
    Bentebbiche, Abed Alhalim
    Boulkroune, Ramzi
    2012 INTERNATIONAL CONFERENCE ON MECHANICAL, INDUSTRIAL, AND MANUFACTURING ENGINEERING, 2012, 1 : 39 - 46
  • [27] Experimental Study of the Impinging Flame Height in an Opposed Multi-burner Gasifier
    Fan, Puxing
    Gong, Yan
    Zhang, Qing
    Guo, Qinghua
    Yu, Guangsuo
    ENERGY & FUELS, 2014, 28 (08) : 4895 - 4904
  • [28] Heat transfer characteristics of an impinging inverse diffusion flame jet. Part II: Impinging flame structure and impingement heat transfer
    Dong, L. L.
    Cheung, C. S.
    Leung, C. W.
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2007, 50 (25-26) : 5124 - 5138
  • [29] Heat transfer characteristics of an impinging inverse diffusion flame jet - Part I: Free flame structure
    Dong, L. L.
    Cheung, C. S.
    Leung, C. W.
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2007, 50 (25-26) : 5108 - 5123
  • [30] Stability of Gas Diffusion Flame in Laterally Confined Space
    Wang, Xiuzhen
    Zhu, Feng
    Wang, Shuangfeng
    JOURNAL OF THERMAL SCIENCE, 2024, 33 (06) : 2437 - 2449