Monitoring of Partial Discharges in Cable Insulation and Cable Head Using Acoustic Method

被引:1
|
作者
Ranachowski, Zbigniew [1 ]
Wieczorek, Krzysztof [2 ]
Ranachowski, Przemyslaw [1 ]
Debowski, Tomasz [1 ]
机构
[1] Polish Acad Sci, Inst Fundamental Technol Res, Warsaw, Poland
[2] Wroclaw Univ Sci & Technol, Dept Elect Engn Fundamentals, Wroclaw, Poland
关键词
partial discharges; medium voltage insulation; acoustic emission; EMISSION METHOD;
D O I
10.24425/aoa.2022.141654
中图分类号
O42 [声学];
学科分类号
070206 ; 082403 ;
摘要
The article presents the application of Acoustic Emission (AE) method for detection and registration of partial discharges (PD) generated in medium voltage (MV) cable isolation and MV cable head. The insulation of the high voltage cable is made of a flexible material whose properties are characterised by a high coefficient of attenuation of the acoustic signals. For this reason, the AE method has not been used so far to detect PD in energetic cables. The subjects of the research were the MV cable and the standard T-type cable head. The cable contained defects which were the source of partial discharges. In case of cable head the PD were provoked by thin grounded electrode which was introduced into connector opening. The results of AE measurements are presented in the form of spectrograms. Acoustic Emission was evoked when the applied voltage level reached the value of 7.5 kV for the cable and 4 kV for the cable head. The authors used the acoustic instrumentation of their own design intended for future field use. Obtaining successful results of partial discharges measurements using the acoustic method in the cable insulation makes an original contribution of the presented work.
引用
收藏
页码:259 / 265
页数:7
相关论文
共 50 条
  • [31] Application of the UHF method for partial discharges measurement in high voltage cable lines
    Konarski, Michal
    Wegierek, Pawel
    PRZEGLAD ELEKTROTECHNICZNY, 2019, 95 (06): : 86 - 89
  • [32] A Novel Cable Tension Monitoring Method Based on Self Stress Attenuation Feature in Cable Anchor Head
    Wu, Jun
    Chen, Weimin
    Liu, Lihua
    Zhao, Xia
    Liu, Li
    Liu, Hao
    SENSOR LETTERS, 2012, 10 (07) : 1366 - 1369
  • [33] Partial Discharges Classification Methods in XLPE Cable: A Review
    Rosle, Norfadilah
    Muhamad, Nor Asiah
    Rohani, Mohamad Nur Khairul Hafizi
    Jamil, Mohamad Kamarol Mohd
    IEEE ACCESS, 2021, 9 : 133258 - 133273
  • [34] Pattern Recognition of Partial Discharges on Power Cable Systems
    Rajendran, Arunjothi
    Thirumurthy
    Meena, K. P.
    PROCEEDINGS OF THE 21ST INTERNATIONAL SYMPOSIUM ON HIGH VOLTAGE ENGINEERING, VOL 1, 2020, 598 : 510 - 520
  • [36] A Novel Model of Partial Discharge Initiation in Cable Insulation
    Li, Gen
    Chen, Jie
    Li, Hongze
    Hu, Libin
    Zhou, Wenjun
    Zhou, Chengke
    IEEE ACCESS, 2022, 10 : 47837 - 47845
  • [37] Influence of cable tension history on the monitoring of cable tension using magnetoelastic inductance method
    Zhang, Senhua
    Zhou, Jianting
    Zhang, Hong
    Liao, Leng
    Liu, Lei
    STRUCTURAL HEALTH MONITORING-AN INTERNATIONAL JOURNAL, 2021, 20 (06): : 3392 - 3405
  • [38] Research on On-Line Monitoring Method of Cable Insulation Based on Signal Injection
    Niu, Lin
    Wu, Guiying
    Xu, Zhangsheng
    2021 IEEE 12TH ENERGY CONVERSION CONGRESS AND EXPOSITION - ASIA (ECCE ASIA), 2021, : 1844 - 1849
  • [39] Investigation of Partial Discharge Phenomena on XLPE Cable Insulation Using COMSOL Multiphysics
    Sahoo, Rakesh
    Karmakar, Subrata
    ELECTRIC POWER COMPONENTS AND SYSTEMS, 2024,
  • [40] DIAGNOSTIC METHOD FOR POWER CABLE INSULATION.
    Soma, K.
    Aihara, M.
    Kataoka, Y.
    IEEE transactions on electrical insulation, 1986, EI-21 (06): : 1027 - 1032