Numerical simulation of ground source heat pump systems considering unsaturated soil properties and groundwater flow

被引:69
|
作者
Li, Chaofeng [1 ]
Cleall, Peter John [2 ]
Mao, Jinfeng [1 ]
Munoz-Criollo, Jose Javier [2 ]
机构
[1] PLA Univ Sci & Technol, Nanjing 210007, Jiangsu, Peoples R China
[2] Cardiff Univ, Cardiff Sch Engn, Cardiff CF24 3AA, S Glam, Wales
关键词
Ground source heat pump; Borehole heat exchanger; Unsaturated soil; Groundwater flow; LONG-TERM PERFORMANCE; SENSITIVITY-ANALYSIS; THERMAL PERFORMANCE; EXCHANGER FIELDS; BOREHOLE; EFFICIENCY; MODEL; TEMPERATURE; SUSTAINABILITY; CONDUCTIVITY;
D O I
10.1016/j.applthermaleng.2018.04.142
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper analyzes the influence of unsaturated soil properties and groundwater flow on the performance of ground source heat pump (GSHP) systems. A mathematical model of GSHP systems, which considers the influence of varying unsaturated soil thermal properties, groundwater table depth and saturated groundwater flow, is introduced and coupled to a heat pump model to consider dynamically-changing loads due to specific heat pump coefficient of performance (COP) characteristics. The model is validated against experiment results and an analytical model reported by others. Finally, numerical simulations are performed to investigate the effect of inclusion of a heat pump, moisture content variations, groundwater table fluctuations and groundwater flow rates on the performance of the GSHP system. Results show that neglecting variations in moisture content in unsaturated soil could lead to underestimating the heat transfer capacity of the soil. A rising groundwater table is beneficial to the operation of the GSHP system. The influence of groundwater table fluctuations should be considered, otherwise it may result in a error of 3-4% in the outlet fluid temperature. When calculating the influence of groundwater flow rates on the performance of the GSHP system, the effect of the position of the groundwater table should also be considered.
引用
收藏
页码:307 / 316
页数:10
相关论文
共 50 条
  • [41] Capacity control in ground source heat pump systems Part I: modeling and simulation
    Madani, Hatef
    Claesson, Joachim
    Lundquist, Per
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2011, 34 (06): : 1338 - 1347
  • [42] SIMULATION MODELING OF GROUND SOURCE HEAT PUMP SYSTEMS FOR THE PERFORMANCE ANALYSIS OF RESIDENTIAL BUILDINGS
    Cho, Soolyeon
    Mirianhosseinabadi, Sedighehsadat
    BUILDING SIMULATION 2013: 13TH INTERNATIONAL CONFERENCE OF THE INTERNATIONAL BUILDING PERFORMANCE SIMULATION ASSOCIATION, 2013, : 1960 - 1967
  • [43] LONG TERM SIMULATION OF HORIZONTAL GROUND HEAT EXCHANGER FOR GROUND SOURCE HEAT PUMP
    Kayaci, Nurullah
    Demir, Hakan
    Atayilmaz, S. Ozgur
    Agra, Ozden
    PROCEEDINGS OF THE ASME INTERNATIONAL MECHANICAL ENGINEERING CONGRESS AND EXPOSITION, 2015, VOL 6B, 2016,
  • [44] Feasibility study and numerical simulation of a ground source heat pump plant, applied to a residential building
    Desideri, U.
    Sorbi, N.
    Arcioni, L.
    Leonardi, D.
    APPLIED THERMAL ENGINEERING, 2011, 31 (16) : 3500 - 3511
  • [45] GROUND-SOURCE HEAT-PUMP SYSTEMS
    CALM, J
    ASHRAE JOURNAL-AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR-CONDITIONING ENGINEERS, 1983, 25 (05): : 59 - 59
  • [46] Ground source heat pump systems: Current status
    Younis M.
    Bolisetti T.
    Ting D.S-K.
    International Journal of Environmental Studies, 2010, 67 (03) : 405 - 415
  • [47] Numerical simulation of ground heat and water transfer for groundwater heat pump system based on real-scale experiment
    Nam, Yujin
    Ooka, Ryozo
    ENERGY AND BUILDINGS, 2010, 42 (01) : 69 - 75
  • [48] Numerical modeling of a ground source heat pump: The Bolu case
    Camdali, Unal
    Bulut, Murat
    Sozbir, Nedim
    RENEWABLE ENERGY, 2015, 83 : 352 - 361
  • [49] Heat transfer performance test and numerical simulation of pile-pipe ground source heat pump system
    Institute of HVAC and GAS Engineering, Tongji University, Shanghai 200092, China
    Taiyangneng Xuebao, 2009, 6 (727-731):
  • [50] A NEW METHOD TO DETERMINE THE THERMAL PROPERTIES OF SOIL FOR VERTICAL-BOREHOLE GROUND-SOURCE HEAT PUMP SYSTEMS
    Dong, Xingjie
    Gu, Bo
    HEAT TRANSFER RESEARCH, 2015, 46 (05) : 417 - 427