Performance Analysis of Variable Mode Adsorption Chiller at Different Recooling Water Temperatures

被引:4
|
作者
Alsarayreh, Ahmad A. [1 ]
Al-Maaitah, Ayman [2 ]
Attarakih, Menwer [3 ]
Bart, Hans-Joerg [4 ]
机构
[1] Precision Ind, POB 37448, Dubai, U Arab Emirates
[2] Wahaj Investment LLC, 24B St,Comm 365,Ind 2,POB 37448, Dubai, U Arab Emirates
[3] Univ Jordan, Dept Chem Engn, Queen Rania St, Amman 11942, Jordan
[4] TU Kaiserslautern, Therm Verfahrenstech, D-67653 Kaiserslautern, Germany
关键词
adsorption; zeolite; SAPO-34; adsorption cooling; mass recovery; variable mode; MASS RECOVERY; HEAT-PUMP;
D O I
10.3390/en14133871
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Adsorption cooling can recover waste heat at low temperature levels, thereby saving energy and reducing greenhouse gas emissions. An air-cooled adsorption cooling system reduces water consumption and the technical problems associated with wet-cooling systems; however, it is difficult to maintain a constant recooling water temperature using such a system. To overcome this limitation, a variable mode adsorption chiller concept was introduced and investigated in this study. A prototype adsorption chiller was designed and tested experimentally and numerically using the lumped model. Experimental and numerical results showed good agreement and a similar trend. The adsorbent pairs investigated in this chiller consisted of silicoaluminophosphate (SAPO-34)/water. The experimental isotherm data were fitted to the Dubinin-Astakhov (D-A), Freundlich, Hill, and Sun and Chakraborty (S-C) models. The fitted data exhibited satisfactory agreement with the experimental data except with the Freundlich model. In addition, the adsorption kinetics parameters were calculated using a linear driving force model that was fitted to the experimental data with high correlation coefficients. The results show that the kinetics of the adsorption parameters were dependent on the partial pressure ratio. Four cooling cycle modes were investigated: single stage mode and mass recovery modes with duration times of 25%, 50%, and 75% of the cooling cycle time (denoted as short, medium, and long mass recovery, respectively). The cycle time was optimized based on the maximum cooling capacity. The single stage, short mass recovery, and medium mass recovery modes were found to be the optimum modes at lower (<35 degrees C), medium (35-44 degrees C), and high (>44 degrees C) recooling temperatures. Notably, the recooling water temperature profile is very important for assessing and optimizing the suitable working mode.
引用
收藏
页数:26
相关论文
共 50 条
  • [1] Energy and Exergy Analyses of Adsorption Chiller at Various Recooling-Water and Dead-State Temperatures
    Alsarayreh, Ahmad A.
    Al-Maaitah, Ayman
    Attarakih, Menwer
    Bart, Hans-Joerg
    ENERGIES, 2021, 14 (08)
  • [2] Increasing the Performance of an Adsorption Chiller Operating in the Water Desalination Mode
    Sztekler, Karol
    Mika, Lukasz
    ENERGIES, 2021, 14 (22)
  • [3] Performance of the chiller with variable chilled-water flow
    Zhang, Mouxiong
    Nuantong Kongtiao/HV & AC, 2000, 30 (06): : 56 - 58
  • [4] THEORETICAL STUDY AND PERFORMANCE ANALYSIS OF AN ADSORPTION CHILLER
    Popa, V
    Costiuc, L.
    Cuzic, M.
    23RD IIR INTERNATIONAL CONGRESS OF REFRIGERATION, 2011, 23 : 1123 - +
  • [5] Performance evaluation of a zeolite-water adsorption chiller with entropy analysis of thermodynamic insight
    Li, Ang
    Bin Ismail, Azhar
    Thu, Kyaw
    Ng, Kim Choon
    Loh, Wai Soong
    APPLIED ENERGY, 2014, 130 : 702 - 711
  • [6] Experimental performance of a silica gel-water adsorption chiller
    Liu, YL
    Wang, RZ
    Xia, ZZ
    APPLIED THERMAL ENGINEERING, 2005, 25 (2-3) : 359 - 375
  • [7] Study of a two-bed silica gel-water adsorption chiller: performance analysis
    Sah, Ramesh P.
    Choudhury, Biplab
    Das, Ranadip K.
    INTERNATIONAL JOURNAL OF SUSTAINABLE ENERGY, 2018, 37 (01) : 30 - 46
  • [8] ANALYSIS OF PERFORMANCE EFFECT OF HEAT SOURCE TEMPERATURE ON SILICA GEL-WATER ADSORPTION CHILLER
    Ma, Xinling
    Wei, Xinli
    Meng, Xiangrui
    Yao, Yao
    PROCEEDINGS OF THE INTERNATIONAL CONFERENCE ON POWER ENGINEERING 2009 (ICOPE-09), VOL 3, 2009, : 163 - 165
  • [9] Performance evaluation of a solar adsorption chiller under different climatic conditions
    Alahmer, Ali
    Wang, Xiaolin
    Al-Rbaihat, Raed
    Alam, K. C. Amanul
    Saha, B. B.
    APPLIED ENERGY, 2016, 175 : 293 - 304
  • [10] Experimental investigation on the optimal performance of Zeolite-water adsorption chiller
    Myat, Aung
    Choon, Ng Kim
    Thu, Kyaw
    Kim, Young-Deuk
    APPLIED ENERGY, 2013, 102 : 582 - 590