Non-Unit Ultra-High-Speed DC Line Protection Method for HVDC Grids Using First Peak Time of Voltage

被引:33
|
作者
Zhang, Chenhao [1 ]
Song, Guobing [1 ]
Dong, Xinzhou [2 ]
机构
[1] Xi An Jiao Tong Univ, Dept Elect Engn, Xian 710049, Shaanxi, Peoples R China
[2] Tsinghua Univ, Dept Elect Engn, State Key Lab Control & Simulat Power Syst & Gene, Beijing 100084, Peoples R China
关键词
Circuit faults; HVDC transmission; Impedance; Inductors; Fault detection; Sensitivity; Power transmission lines; First peak time of line-mode fault component voltage; high sensitivity; HVDC grid; ultra-high-speed dc line protection; FAULT-DETECTION; SYSTEMS;
D O I
10.1109/TPWRD.2020.3013021
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The high-speed and selective dc line protection method is required for the safe operation of HVDC grids. In this paper, the expressions of the line-mode fault component voltage at the line end as well as its first peak time (FPT) when different internal and external faults occur are derived respectively. The conclusion proves that the FPT of line-mode fault component voltage for internal faults is smaller than that for backward and forward external faults, which is independent of fault impedance and fault type as well. Then a FPT-based non-unit ultra-high-speed dc line protection method for HVDC grids is proposed. The algorithm is verified by a four terminal +/- 400 kV MMC-HVDC grid PSCAD test model as well as implemented in the developed protection device and validated by the Zhangjiakou-Beijing MMC-HVDC grid RTDS test system. The test results show that i) the FPT-based protection algorithm is independent of fault impedance and fault type, ii) the proposed method can fast and correctly identify dc line faults in the HVDC grids, even with 500 omega fault impedance, and iii) the sensitivity and fault identification time of the proposed method meet the engineering requirement of MMC-HVDC grids for dc line protection.
引用
收藏
页码:1683 / 1693
页数:11
相关论文
共 32 条
  • [21] Non-unit protection method for flexible DC transmission line based on traveling wave difference of mode component
    Jia K.
    Yao K.
    Liu Z.
    Liu K.
    Zhang T.
    Bi T.
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2023, 43 (10): : 112 - 120
  • [22] Ultra-High-Speed Transmission Line Differential Protection using an Error Index of Bergeron Equation
    Quispe, H. Juan Carlos
    Morales, John
    Orduna, Eduardo
    IEEE LATIN AMERICA TRANSACTIONS, 2021, 19 (07) : 1182 - 1190
  • [23] High-speed non-unit transmission line protection using single-phase measurements and an adaptive wavelet: zone detection and fault classification
    Perez, F. E.
    Aguilar, R.
    Orduna, E.
    Jaeger, J.
    Guidi, G.
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2012, 6 (07) : 593 - 604
  • [24] Simplified calculation method of threshold value for the non-unit transient-voltage based protection in multi-terminal VSC-HVDC grid
    He, Jiawei
    Li, Bin
    Li, Ye
    Wang, Wenbo
    Lyu, Huijie
    Li, Botong
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2022, 134
  • [25] Principle of Non-unit Traveling Wave Protection for VSC-HVDC Transmission Line Using Fault Current Initial Traveling Wave Fitting
    Zhang C.
    Song G.
    Dong X.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2021, 41 (08): : 2651 - 2660
  • [26] Non-unit protection scheme for flexible DC transmission lines based on fitting the rate of change of line-mode voltage reverse traveling waves
    Zhang, Qixuan
    Li, Haifeng
    Liu, Hainan
    Wang, Zhijie
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2025, 164
  • [27] Non-unit wavelet transform-based protection principle for modular multi-level converter-based HVDC grids using adaptive threshold setting
    Marvasti, Farzad Dehghan
    Mirzaei, Ahmad
    Bakhshi-Jafarabadi, Reza
    Popov, Marjan
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2024, 163
  • [28] A sensitive single-end DC line fault detection method for MMC-HVDC grids using reactor voltage ratio
    Yu, Senlin
    Wang, Xiaoru
    Zhang, Xiao-Ping
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2023, 148
  • [29] Single-ended DC line protection scheme based on first peak time of current-limiting reactor voltage
    Wei, Xiuyan
    Zou, Guibin
    Chen, Chaochao
    Zhang, Shuo
    Zhou, Chenghan
    Song, Shenglan
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2023, 150
  • [30] Ultra-High-Speed Travelling Wave Protection of Transmission Line Using Polarity Comparison Principle Based on Empirical Mode Decomposition
    Wang, Dong
    Gao, Houlei
    Luo, Sibei
    Zou, Guibin
    MATHEMATICAL PROBLEMS IN ENGINEERING, 2015, 2015