Assessment of LVRT Requirements and Dynamic Behavior of a Mixed PMSG/DFIG Wind Power Plant

被引:1
|
作者
Ribeiro, Renata [1 ]
Boeira, Rafael [1 ]
Leborgne, Roberto Chouhy [1 ]
de Oliveira, Roger Alves [2 ]
Bollen, Math H. J. [2 ]
机构
[1] Univ Fed Rio Grande do Sul, Porto Alegre, RS, Brazil
[2] Lulea Univ Technol, Elect Power Engn Grp, Skelleftea, Sweden
关键词
Power Quality; Voltage Dip; LVRT; FRT; Wind Power; DFIG; PMSG; FED INDUCTION GENERATOR; TURBINES;
D O I
10.1109/TDLA47668.2020.9326154
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This work assesses the low voltage ride-through requirements and the dynamic behavior of a mixed PMSG/ DFIG wind power plant. Previous works in the literature applied voltage dips seen at the Point of Common Coupling (PCC) of the wind power plant (WPP) directly, which means that the propagation from the transmission grid to the low-voltage level was not considered. This work aims to show the expected operation of a wind power plant when submitted to voltage dips caused by faults at the transmission level, i.e considering the propagation. Equivalent models of a transmission system and a wind power plant were used to generate five types of dips and to access the behavior of the WPP during these events. The results show the expected ranges during the voltage dips for the active power of the generators as well as for overvoltages and overcurrents of the converters.
引用
收藏
页数:6
相关论文
共 50 条
  • [41] Inertial Response Identification Algorithm for the Development of Dynamic Equivalent Model of DFIG-Based Wind Power Plant
    Hu, Yi-Liang
    Wu, Yuan-Kang
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2021, 57 (03) : 2104 - 2113
  • [42] Inertial Response Identification Algorithm for Development of Dynamic Equivalent Model of DFIG-based Wind Power Plant
    Hu, Yi-Liang
    Wu, Yuan-Kang
    2020 IEEE INDUSTRY APPLICATIONS SOCIETY ANNUAL MEETING, 2020,
  • [43] Direct method for transient stability assessment of a single wind turbine generator subject to LVRT requirements
    Sohn, Alexandre Prodossimo
    Abrantes, Adriano Lima
    Costa Alberto, Luis Fernando
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2020, 14 (25) : 6195 - 6206
  • [44] A Improved LVRT Control Strategy Based on active and reactive power for direct-drive PMSG Wind Generation System
    Yang, Guoliang
    Liu, Shuoyang
    Chang, Xinyan
    Zhang, Enbei
    THERMAL, POWER AND ELECTRICAL ENGINEERING, PTS 1 AND 2, 2013, 732-733 : 1184 - 1187
  • [46] Rapid LVRT Control of a DFIG-Based Wind Power Plants Based on Adaptive IQ-V Characteristics
    Thapa, Khagendra
    Jayasawal, Kishan
    Marasini, Ganesh
    2018 IEEE INTERNATIONAL CONFERENCE ON POWER ELECTRONICS, DRIVES AND ENERGY SYSTEMS (PEDES), 2018,
  • [47] Direct Power Control of a DFIG in Wind Turbines to Improve Dynamic Responses
    Jou, Sung-Tak
    Lee, Sol-Bin
    Park, Yong-Bae
    Lee, Kyo-Beum
    JOURNAL OF POWER ELECTRONICS, 2009, 9 (05) : 781 - 790
  • [48] Impact of SCIG, DFIG Wind Power Plant on IEEE 14 Bus System with Small Signal Stability Assessment
    Chandra, D. Rakesh
    Kumari, M. Sailaja
    Sydulu, M.
    Grimaccia, F.
    Mussetta, M.
    Leva, S.
    Duong, M. Q.
    2014 EIGHTEENTH NATIONAL POWER SYSTEMS CONFERENCE (NPSC), 2014,
  • [49] Nine-Switch-Converter-Based DFIG Wind Power System and Its Dynamic Dc Voltage Assigned Approach for Low Voltage Riding Through (LVRT)
    Wen, Gang
    Chen, Yu
    Zhong, Zhihao
    Kang, Yong
    2014 IEEE ENERGY CONVERSION CONGRESS AND EXPOSITION (ECCE), 2014, : 4599 - 4605
  • [50] Dynamic performance assessment of DFIG-based wind turbines: A review
    Rahimi, Mohsen