The impact of the aging of intumescent fire protective coatings on fire resistance

被引:30
|
作者
Maciulaitis, R. [1 ]
Grigonis, M. [2 ]
Malaiskiene, J. [3 ]
机构
[1] Vilnius Gediminas Tech Univ, Vilnius, Lithuania
[2] UAB Kiwa Inspecta, Conform Assessment Dept, Vilnius, Lithuania
[3] Vilnius Gediminas Tech Univ, Inst Bldg Mat, Lab Composite Mat, Vilnius, Lithuania
关键词
Fire protective coatings; Steel; Aging; Simulated operating conditions; Atmospheric factors; PAINTS; TESTS;
D O I
10.1016/j.firesaf.2018.03.007
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The paper is aimed at determining fire resistance of various intumescent fire protective coatings intended for the protection of steel structures dependently on the simulated operating conditions and atmospheric factors having affected the materials for a certain period. Fire resistance was determined upon applying four methods. The first of them was a method of theoretical calculations. The other methods were experimental ones: a) the fire resistance was established upon using samples of steel double-T profiles covered with fire protective coatings; b) the fire resistance was established after aging the samples at a laboratory upon applying the cyclic freezing-thawing; and c) the fire resistance was established after aging the samples in outdoor shed for 12 months with subsequent heating of the samples according to the standard methodology. The statistical analysis of the obtained fire resistance data shows that there was practically no connection between the values of indicators of fire resistance of non-aged samples calculated theoretically and determined in the experimental way and the indicators of fire resistance of aged samples. The mechanism of material aging taking place as a result of simulated operating and climatic factors is similar for all coatings. However, different coatings are differently affected by aging due to their composition and complexity of the structure. Thus forecasting the fire resistance indicators for different coatings after their aging on the base of the values of the primary fire resistance indicator is impossible. However, a strong link had been obtained and an equation usable for forecasting the fire resistance time (determined according to the standard ISO 834 fire curve) after 12 months of operation of the coating in the outdoor shed according to the results of fire resistance of intumescent fire protective coatings after 60 artificial aging cycles at the laboratory had been deduced.
引用
收藏
页码:15 / 23
页数:9
相关论文
共 50 条
  • [31] Weathering of intumescent coatings for passive fire protection
    Jimenez, Maude
    Bellayer, Severine
    Duquesne, Sophie
    Bourbigot, Serge
    ABSTRACTS OF PAPERS OF THE AMERICAN CHEMICAL SOCIETY, 2014, 248
  • [32] NOVEL FIRE RETARDANT INTUMESCENT COATINGS.
    Blair, N.D.
    Witschard, G.
    Hindersinn, R.R.
    1600, (44):
  • [33] Intumescent Coatings Based on Tannins for Fire Protection
    da Silveira, Mauro Ricardo
    Peres, Rafael Silveira
    Moritz, Vicente Froes
    Ferreira, Carlos Arthur
    MATERIALS RESEARCH-IBERO-AMERICAN JOURNAL OF MATERIALS, 2019, 22 (02):
  • [34] Characterization of the performance of an intumescent fire protective coating
    Jimenez, M.
    Duquesne, S.
    Bourbigot, S.
    SURFACE & COATINGS TECHNOLOGY, 2006, 201 (3-4): : 979 - 987
  • [35] Fire protection of wood with intumescent coatings and impregnation
    David, Enczel
    Eva, Lubloy
    Istvan, Bodi
    EPITOANYAG-JOURNAL OF SILICATE BASED AND COMPOSITE MATERIALS, 2012, 64 (3-4): : 68 - 70
  • [36] Assessment of the thermal conductivity of intumescent coatings in fire
    Cirpici, Burak Kaan
    Wang, Y. C.
    Rogers, B.
    FIRE SAFETY JOURNAL, 2016, 81 : 74 - 84
  • [37] Evaluation of intumescent coatings for shipboard fire protection
    Sorathia, U
    Gracik, T
    Ness, J
    Durkin, A
    Willlams, F
    Hunstad, M
    Berry, F
    JOURNAL OF FIRE SCIENCES, 2003, 21 (06) : 423 - 450
  • [38] Fire resistance of waterborne intumescent fire-retardant coatings reinforced by fly ash-chitosan composites
    Sun, Zhao
    Jin, Yijie
    Yan, Han
    Duan, Haitao
    Zhan, Shengpeng
    Yu, Hualong
    Chen, Ao
    Jia, Dan
    Fuhe Cailiao Xuebao/Acta Materiae Compositae Sinica, 2025, 42 (02): : 1061 - 1070
  • [39] Latest trends for structural steel protection by using intumescent fire protective coatings: a review
    Yasir, Muhammad
    Ahmad, Faiz
    Yusoff, Puteri Sri Melor Megat
    Ullah, Sami
    Jimenez, Maude
    SURFACE ENGINEERING, 2020, 36 (04) : 334 - 363
  • [40] Flame retardancy and crack resistance of transparent intumescent fire-resistive coatings
    Hong, Ling
    Hu, Xiaoxian
    Rao, Weiwei
    Zhang, Xiaoping
    JOURNAL OF APPLIED POLYMER SCIENCE, 2015, 132 (35)