Termination control temperature study for an air source heat pump unit during its reverse cycle defrosting

被引:16
|
作者
Song Mengjie [1 ]
Wang Xuanjie [2 ]
Liao Liyuan [1 ]
Deng Shiming [3 ]
机构
[1] Guangdong Univ Technol, Sch Mat & Energy, Dept Energy Engn, Guangzhou, Guangdong, Peoples R China
[2] Hong Kong Univ Sci & Technol, Dept Mech & Aerosp Engn, Kowloon, Hong Kong, Peoples R China
[3] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Kowloon, Hong Kong, Peoples R China
基金
中国国家自然科学基金;
关键词
Air source heat pump; Multi-circuit outdoor coil; Reverse cycle defrosting; Defrosting termination temperature; Experimental study; CIRCUIT OUTDOOR COIL; FROSTING EVENNESS VALUES; HOT-GAS BYPASS; MELTED FROST; THERMAL COMFORT; LOCAL DRAINAGE; PERFORMANCE; FLOW; EVAPORATORS; SURFACE;
D O I
10.1016/j.egypro.2017.03.323
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
For an air source heat pump (ASHP) unit with a vertically installed multi-circuit outdoor coil, a reverse cycle defrosting (RCD) operation is always terminated when the tube surface temperature at the exit of the lowest circuit reaches a pre-set value. It is obviously that when the pre-set temperature is higher, the defrosting duration would be prolonged. Not only more energy would be consumed on heating cold ambient air, but also the occupants' thermal comfort adversely affected. However, if the pre-set temperature is lower, more residual water would be left on the downside surface of fin in an outdoor coil, which degrades the system performance during the next frosting/defrosting cycle. In order to find a suitable DTT or its range, in this paper, an experimental investigation on RCD operation for an ASHP unit with a multi-circuit outdoor coil was conducted and reported. As concluded, DTT is suitable at the range of 20-25 degrees C, around 22 degrees C. (C) 2017 The Authors. Published by Elsevier Ltd.
引用
收藏
页码:335 / 342
页数:8
相关论文
共 50 条
  • [41] An experimental study on defrosting performance for an air source heat pump unit with a horizontally installed multi-circuit outdoor coil
    Song Mengjie
    Deng Shiming
    Mao Ning
    Ye Xianming
    APPLIED ENERGY, 2016, 165 : 371 - 382
  • [42] Experimental Study on the Control of the Positions of the Cycle Isotherms of the Heat Pump in the Air Handling Unit
    Frik, Anton
    Bielskus, Juozas
    Dzikevics, Mikelis
    ENVIRONMENTAL AND CLIMATE TECHNOLOGIES, 2023, 27 (01) : 889 - 899
  • [43] AN EXPERIMENTAL STUDY ON PERFORMANCE IMPROVEMENT FOR AN AIR SOURCE HEAT PUMP BY ALTERNATE DEFROSTING OF OUTDOOR HEAT EXCHANGER
    Jung, Hoon
    Hwang, Jungho
    Jeon, Changduk
    INTERNATIONAL JOURNAL OF AIR-CONDITIONING AND REFRIGERATION, 2014, 22 (03)
  • [44] Energy transfer procession in an air source heat pump unit during defrosting with melted frost locally drainage in its multi-circuit outdoor coil
    Song, Mengjie
    Dang Chaobin
    Ning, Mao
    Deng Shiming
    ENERGY AND BUILDINGS, 2018, 164 : 109 - 120
  • [45] An experimental study on improving defrosting performances of air source heat pump unit based on hot-gas bypass method
    Zhang, Long
    Song, Mengjie
    Shen, Jun
    Jiang, Yiqiang
    Chao, Christopher Yu Hang
    INTERNATIONAL JOURNAL OF GREEN ENERGY, 2023, 20 (12) : 1363 - 1373
  • [46] An experimental study on frosting and defrosting performances of a novel air source heat pump unit with a radiant-convective heating terminal
    Zhang, Long
    Dong, Jiankai
    Jiang, Yiqiang
    Deng, Shiming
    Huang, Shun
    ENERGY AND BUILDINGS, 2018, 163 : 10 - 21
  • [47] Defrosting start control strategy optimization for an air source heat pump unit with the frost accumulation and melted frost downwards flowing considered
    Song Mengjie
    Wang Zhihua
    Mao Ning
    Dong Jiankai
    Zhang Haoran
    SUSTAINABLE CITIES AND SOCIETY, 2019, 46
  • [48] An experimental study on the operating performance of a novel reverse-cycle hot gas defrosting method for air source heat pumps
    Hu Wenju
    Jiang Yiqiang
    Qu Minglu
    Ni Long
    Yao Yang
    Deng Shiming
    APPLIED THERMAL ENGINEERING, 2011, 31 (2-3) : 363 - 369
  • [49] A modeling study on the revere cycle defrosting of an air source heat pump with the melted frost downwards flowing away and local drainage
    Song, Mengjie
    Xie, Gongnan
    Pekar, Libor
    Mao, Ning
    Qu, Minglu
    ENERGY AND BUILDINGS, 2020, 226
  • [50] An investigation on the efficient reverse cycle defrosting strategy for microchannel heat exchanger heat pump system
    Xiong, Tong
    Liu, Guoqiang
    Wang, Siyuan
    Yan, Gang
    Yu, Jianlin
    JOURNAL OF BUILDING ENGINEERING, 2023, 71