Study on Aging Assessment Model of Transformer Cellulose Insulation Paper Based on Methanol in Oil

被引:15
|
作者
Chen, Qingguo [1 ]
Li, Chunpeng [1 ]
Cheng, Song [1 ]
Sun, Wei [1 ,2 ]
Chi, Minghe [1 ]
Zhang, He [1 ]
机构
[1] Harbin Univ Sci & Technol, Sch Elect & Elect Engn, Key Lab Engn Dielect & Its Applicat, Minist Educ, Harbin 150080, Peoples R China
[2] State Grid Heilongjiang Elect Power Co Ltd, Elect Power Res Inst, Harbin 150030, Peoples R China
基金
中国国家自然科学基金;
关键词
Methanol; Aging; Oils; Moisture; Temperature; Power transformer insulation; Oil insulation; Aging assessment model; degree of polymerization (DP); insulation paper; methanol; moisture; temperature; CHAIN-END GROUPS; PART; FURANIC COMPOUNDS; DEGRADATION; KINETICS; DEPOLYMERIZATION; EQUATIONS; ETHANOL; MARKERS; DP;
D O I
10.1109/TDEI.2022.3157900
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Methanol is considered to be a new chemical marker to estimate the aging state of transformer cellulose insulation paper. The key to improve the assessment accuracy is to establish the precise relationship between the concentration of methanol in oil and degree of polymerization (DP) of insulation paper. The previous research in this area has shortcomings and needs to be further improved. In this article, first, an aging assessment basic model (temperature 20 degrees C, moisture content of insulation paper 0.637%) is established based on the theoretical derivation of cellulose degradation kinetics, and is calculated by 130 degrees C thermal aging experiment. Furthermore, the effects of different temperatures (20 degrees C-90 degrees C) and moisture contents of insulation paper (0.6%-3.4%) on methanol in oil are studied by diffusion experiment. Based on the above effects, the temperature and moisture correction factors are established by mathematical reduction. What is more, a modified model is proposed by integrating the basic model and the correction factors. Eventually, the verification experiment is randomly prepared to test the accuracy of modified model and the result shows that the relative error of DP is within 7%. The physical meaning and accuracy of aging assessment are improved by model derivation and modification of influencing factors.
引用
收藏
页码:591 / 598
页数:8
相关论文
共 50 条
  • [41] The Research of Methanol Generation in Aging Paper Insulation
    Darian, L. A.
    Obraztsov, R. M.
    Maksimchenko, A. V.
    Le, L. K.
    SPECIAL ISSUE OF THE 4TH INTERNATIONAL COLLOQUIUM -TRANSFORMER RESEARCH AND ASSET MANAGEMENT, 2017, 202 : 13 - 19
  • [42] Study on the Aging Characteristics of Insulation Oil of UHVDC Converter Transformer
    Liu C.
    Shao S.
    Liao R.
    Yang L.
    Cheng L.
    Gaodianya Jishu/High Voltage Engineering, 2019, 45 (03): : 730 - 736
  • [43] Condition Assessment of Oil-paper Insulation used in Power Transformer based on Polarization Energy
    Mukherjee, M.
    Pradhan, A. K.
    Baral, A.
    Chakravorti, S.
    2015 International Conference on Condition Assessment Techniques in Electrical Systems (CATCON), 2015, : 222 - 225
  • [44] Methanol in Oil Interpretation Model Based on Transformer Post-Mortem Paper Analysis
    Jalbert, Jocelyn
    Rajotte, Claude
    Lessard, Marie-Claude
    Rodriguez-Celis, Mariela
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2018, 25 (02) : 568 - 573
  • [45] Study on aging characteristics of transformer oil-paper insulation based on the time domain dielectric spectroscopy and depolarization charge quantity
    Wu G.
    Song Z.
    Yang F.
    Chen M.
    Gao B.
    Wu, Guangning (gnwu@home.swjtu.edu.cn), 1600, Science Press (43): : 195 - 202
  • [46] Study on Thermal Aging Condition Assessment of Oil-Paper Insulation Based on Statistical Features of Partial Discharge
    Liao, Rui-jin
    Wang, Ke
    Yang, Li-jun
    Zhou, Tian-chun
    Zheng, Sheng-xun
    ICPADM 2009: PROCEEDINGS OF THE 9TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1-3, 2009, : 325 - 328
  • [47] Discharges in combined transformer oil/paper insulation
    SINTEF Energy Research, Trondheim, Norway
    IEEE Int Conf Conduct Breakdown Dielectr Liq ICDL, (144-147):
  • [48] Influence of the copper ion on aging rate of oil-paper insulation in a power transformer
    Liao, R. -J.
    Tang, C.
    Yang, L. -J.
    Feng, Y.
    Sun, C. -X.
    IET ELECTRIC POWER APPLICATIONS, 2009, 3 (05) : 407 - 412
  • [49] Aging Characteristics of Transformer Oil-paper Insulation Under Continuous Lightning Impulses
    Cheng X.
    Tao X.
    Ye G.
    Chen J.
    Chang H.
    Li T.
    Gaodianya Jishu/High Voltage Engineering, 2023, 49 (05): : 1958 - 1966
  • [50] The Influence of Organic Acid on Thermal Aging of Power Transformer Oil-paper Insulation
    Cui Yunguang
    Wu Guangning
    Wang Xiaojian
    Peng Qian
    Chen Ling
    Gao Bo
    2013 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP), 2013, : 116 - 119