Condition assessment of XLPE insulated cables using isothermal relaxation current technique

被引:0
|
作者
Oyegoke, Bolarin S. [1 ]
Foottit, Frith [1 ]
Birtwhistle, David [1 ]
Lyall, Jim [1 ]
Wickramasuriya, Prasanna B. [2 ]
机构
[1] Queensland Univ Technol, Brisbane, Qld 4001, Australia
[2] Ergon Energy, Virginia, Australia
关键词
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The Isothermal Relaxation Current (IRC) method of assessing the condition of power cable insulation has been in use for more than 10 years. The method is based on a relaxation model of the thermal release of carriers from traps. An empirical aging factor often called A-factor determined from IRC analysis is investigated using measured depolarization currents from laboratory and field aged cables. Measurement results presented here indicate that calculation of A-factor depends on how well the software of the measuring system in IRC test set is able to approximate the measured depolarization current data. It is found that wrong approximation of measured data may result especially when the current decay is not monotonically decaying with time. For a better use of this equipment it is propose that the user make use of the raw depolarization current data instead of the A-factor output from the test system.
引用
收藏
页码:4339 / +
页数:2
相关论文
共 50 条
  • [1] Improved condition assessment of XLPE insulated cables using the isothermal relaxation current technique
    Oyegoke, B. S.
    2006 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2006, : 477 - 480
  • [2] The Condition Assessment System of XLPE Cables Using the Isothermal Relaxation Current Technique
    Wu, Jiandong
    Yin, Yi
    Li, Xuguang
    Wang, Yaqun
    Xiao, Dengming
    ICPADM 2009: PROCEEDINGS OF THE 9TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1-3, 2009, : 1114 - 1117
  • [3] Condition Assessment of XLPE Insulated Cables Based on Polarization/Depolarization Current Method
    Ye, Gang
    Li, Hua
    Lin, Fuchang
    Tong, Jin
    Wu, Xiaogang
    Huang, Zeqi
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2016, 23 (02) : 721 - 729
  • [4] Condition Assessment of XLPO Insulated Photovoltaic Cables Based on Polarisation/Depolarisation Current
    Afia, Ramy S. A.
    Mustafa, Ehtasham
    Tamus, Zoltan Adam
    2020 INTERNATIONAL CONFERENCE ON DIAGNOSTICS IN ELECTRICAL ENGINEERING, DIAGNOSTIKA, 2020, : 247 - 250
  • [5] Condition assessment of 15 kV rejuvenated underground XLPE cables
    Ogawa, Lisa E.
    Abdolall, Kal
    Stephens, Mike J.
    Smith, Brent
    CONFERENCE RECORD OF THE 2008 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, VOLS 1 AND 2, 2008, : 698 - +
  • [6] Water treeing and condition assessment of high voltage XLPE cables
    Hvidsten, S
    Faremo, H
    Eriksson, R
    Min, W
    CONFERENCE RECORD OF THE 2002 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, 2002, : 112 - 115
  • [7] Experience from on-site condition assessment of XLPE MV cables
    Skjolberg, Johan
    Hvidsten, Sverre
    Farmeo, Hallvard
    CONFERENCE RECORD OF THE 2006 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, 2006, : 432 - +
  • [8] The Application of Partial Discharge Detection for the condition assessment of XLPE Power Cables
    Zhou, Xiaoli
    Qian, Yong
    Liu, Muqing
    PRZEGLAD ELEKTROTECHNICZNY, 2012, 88 (06): : 313 - 316
  • [9] Condition Assessment of DC XLPE Cables Based on Combination Weighting Method
    Zhu, Yufeng
    Wang, Siyuan
    Li, Cong
    Xu, Yongpeng
    Sheng, Gehao
    Jiang, Xiuchen
    PROCEEDINGS OF THE 21ST INTERNATIONAL SYMPOSIUM ON HIGH VOLTAGE ENGINEERING, VOL 1, 2020, 598 : 449 - 457
  • [10] Research on aging parameters of XLPE cable based on isothermal relaxation current
    Zhao, Ai-xuan
    Xu, Long
    Zhang, Xing
    Deng, Jun-bo
    Zhang, Guan-Jun
    Zhao, Xue-Feng
    AIP ADVANCES, 2018, 8 (07)