Countermeasures on preventing backup protection mal-operation during load flow transferring

被引:7
|
作者
Lin, Xiangning [1 ]
Yu, Kun [1 ]
Tong, Ning [1 ]
Li, Zhengtian [1 ]
Khalid, Muhammad Shoaib [1 ]
Huang, Jingguang [2 ]
Li, Zhongqing [3 ]
Zhang, Rui [4 ]
机构
[1] Huazhong Univ Sci & Technol, State Key Lab Adv Electromagnet Engn & Technol, Wuhan 430074, Peoples R China
[2] Three Gorges Univ, Coll Elect Engn & New Energy, Yichang 443002, Peoples R China
[3] China Elect Power Res Inst, Beijing 100192, Peoples R China
[4] State Power Econ Res Inst, Beijing 100761, Peoples R China
基金
中国国家自然科学基金;
关键词
Backup protection; Load flow transferring; Cascading trip; Adaptive adjustment;
D O I
10.1016/j.ijepes.2015.12.027
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Removal of transmission lines in power systems may result in load flow transferring and unreasonable operations of backup protections, which may develop into cascading tripping accidents and even blackouts. Traditional backup protection based on local measurement information has disadvantages in preventing from cascading trip because it cannot distinguish the over load reason between due to faults and due to load flow transferring. On the premise that the load flow transferring can be identified based on wide-area coordination system, concise adaptive adjustment methods for the operation characteristics of zone III distance protection and overcurrent protections are proposed to avoid the maloperation caused by load flow transferring. Meanwhile, their backup protection functionality can be reserve to a great extent. The simulation test results illustrate the validity of the proposed method. (C) 2015 Elsevier Ltd. All rights reserved.
引用
收藏
页码:27 / 33
页数:7
相关论文
共 44 条
  • [21] Study on preventing mal-operation on lock system in concentration control station by micro-computer
    Tan, Yue-Kai
    Li, Sheng-Li
    Gaoya Dianqi/High Voltage Apparatus, 2002, 38 (03):
  • [22] Wide Area Protection Scheme Preventing Cascading Events Caused by Load Flow Transferring
    Liu, Zhou
    Chen, Zhe
    Sun, Haishun
    Hu, Yanting
    2013 IEEE POWER AND ENERGY SOCIETY GENERAL MEETING (PES), 2013,
  • [23] New algorithm based on the mathematical morphology for avoiding mal-operation of transformer differential protection
    Zheng, Tao
    Liu, Wan-Shun
    Liu, Jian-Fei
    Xiao, Shi-Wu
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2005, 25 (20): : 6 - 11
  • [24] A New Algorithm Based on the Morphological Gradient for Avoiding Mal-operation of Transformer Differential Protection
    Gu, J.
    Zheng, T.
    Huang, S. F.
    IEEE POWER AND ENERGY SOCIETY GENERAL MEETING 2010, 2010,
  • [25] Algorithm to Prevent Breaker-Failure Protection Mal-operation Due to Subsidence Current
    Jena, Soumitri
    Bhalja, Bhavesh R.
    Malik, Om P.
    2020 IEEE INDUSTRY APPLICATIONS SOCIETY ANNUAL MEETING, 2020,
  • [26] A method for preventing mal-operation of zero-sequence direction component using current fault component
    Song G.
    Xu H.
    Fan Z.
    Wang C.
    Xu, Haiyang (xuhaiyang.2009@stu.xjtu.edu.cn), 1600, Automation of Electric Power Systems Press (40): : 114 - 120
  • [27] Modular Supervisory Control of Computer Based Preventing Electric Mal-operation System for Multiple Bays in Substation
    Chao, Wujie
    Tang, Zhijun
    Lin, Guodong
    Guo, Jiansheng
    Lin, Wenbin
    Yu, Sihang
    PROCEEDINGS OF 2017 IEEE 2ND INFORMATION TECHNOLOGY, NETWORKING, ELECTRONIC AND AUTOMATION CONTROL CONFERENCE (ITNEC), 2017, : 1730 - 1739
  • [28] Analysis of a sort of unusual mal-operation of transformer differential protection due to removal of external fault
    Lin, Xiangning
    Weng, Hanli
    Liu, Pei
    Wang, Bin
    Bo, Zhiqian
    IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (03) : 1374 - 1379
  • [29] Substation Information Based Method for Preventing Mal-operation of Zero-sequence Directional Protection on Multi-circuit Transmission Lines on the Same Tower
    Dai F.
    Wang X.
    Yang G.
    Zhou Z.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2019, 43 (13): : 131 - 138
  • [30] Mal-operation risk assessment for the feeder overcurrent protection in large-scale clustering wind farms
    Tong, Ning
    Lin, Xiangning
    Li, Zhengtian
    Zhang, Rui
    Yang, Dexian
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2015, 71 : 26 - 32