Thermal comfort in chilled ceiling and displacement ventilation environments: Vertical radiant temperature asymmetry effects

被引:52
|
作者
Hodder, SG [1 ]
Loveday, DL [1 ]
Parsons, KC [1 ]
Taki, AH [1 ]
机构
[1] Loughborough Univ Technol, Dept Human Sci, Human Thermal Environm Lab, Loughborough LE11 3TU, Leics, England
关键词
chilled ceiling; displacement ventilation; radiant asymmetry;
D O I
10.1016/S0378-7788(97)00038-8
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The paper presents some of the findings from a broader investigation aimed at determining thermal comfort design conditions for combined chilled ceiling/displacement ventilation environments. A typical chilled ceiling/displacement ventilation office has been created within a laboratory test room, in which the ceiling temperature can be varied over a range of typical operating values; the thermal comfort of eight female test subjects was then measured in the test room over the range of ceiling temperatures. Vertical radiant temperature asymmetry was found to have an insignificant effect on the overall thermal comfort of the seated occupants for the typical range of ceiling temperatures that would be encountered in practice in such combination environments. Then was a slight trend for the reported sensation of 'freshness' to increase as ceiling temperature was reduced though this requires further study. It is concluded that existing guidance regarding toleration of radiant asymmetry is valid for thermal comfort design of chilled ceiling/displacement Ventilation environments. (C) 1998 Elsevier Science S.A.
引用
收藏
页码:167 / 173
页数:7
相关论文
共 50 条
  • [41] A novel operating strategy to avoid dew condensation for displacement ventilation and chilled ceiling system
    Guo, Shaopeng
    Tian, Yuchen
    Fan, Donghao
    Wu, Wenfei
    Zhao, Jun
    Jin, Guang
    Wang, Xiaotong
    APPLIED THERMAL ENGINEERING, 2020, 176
  • [42] Air quality in rooms conditioned by chilled ceiling and mixed displacement ventilation for energy saving
    Chakroun, W.
    Ghali, K.
    Ghaddar, N.
    ENERGY AND BUILDINGS, 2011, 43 (10) : 2684 - 2695
  • [43] Effect of horizontal radiant temperature asymmetry on thermal comfort and environmental parameters in a warm sitting area
    苏智群
    夏绍毅
    Journal of Harbin Institute of Technology, 2010, 17 (06) : 847 - 852
  • [44] Model-based optimal supervisory control of chilled ceiling displacement ventilation system
    Keblawi, A.
    Ghaddar, N.
    Ghali, K.
    ENERGY AND BUILDINGS, 2011, 43 (06) : 1359 - 1370
  • [45] Numerical investigation of transient buoyant flow in a room with a displacement ventilation and chilled ceiling system
    Rees, SJ
    McGuirk, JJ
    Haves, P
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2001, 44 (16) : 3067 - 3080
  • [46] Optimized Operation of Combined Chilled Ceiling Displacement Ventilation System Using Genetic Algorithm
    Mossolly, Mounir
    Ghaddar, Nesreen
    Ghali, Kamel
    Jensen, Lars
    ASHRAE TRANSACTIONS 2008, VOL 114, PT 2, 2008, 114 : 541 - +
  • [47] Numerical Comparison of Thermal Comfort and Air Age Between Two Combined Ventilation Systems with Chilled Ceiling Considering Occupant Density
    Nayyef, Dhuha Radhi
    Mahdi, Ala'a Abbas
    INTERNATIONAL JOURNAL OF HEAT AND TECHNOLOGY, 2023, 41 (01) : 213 - 223
  • [48] Experimental Evaluation of Radiant Heating Ceiling Systems Based on Thermal Comfort Criteria
    Safizadeh, M. Reza
    Schweiker, Marcel
    Wagner, Andreas
    ENERGIES, 2018, 11 (11)
  • [49] Effect of Supply Air Temperature on Indoor Thermal Comfort in a Room with Radiant Heating and Mechanical Ventilation
    Wu, Xiaozhou
    Liu, Yujia
    Liu, Genglin
    Wang, Fenghao
    Wang, Zhihua
    IMPROVING RESIDENTIAL ENERGY EFFICIENCY INTERNATIONAL CONFERENCE, IREE 2017, 2017, 121 : 206 - 213
  • [50] Experimental investigation of thermal comfort performance of a radiant wall and ceiling panel system
    Dogan, Ahmet
    Kayaci, Nurullah
    Demir, Hakan
    Sevindir, Mustafa Kemal
    JOURNAL OF THERMAL ENGINEERING, 2022, 8 (04): : 551 - 561