Transfer Characteristic of a MV/LV Transformer in the Frequency Range between 2 kHz and 150 kHz

被引:0
|
作者
Schoettke, Stefan [1 ]
Rademacher, Stephan [1 ]
Meyer, Jan [1 ]
Schegner, Peter [1 ]
机构
[1] Tech Univ Dresden, Inst Elect Power Syst & High Voltage Engn, Dresden, Germany
关键词
supraharmonics; transfer characteristic; frequency analysis; distribution transformer; higher frequency emission;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Switching frequencies of modern, energy-efficient power electronics are commonly located within the frequency range between 2 kHz and 150 kHz, also referred to as supraharmonics. Due to the increasing use of this equipment, rising emission levels and a rising number of interference cases have been observed recently. While first studies exist about the emission and interaction of equipment, little is known about the propagation of supraharmonics via cables and transformers. This paper presents recent research results in order to identify the transfer characteristic of a distribution transformer at higher frequencies based on measurements. After a description of the used transformer, the measurement setup and the performed measurements are described in detail. In order to provide test conditions, which are as close to reality as possible, a two-frequency test signal is used. The last part of the paper discusses the results of the measurements, covering injection on the MV and the LV side as well as single or three-phase supraharmonics among others. The results are quantified by indices representing the transfer (ratio between the same phases at both sides) and the coupling between different phases. The presented results provide a comprehensive basis for the development of respective simulation models.
引用
收藏
页码:114 / 119
页数:6
相关论文
共 50 条
  • [11] Electromagnetic interference examples of telecommunications system in the frequency range from 2kHz to 150kHz
    Murakawa, Kazuo
    Hirasawa, Norihito
    Ito, Hidenori
    Ogura, Yasunori
    2014 INTERNATIONAL SYMPOSIUM ON ELECTROMAGNETIC COMPATIBILITY, TOKYO (EMC'14/TOKYO), 2014, : 581 - 584
  • [12] EMC between communications Circuits and Power Systems in the frequency range 2-150 kHz
    Thomas, Dave
    2017 IEEE INTERNATIONAL SYMPOSIUM ON ELECTROMAGNETIC COMPATIBILITY & SIGNAL/POWER INTEGRITY (EMCSI), 2017,
  • [13] Study on the RFI noise reduction of the electric railway in the frequency range of 9 kHz to 150 kHz
    Kang, Yong-Sam
    Lee, Jongwoo
    Transactions of the Korean Institute of Electrical Engineers, 2013, 62 (09): : 1329 - 1334
  • [14] A correction method for the phase angle error of surface impedance measurements in the 2 kHz-150 kHz frequency range
    Mohos, Andras
    Ladanyi, Jozsef
    ELECTRIC POWER SYSTEMS RESEARCH, 2020, 186
  • [15] Overview and Classification of Interferences in the Frequency Range 2-150 kHz (Supraharmonics)
    Meyer, Jan
    Khokhlov, Victor
    Klatt, Matthias
    Blum, Juergen
    Waniek, Christian
    Wohlfahrt, Thomas
    Myrzik, Johanna
    2018 INTERNATIONAL SYMPOSIUM ON POWER ELECTRONICS, ELECTRICAL DRIVES, AUTOMATION AND MOTION (SPEEDAM), 2018, : 165 - 170
  • [16] Comparison of measurement methods for the frequency range 2-150 kHz (supraharmonics)
    Anne, Grevener
    Jan, Meyer
    Sarah, Ronnberg
    2018 IEEE 9TH INTERNATIONAL WORKSHOP ON APPLIED MEASUREMENTS FOR POWER SYSTEMS (AMPS), 2018, : 128 - 133
  • [17] Characterization of the Emission of an Electric Bus Inductive Charging in the 2 kHz to 150 kHz Range
    Lodetti, Stefano
    Bruna, Jorge
    Francisco Sanz, Jose
    Melero, Julio J.
    2019 AEIT INTERNATIONAL CONFERENCE OF ELECTRICAL AND ELECTRONIC TECHNOLOGIES FOR AUTOMOTIVE (AEIT AUTOMOTIVE), 2019,
  • [18] A New High Frequency Grid Impedance Estimation Technique for the Frequency Range of 2 to 150 kHz
    AlyanNezhadi, M. M.
    Hassanpour, H.
    Zare, F.
    INTERNATIONAL JOURNAL OF ENGINEERING, 2018, 31 (10): : 1666 - 1674
  • [19] System impedances and background noise in the frequency range 2 kHz to 9 kHz
    Gretsch, R
    Neubauer, M
    EUROPEAN TRANSACTIONS ON ELECTRICAL POWER, 1998, 8 (05): : 369 - 374
  • [20] Measurement of current taken by fluorescent lights in the frequency range 2-150 kHz
    Larsson, E. O. A.
    Lundmark, C. A.
    Bollen, M. H. J.
    2006 POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1-9, 2006, : 1231 - +