On-line Estimation of Transmission Line Parameters Using Synchronized Measurements

被引:14
|
作者
Al-Othman, Abdulrahman K. [1 ]
El-Naggar, Khaled M. [1 ]
AlSharidah, Michel E. [1 ]
机构
[1] Coll Technol Studies, Dept Elect Engn, Shuwaikh 73452, Kuwait
关键词
estimation; discrete filter; GPS; transmission lines; synchronized phasor measurements; on-line technique; line models; least absolute value minimization; line constants; two-port network;
D O I
10.1080/15325008.2015.1104564
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A new on-line method for estimating transmission line constants of a power system is proposed in this article. The method applies a digital dynamic filter technique to perform the estimation based on minimization of residual least absolute value. The proposed technique can be used on-line to account for any dynamics changes in line constants. Synchronized phasor measurements are used to feed the dynamic filter. The synchronized samples of voltage and current waveforms, at both the receiving and sending end terminals, are used to set an over-determined system of equations. The problem is formulated as an estimation problem. Different practical case studies are presented. Eventually, the proposed discrete dynamic filtering algorithm estimates the ABCD constants and, consequently, the line parameters of both short and long lines. Effects of different factors, such as noise and unsynchronized samples, are studied. Results obtained show the reliability and accuracy of the method in estimating the transmission line parameters.
引用
收藏
页码:233 / 239
页数:7
相关论文
共 50 条
  • [1] On-line estimation of transmission line parameters, temperature and sag using PMU measurements
    Du, Yan
    Liao, Yuan
    ELECTRIC POWER SYSTEMS RESEARCH, 2012, 93 : 39 - 45
  • [2] Estimation of Transmission Line Parameters Using PMU Measurements
    Asprou, Markos
    Kyriakides, Elias
    2015 IEEE POWER & ENERGY SOCIETY GENERAL MEETING, 2015,
  • [3] Calculation of transmission line parameters from synchronized measurements
    Wilson, RE
    Zevenbergen, GA
    Mah, DL
    Murphy, AJ
    ELECTRIC MACHINES AND POWER SYSTEMS, 1999, 27 (12): : 1269 - 1278
  • [4] Estimation of transmission line parameters from measurements
    Indulkar, C. S.
    Ramalingam, K.
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2008, 30 (05) : 337 - 342
  • [5] On-line Performance Monitoring of a Transmission Line using Synchrophasor Measurements
    de Jager, F. A.
    Rens, A. P. J.
    2015 IEEE EINDHOVEN POWERTECH, 2015,
  • [6] Accurate Kalman filter based estimation of transmission line parameters utilizing synchronized phasor measurements
    Moghanian, Mehrdad
    Dobakhshari, Ahmad Salehi
    ELECTRIC POWER SYSTEMS RESEARCH, 2024, 230
  • [7] Tracking Three-Phase Untransposed Transmission Line Parameters Using Synchronized Measurements
    Ren, Pengxiang
    Lev-Ari, Hanoch
    Abur, Ali
    IEEE TRANSACTIONS ON POWER SYSTEMS, 2018, 33 (04) : 4155 - 4163
  • [8] A robust method for transmission line sequence parameter estimation using synchronized phasor measurements
    Goklani, Hemantkumar
    Gajjar, Gopal
    Soman, S. A.
    ELECTRIC POWER SYSTEMS RESEARCH, 2023, 223
  • [9] On-line Overhead Transmission Line And Transformer Parameters Identification Based On PMU Measurements
    Vicol, Bogdan
    2014 INTERNATIONAL CONFERENCE AND EXPOSITION ON ELECTRICAL AND POWER ENGINEERING (EPE), 2014, : 1045 - 1050
  • [10] Identification and Estimation of Erroneous Transmission Line Parameters Using PMU Measurements
    Asprou, Markos
    Kyriakides, Elias
    2018 IEEE POWER & ENERGY SOCIETY GENERAL MEETING (PESGM), 2018,