Effects of vent shaft location on the ventilation performance in a subway tunnel

被引:75
|
作者
Kim, Jung-Yup [2 ]
Kim, Kwang-Yong [1 ]
机构
[1] Inha Univ, Dept Mech Engn, Inchon 402751, South Korea
[2] Korea Inst Construct Technol, Construct Qual Policy Dept, Koyang 411712, South Korea
基金
新加坡国家研究基金会;
关键词
Subway tunnel; Ventilation performance; Vent shaft; Train-induced flow; Numerical analysis; Moving boundary; Sharp interface method; CARTESIAN GRID METHOD; FLOWS;
D O I
10.1016/j.jweia.2009.06.002
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
A computational analysis of a ventilation system in a subway tunnel is carried out by solving 3D Reynolds-averaged Navier-Stokes equations for train-induced unsteady flow using the sharp interface method as the model for the moving boundary of an immersed solid. The ventilation performance is evaluated depending on the location of the vent shaft by analyzing the ventilating flow rate through the shaft and the feature of the flow field in the subway tunnel around the shaft. It is found that the optimum location of the vent shaft with respect to maximizing ventilation performance lies near the station. (C) 2009 Elsevier Ltd. All rights reserved.
引用
收藏
页码:174 / 179
页数:6
相关论文
共 50 条
  • [1] Influence of mechanical ventilation-shaft connecting location on subway tunnel ventilation performance
    Juraeva, Makhsuda
    Ryu, Kyung Jin
    Jeong, Sang-Hyun
    Song, Dong Joo
    JOURNAL OF WIND ENGINEERING AND INDUSTRIAL AERODYNAMICS, 2013, 119 : 114 - 120
  • [2] A Study on Optimization of Middle Vent Shaft in Subway Tunnel Ventilation System
    Lin, Fang
    Zeng, Yanhua
    Zhou, Xiaohan
    He, Jianfeng
    CIVIL, STRUCTURAL AND ENVIRONMENTAL ENGINEERING, PTS 1-4, 2014, 838-841 : 1381 - +
  • [3] Effects of the solid curtains on natural ventilation performance in a subway tunnel
    Huang, Yuan-dong
    Gong, Xiao-lu
    Peng, Yue-jiao
    Kim, Chang-Nyung
    TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2013, 38 : 526 - 533
  • [4] Effects of the ventilation duct arrangement and duct geometry on ventilation performance in a subway tunnel
    Huang Yuan-dong
    Gong Xiao-lu
    Peng Yue-jiao
    Lin Xiao-yu
    Chang-Nyung, Kim
    TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2011, 26 (06) : 725 - 733
  • [5] Study on underground tunnel ventilation for piston effects influenced by draught relief shaft in subway system
    Lin, Chi-Ji
    Chuah, Yew Khoy
    Liu, Chia-Wei
    APPLIED THERMAL ENGINEERING, 2008, 28 (5-6) : 372 - 379
  • [6] A Numerical Analysis of the Ventilation Performance for Different Ventilation Strategies in a Subway Tunnel
    Yuan-dong Huang
    Chan Li
    Chang Nyung Kim
    Journal of Hydrodynamics, 2012, 24 : 193 - 201
  • [7] A NUMERICAL ANALYSIS OF THE VENTILATION PERFORMANCE FOR DIFFERENT VENTILATION STRATEGIES IN A SUBWAY TUNNEL
    KIM Chang Nyung
    Journal of Hydrodynamics, 2012, 24 (02) : 193 - 201
  • [8] A NUMERICAL ANALYSIS OF THE VENTILATION PERFORMANCE FOR DIFFERENT VENTILATION STRATEGIES IN A SUBWAY TUNNEL
    Huang Yuan-dong
    Li Chan
    Kim, Chang Nyung
    JOURNAL OF HYDRODYNAMICS, 2012, 24 (02) : 193 - 201
  • [9] Effects of vertical shaft arrangement on natural ventilation performance during tunnel fires
    Fan, C. G.
    Ji, J.
    Wang, W.
    Sun, J. H.
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2014, 73 : 158 - 169
  • [10] The application of array silencer performance curve in subway tunnel ventilation system
    Hu, Zilin
    Fang, Qingchuan
    Journal of Railway Science and Engineering, 2022, 19 (06) : 1794 - 1800