Experimental testing of a passive, evaporation-based roof cooling system

被引:14
|
作者
Crawford, Robert [1 ]
da Silva, Alexandre K. [1 ]
机构
[1] Univ Texas Austin, Dept Mech Engn, Austin, TX 78712 USA
基金
美国国家科学基金会;
关键词
Bio-inspired cooling; Building cooling; Evaporative pumping; Heat removal; Porous membrane; PERFORMANCE;
D O I
10.1016/j.enbuild.2013.11.009
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In this paper, we study the capability of a roof based, passive, evaporative pumping system to lessen thermal loadings imposed on the interior of a building thus reducing air conditioning energy consumption. To do so, an instrumented experimental setup was constructed wherein a porous membrane rested on top of an air cooled copper plate while heated by a halogen lamp from above. From the membrane, water evaporated while drawing replenishment from a separated reservoir. The tests aimed to determine the ability of such a system to lessen roof temperatures and heat fluxes into the building compared to traditional (e.g., dark ethylene propylene diene monomer (EPDM)) and non-traditional roofs (e.g., white). The results indicated that the evaporation system considered kept the plate temperature of the test section considerably lower than competing options, for a typical summer day in Austin, TX. Additionally, with the use of reclaimed water in mind, the system's performance was evaluated under membrane fouling conditions, which was shown to affect the evaporation rate of the porous membrane. (C) 2013 Elsevier B.V. All rights reserved.
引用
收藏
页码:12 / 19
页数:8
相关论文
共 50 条
  • [1] Experimental Studies of a Passive Cooling Roof in Hot Arid Areas
    Ben Cheikh, Hamida
    SUSTAINABLE ARCHITECTURE AND URBAN DEVELOPMENT (SAUD 2010), VOL IV, 2010, : 203 - 212
  • [2] Effect of plants layout mode on passive cooling of photovoltaic module and roof, and water evaporation
    Zhang K.
    Ran M.
    Taiyangneng Xuebao/Acta Energiae Solaris Sinica, 2022, 43 (10): : 88 - 93
  • [3] EXPERIMENTAL STUDY ON PASSIVE EVAPORATION COOLING TECHNOLOGY OF WALLS IN GUANGZHOU
    Li, L.
    Zhao, L. H.
    Zhang, Z. P.
    Meng, Q. L.
    7TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATING AND AIR CONDITIONING, PROCEEDINGS OF ISHVAC 2011, VOLS I-IV, 2011, : 27 - 32
  • [4] An evaporation-based microfluidic sample concentration method
    Walker, GM
    Beebe, DJ
    LAB ON A CHIP, 2002, 2 (02): : 57 - 61
  • [5] Passive Cooling with Finned Roof Tiles
    Salem, Hayder
    Sedaghat, Ahmad
    Malayer, Mahdi Ashtian
    2023 7TH INTERNATIONAL CONFERENCE ON GREEN ENERGY AND APPLICATIONS, ICGEA, 2023, : 204 - 208
  • [6] Templated Droplet Evaporation-Based Supraparticles in Environmental Applications
    Dabodiya, Tulsi Satyavir
    Singh, Kapil Dev
    Verma, Ravikant
    Barman, Bittesh
    Zhang, Xuehua
    PARTICLE & PARTICLE SYSTEMS CHARACTERIZATION, 2024, 41 (03)
  • [7] COOLING BY WATER EVAPORATION OVER ROOF - REVIEW
    TIWARI, GN
    KUMAR, A
    SODHA, MS
    ENERGY CONVERSION AND MANAGEMENT, 1982, 22 (02) : 143 - 153
  • [8] An experimental investigation on passive and hybrid roof cooling systems with a double skin envelope
    Kumar, V. Vinod
    Raut, Nitin
    Akeel, Norie
    ENERGY SOURCES PART A-RECOVERY UTILIZATION AND ENVIRONMENTAL EFFECTS, 2021,
  • [9] Passive cooling effect of RC roof covered with the ceramics having high water retention and evaporation capacity
    Yamazaki, M.
    Kanaya, M.
    Shimazu, T.
    Ohashi, T.
    Kato, N.
    Horikoshi, T.
    3RD INTERNATIONAL CONGRESS ON CERAMICS (ICC3): INNOVATION IN REFRACTORIES AND TRADITIONAL CERAMICS, 2011, 18
  • [10] Roof ponds combined with a water-to-air heat exchanger as a passive cooling system: Experimental comparison of two system variants
    Manuel Almodovar, Jose
    La Roche, Pablo
    RENEWABLE ENERGY, 2019, 141 : 195 - 208