A line-interactive UPS system implementation with series-parallel active power-line conditioning for three-phase, four-wire systems

被引:22
|
作者
da Silva, SAO
Donoso-Garcia, P
Cortizo, PC
Seixas, PF
机构
[1] Univ Fed Minas Gerais, Dept Elect Engn, BR-31270901 Belo Horizonte, MG, Brazil
[2] CEFET PR, Dept Elect Engn, BR-86300000 Cornelio Procopio, PR, Brazil
关键词
active power filters; harmonics; uninterruptible power supply system; power factor correction; synchronous reference frame controller;
D O I
10.1016/j.ijepes.2003.11.008
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a three-phase line-interactive uninterruptible power supply (UPS) system with active series-parallel power-line conditioning capabilities. Synchronous reference frame (SRF)-based controller is used to harmonic and reactive power compensation generated from any configuration of non-linear load. Under normal line conditions the UPS system works with universal filtering capabilities, such as compensating the input currents and output voltages. Two three-phase pulse width inoculation (PWM) converters, called series and parallel active filters. are used to perform the series and parallel active power-line compensation. The series active power filter works as sinusoidal current source in phase with the input voltage, drawing from utility sinusoidal and balanced input currents with low total harmonic distortion (THD). The parallel active power filter works as sinusoidal voltage source in phase with the input voltage, providing regulated and sinusoidal Output voltages with low THD. Operation of a three-phase phase-locked loop (PLL) structure, used in the proposed line-interactive UPS implementation. is presented and experimentally verified under distorted utility conditions. The performance of the UPS system is evaluated in three-phase. four-wire systems. Digital simulations and experimental results are presented to confirm the theoretical studies. (C) 2004 Elsevier Ltd. All rights reserved.
引用
收藏
页码:399 / 411
页数:13
相关论文
共 50 条
  • [11] Study on dual-DSP-controlled three-phase series-parallel compensated line-interactive UPS system (delta-conversion UPS)
    Dai, K
    Liu, PG
    Xiong, J
    Chen, R
    IEEE IEMDC'03: IEEE INTERNATIONAL ELECTRIC MACHINES AND DRIVES CONFERENCE, VOLS 1-3, 2003, : 436 - 442
  • [12] Dynamic response improvement of a three-phase line interactive UPS system with active power line conditioning
    Oliveira da Silva, Srgio Augusto
    Modesto, Rodrigo A.
    Barbosa, Lucio dos Reis
    2007 IEEE POWER ELECTRONICS SPECIALISTS CONFERENCE, VOLS 1-6, 2007, : 1055 - 1059
  • [13] Performance investigation of a three-phase three-wire series-parallel compensated line-interactive UPS system based on SVPWM and controlled by two digital signal processors
    Dai, K
    Liu, PG
    Wang, GX
    Kang, Y
    Chen, H
    INTELEC'03: POWERING THE BROADBAND NETWORK, PROCEEDINGS, 2003, : 814 - 820
  • [14] Simple Reactive Power Control Method of an Active Power-Line Conditioner in Three-Phase Four-Wire Feeders
    Kihara, Yuya
    Hikosaka, Seita
    Yamada, Hiroaki
    Tanaka, Toshihiko
    Ikeda, Fuka
    Okamoto, Masayuki
    Lee, Seong Ryong
    2021 IEEE 12TH ENERGY CONVERSION CONGRESS AND EXPOSITION - ASIA (ECCE ASIA), 2021, : 1057 - 1062
  • [15] Harmonics Compensation in Three-Phase Four-Wire Distribution Feeders With a Four-Leg Structured Active Power-Line Conditioner
    Kihara, Yuya
    Hikosaka, Seita
    Yamada, Hiroaki
    Tanaka, Toshihiko
    Ikeda, Fuka
    Okamoto, Masayuki
    Lee, Seong Ryong
    IEEJ JOURNAL OF INDUSTRY APPLICATIONS, 2020, 9 (05) : 605 - 606
  • [16] Individual-Phase Displacement Power Factor Control Strategy of an Active Power-Line Conditioner in Three-Phase Four-Wire Distribution Feeders
    Sabi, Yuka
    Kihara, Yuya
    Yamada, Hiroaki
    Tanaka, Toshihiko
    Ikeda, Fuka
    Okamoto, Masayuki
    Lee, Seong Ryong
    2022 INTERNATIONAL POWER ELECTRONICS CONFERENCE (IPEC-HIMEJI 2022- ECCE ASIA), 2022, : 2207 - 2212
  • [17] Power Quality Compensator for Hybrid Three-phase Four-wire Distribution Network Based on Series-Parallel Structure
    Luo P.
    Xia L.
    Chen Y.
    Zhou G.
    Wang W.
    Xia, Ling (446896834@qq.com), 1600, Automation of Electric Power Systems Press (41): : 165 - 170
  • [18] Three-phase series-parallel double conversion UPS with power quality conditioning characteristics
    Zhu, PC
    Li, X
    Kang, Y
    Chen, J
    IPEMC 2004: THE 4TH INTERNATIONAL POWER ELECTRONICS AND MOTION CONTROL CONFERENCE, VOLS 1-3, CONFERENCE PROCEEDINGS, 2004, : 960 - 964
  • [19] A PWM strategy for four-leg voltage source converters and applications to a novel line interactive UPS in a three-phase four-wire system
    Kim, JH
    Sul, SK
    Kim, H
    Ji, JK
    CONFERENCE RECORD OF THE 2004 IEEE INDUSTRY APPLICATIONS CONFERENCE, VOLS 1-4: COVERING THEORY TO PRACTICE, 2004, : 2202 - 2209
  • [20] Active power filter used for three-phase four-wire system
    Zhuo, F
    Wang, Y
    Li, H
    Wang, Z
    ICEMS'2001: PROCEEDINGS OF THE FIFTH INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES AND SYSTEMS, VOLS I AND II, 2001, : 616 - 619