Impact of demand response for frequency regulation in two-area thermal power system

被引:31
|
作者
Singh, Vijay P. [1 ]
Samuel, Paulson [1 ]
Kishor, Nand [1 ]
机构
[1] Motilal Nehru Natl Inst Technol, Dept Elect Engn, Allahabad, Uttar Pradesh, India
关键词
communication delay; demand response (DR); particle swarm optimization (PSO); two-area power system; Pade approximation; CONTROLLER-DESIGN; LOAD; GENERATION; TIME; ALGORITHM;
D O I
10.1002/etep.2246
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In future power system operation, wide area monitoring applications will rely heavily on demand response (DR) because of its inherent characteristics mainly in ancillary services (AS). The DR is widely applied in power system; however, impact of DR loop with communication delay on dynamic performance of two-area power system, mainly load frequency control (LFC), have not been reported by researchers. This paper presents the impact of DR control loop with communication delay in two-area thermal power systems for improvement in frequency deviation profile. The optimal power sharing between supplementary and DR loop control is presented for different load variations. Further, efficacy of controller performance is also validated by introducing non-linearities in generation in terms of generation rate constraint (GRC) and governor dead band (GDB). The simulations are performed with inclusion of DR for LFC control problem in (i) single-area, (ii) two-area thermal and (iii) thermal power system integrated with pumped hydropower system to improve the dynamic performance of system and hence minimize the frequency deviation. The controller in supplementary loop and DR loop is optimized using particle swarm optimization (PSO) technique. Copyright (c) 2016 John Wiley & Sons, Ltd.
引用
收藏
页数:23
相关论文
共 50 条
  • [1] Optimal Frequency Regulation of a Two-area Power System
    Hassen, S. Z. Sayed
    Jahmeerbacus, M. I.
    2013 IEEE INTERNATIONAL CONFERENCE ON INDUSTRIAL TECHNOLOGY (ICIT), 2013, : 140 - 145
  • [2] Frequency regulation of two-area thermal and photovoltaic power system via flood algorithm
    Ekinci, Serdar
    Izci, Davut
    Turkeri, Cebrail
    Smerat, Aseel
    Ezugwu, Absalom E.
    Abualigah, Laith
    RESULTS IN CONTROL AND OPTIMIZATION, 2025, 18
  • [3] Impact of Wind/Solar Integration on Frequency Control in Two-Area Power System
    Mishra, Dillip K.
    Panigrahi, Tapas K.
    Mohanty, Asit
    Ray, Prakash K.
    2018 19TH INTERNATIONAL CARPATHIAN CONTROL CONFERENCE (ICCC), 2018, : 580 - 584
  • [4] DESIGN OF SUBOPTIMAL AGC REGULATION FOR TWO-AREA HYDRO-THERMAL POWER SYSTEM.
    Kumar, Prabhat
    Hole, K.E.
    Aggarwal, R.P.
    1600, (63):
  • [5] Impact of storage device on Load frequency control of a two-area renewable penetrated power system
    Jood, Pankaj
    Aggarwal, S. K.
    Chopra, Vikram
    2018 IEEE 8TH POWER INDIA INTERNATIONAL CONFERENCE (PIICON), 2018,
  • [6] Decentralized load frequency control for two-area interconnected power system
    Wang W.
    Ohmori H.
    Control Theory and Technology, 2015, 13 (02) : 101 - 114
  • [7] Decentralized load frequency control for two-area interconnected power system
    Wei WANG
    Hiromitsu OHMORI
    ControlTheoryandTechnology, 2015, 13 (02) : 101 - 114
  • [8] Study of AGC in Two-Area Hydro-thermal Power System
    Ganthia, Bibhu Prasad
    Pritam, Anita
    Rout, Krishna
    Singhsamant, Siddhartha
    Nayak, Jayashree
    ADVANCES IN POWER SYSTEMS AND ENERGY MANAGEMENT, 2018, 436
  • [9] Intelligent Controllers for Load Frequency Control of Two-Area Power System
    Azeer, S. A.
    Ramjug-Ballgobin, R.
    Hassen, S. Z. Sayed
    IFAC PAPERSONLINE, 2017, 50 (02): : 301 - 306
  • [10] Slime Mould Algorithm for Frequency Controller Design of a Two-area Thermal-PV Power System
    Khamies, Mohamed
    Magdy, Gaber
    Kamel, Salah
    Elsayed, Salah K.
    2021 IEEE IFAC INTERNATIONAL CONFERENCE ON AUTOMATION/XXIV CONGRESS OF THE CHILEAN ASSOCIATION OF AUTOMATIC CONTROL (IEEE IFAC ICA - ACCA2021), 2021,