FREQUENCY AND VOLTAGE CONTROL OF MICRO HYDRO POWER STATIONS BASED ON HYDRAULIC TURBINE'S LINEAR MODEL APPLIED ON INDUCTION GENERATORS

被引:0
|
作者
Scherer, Lucas Giuliani [1 ]
de Camargo, Robinson Figueiredo [1 ]
机构
[1] Univ Fed Santa Maria, BR-97105900 Santa Maria, RS, Brazil
关键词
Hydro power station; induction generator; voltage and frequency control; FLUX;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper presents an approach to full modeling and control of micro hydro power stations using linear model of hydraulic turbine applied on induction generators. Constant frequency control is obtained by a speed governor applied in turbine feed system while constant voltage control is reached through reactive power control by a voltage-source inverter (VSI). In order to reach effective frequency control it is proposed the use of motor flux estimation algorithm to obtain the measurement of instantaneous rotor speed without the necessity of mechanical sensor applied on his shaft, resulting in inherent cost reduction. Simulation results, considering step changes in load and frequency reference setting, have been considered. Experimental results related to reactive power control and voltage regulation are presented and have shown satisfactory dynamic performance.
引用
收藏
页码:546 / 552
页数:7
相关论文
共 50 条
  • [21] Control of a wind turbine cluster based on squirrel cage induction generators connected to a single VSC power converter
    Egea-Alvarez, Agusti
    Junyent-Ferre, Adria
    Bergas-Jane, Joan
    Bianchi, Fernando D.
    Gomis-Bellmunt, Oriol
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2014, 61 : 523 - 530
  • [22] Linear Kalman filtering algorithm applied to measurements of power system voltage magnitude and frequency: A constant-frequency model
    Soliman, SA
    Abdel-Rahman, MH
    El-Hawary, ME
    CANADIAN JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING-REVUE CANADIENNE DE GENIE ELECTRIQUE ET INFORMATIQUE, 1997, 22 (04): : 145 - 153
  • [23] Linear Kalman filtering algorithm applied to measurements of power system voltage magnitude and frequency: a constant-frequency model
    Coll of Technological Studies, Shuweikh, Kuwait
    Canadian Journal of Electrical and Computer Engineering, 1997, 22 (04): : 145 - 153
  • [24] A non-Linear Control of Power Wind Turbine Based on Doubly Fed Induction Generator
    Boulaam, Karima
    Boukhelifa, Akkila
    Janajreh, Isam
    2013 1ST INTERNATIONAL CONFERENCE & EXHIBITION ON THE APPLICATIONS OF INFORMATION TECHNOLOGY TO RENEWABLE ENERGY PROCESSES AND SYSTEMS (IT-DREPS 2013), 2013, : 127 - 131
  • [25] Reactive Power Estimation Based Adaptive Voltage Control for Improved Grid Voltage Restoration using Doubly Fed Induction Generators
    Ghosh, Sudipta
    Bhattarai, Rojan
    Kamalasadan, Sukumar
    2017 IEEE TRANSPORTATION ELECTRIFICATION CONFERENCE (ITEC-INDIA), 2017,
  • [26] Adaptive Inertial Control for Wind Turbine Generators in Fast Frequency Response Based on the Power Reduction Period Assessment
    Heidari, Mahdi
    Ding, Lei
    Kheshti, Mostafa
    Zhao, Xiaowei
    Terzija, Vladimir
    IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2025, 16 (01) : 377 - 391
  • [27] Voltage and frequency control of an autonomous hybrid generation system based on linear model predictive control
    Kassem, Ahmed M.
    Yousef, Ali M.
    SUSTAINABLE ENERGY TECHNOLOGIES AND ASSESSMENTS, 2013, 4 (04) : 52 - 61
  • [28] Optimal constant power control of wind turbine generators based on Takagi-Sugeno fuzzy model
    Qin, Shengsheng
    Ngu, SzeSong
    Zeng, Tingting
    ALEXANDRIA ENGINEERING JOURNAL, 2022, 61 (08) : 5977 - 5982
  • [29] Voltage and frequency control of isolated micro-grid using extended linear model predictive controller
    Vidyasagar, Puvvula S. R. V. R. S. S.
    Swarup, K. Shanti
    2018 IEEE POWER & ENERGY SOCIETY GENERAL MEETING (PESGM), 2018,
  • [30] Frequency and voltage regulation control strategy of Wind Turbine based on supercapacitors under power grid fault
    Li, Zhongliang
    Liu, Fang
    ENERGY REPORTS, 2023, 10 : 2612 - 2622