Mid-point siting of FACTS devices in transmission lines

被引:68
|
作者
Ooi, BT
Kazerani, M
Marceau, R
Wolanski, Z
Galiana, FD
McGillis, D
Joos, G
机构
[1] ECOLE POLYTECH,MONTREAL,PQ H3C 3A7,CANADA
[2] CONCORDIA UNIV,MONTREAL,PQ,CANADA
关键词
transmission line; Flexible AC Transmission Systems; FACTS; thyristor; gate-turn-off thyristors; power electronics; phase shifters; STATCOM; Unified Power flow Controller;
D O I
10.1109/61.634196
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Many controllers of Flexible AC Transmission Systems (FACTS), such as the STATCOM, the Unified Power Flow Controller (UPFC), the PWM asynchronous de link, the Thyristor-Controlled Series Capacitor (TCSC) and the PWM Series Static VAR compensator have stabilized ac voltage support. Thus, they can be sited at the mid-point of the transmission line, which has been proven by the late E.W. Kimbark, as the optimum location for shunt capacitor compensation. This paper points out that the ability to double the power transfer of the uncompensated line applies also to the aforementioned FACTS devices. The mid-point siting also facilitates the independent control of reactive power at both ends of the transmission line.