Methodology for Fire PSA during design process

被引:0
|
作者
Blombach, J. [1 ]
Kollasko, H. [1 ]
机构
[1] AREVA NP GmbH, D-91058 Erlangen, Germany
关键词
D O I
10.3139/124.110017
中图分类号
TL [原子能技术]; O571 [原子核物理学];
学科分类号
0827 ; 082701 ;
摘要
Fire PSA is an essential part of a full scope level 1 PSA. Cable fires play an important role in fire PSA. Usually, cable routing is therefore modeled in detail. During the design of new nuclear power plants the information on cable routing is not yet available. However, for the use of probabilistic safety insights during the design and for licensing purposes a fire PSA may be requested. Therefore a methodology has been developed which makes use of the strictly divisional separation of redundancies in the design of modern nuclear power plants: cable routing is not needed within one division but replaced by the conservative assumption that all equipment fails due to a fire in the concerned division; critical fire areas are defined where components belonging to different divisions may be affected by a fire. For the determination of fire frequencies a component based approach is proposed. The resulting core damage frequencies due to fire are conservative.
引用
收藏
页码:126 / 131
页数:6
相关论文