New after-laying test methods for XLPE cable lines

被引:0
|
作者
Uchida, K
Kobayashi, S
Kawashima, T
Hirotsu, K
Inoue, H
Tanaka, H
Sakuma, S
机构
关键词
after-laying test; damped oscillating wave; very low frequency; CV cable; partial discharge; electrical tree;
D O I
10.1002/eej.4391170603
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
An after-laying test is required to demonstrate the soundness of XLPE underground cable lines with joints. AC voltage application is desirable for the test; however, the equipment for ac application must be very large because it must supply large capacitive current for cables. DC voltage is normally applied, which can be supplied with small equipment; however, the effectiveness of the de application is questioned because the electrical stress distribution is quite different from that with ac application and, moreover, de application could damage insulation properties of cables. The authors targeted the Oscillating Wave (OSW) method and the Very Low-Frequency (VLF) method as alternative after-laying tests. They first developed modeling methods of various defects on underground cable lines and applied OSW and VLF to these defect models. They found that OSW and VLF methods have higher fault detection capability than de voltage application. They also demonstrated that the defects which can be easily detected with the OSW method are difficult to detect with the VLF method and vice versa. They showed that serial application of both methods highly improve the fault detection ability for XLPE underground cable lines.
引用
收藏
页码:18 / 30
页数:13
相关论文
共 50 条
  • [21] Partial Discharges Classification Methods in XLPE Cable: A Review
    Rosle, Norfadilah
    Muhamad, Nor Asiah
    Rohani, Mohamad Nur Khairul Hafizi
    Jamil, Mohamad Kamarol Mohd
    IEEE ACCESS, 2021, 9 : 133258 - 133273
  • [22] Thermal Effect of Different Laying Modes on Cross-Linked Polyethylene (XLPE) Insulation and a New Estimation on Cable Ampacity
    Zhu, WenWei
    Zhao, YiFeng
    Han, ZhuoZhan
    Wang, XiangBing
    Wang, YanFeng
    Liu, Gang
    Xie, Yue
    Zhu, NingXi
    ENERGIES, 2019, 12 (15)
  • [23] Evaluation of Voltage Endurance Characteristics for New and Aged XLPE Cable Insulation by Electrical Treeing Test
    Su, Yu
    Liu, Ying
    Zhong, Lisheng
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2019, 26 (01) : 72 - 80
  • [24] Discuss AC voltage withstand test of XLPE power cable
    2005, Science Press, Beijing, China (31):
  • [25] DEVELOPMENT OF NEW WATER TREE SUPPRESSIVE XLPE CABLE
    WATANABE, K
    YAGYU, H
    SEKII, Y
    MARUMO, M
    IEEE TRANSACTIONS ON POWER DELIVERY, 1986, 1 (01) : 27 - 33
  • [26] Laying of superconducting cable and cooling test on the field of subway
    Tomita, Masaru
    Fukumoto, Yusuke
    Kobayashi, Yusuke
    Ishihara, Atsushi
    Akasaka, Tomoyuki
    Suzuki, Kenji
    Onji, Taiki
    CRYOGENICS, 2022, 123
  • [27] USE OF BURNED ROCKS IN UNDERGROUND LAYING OF CABLE LINES IN THE CRYOLITZONE
    Galkin, Aleksandr F.
    Kurta, Ivan, V
    Pankov, Vladimir Yu
    BULLETIN OF THE TOMSK POLYTECHNIC UNIVERSITY-GEO ASSETS ENGINEERING, 2020, 331 (12): : 131 - 137
  • [28] RELATIONSHIPS OF CORONA TO LIFE + RELIABILITY OF POLYETHYLENE INSULATED CABLE - NEW TEST METHODS FOR CABLE
    STARR, WT
    AGRIOS, JP
    IEEE TRANSACTIONS ON COMMUNICATION AND ELECTRONICS, 1964, (70): : 88 - &
  • [30] Examples of additional test for 275kV XLPE cable systems
    Hashikawa, Tatsuro
    CIGRE Session 46, 2016, 2016-August