Developing an indoor environment quality tool for assessment of mechanically ventilated office buildings in the UK - A preliminary study

被引:110
|
作者
Ncube, Matiwaza [1 ]
Riffat, Saffa [1 ]
机构
[1] Univ Nottingham, Dept Built Environm, Nottingham NG7 2RD, England
基金
英国工程与自然科学研究理事会;
关键词
Office buildings; Rating system; Indoor environment quality; United Kingdom; WEIGHTED SOUND; LEVEL;
D O I
10.1016/j.buildenv.2012.01.003
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This study describes the development of a new model for rapid assessment of Indoor Environment Quality (IEQ) in air-conditioned office buildings in the UK using design, measured, calculated and surveyed input data. The novelty of this model is that it addresses the need to present indoor environment performance ratings alongside energy performance certification and help determine by how much energy efficiency imperatives sacrifice human comfort. The model is based on the IEQ(index) which was developed from literature. The IEQ(index) is an expression which was derived from four contributing factors namely Thermal Comfort, Indoor Air quality (IAQ), Acoustic Comfort and Lighting. The relative weightings of each of the contributing factors were derived by fitting a multiple regression model to questionnaire data obtained from 68 occupants of two selected case study buildings in the UK. During questionnaire administration, measurement of indoor environment variables such as air temperature, relative humidity, air velocity, illuminance, CO2 concentrations and A-weighted sound pressure level was carried out in order to validate occupant responses. An empirical expression more suited to the air-conditioned offices in the UK was developed and the end result was a computer based program called the Indoor Environment Quality Assessment Tool (IEQAT). The model was compared to the AHP developed by Chiang et al. and the models showed good agreement (C) 2012 Elsevier Ltd. All rights reserved.
引用
收藏
页码:26 / 33
页数:8
相关论文
共 50 条
  • [21] Observational study of the indoor environment and energy use in office buildings in tropical Asia
    Yamauchi, Ro
    Ichinose, Masayuki
    SUSTAINABLE BUILT ENVIRONMENT CONFERENCE 2019 TOKYO (SBE19TOKYO) - BUILT ENVIRONMENT IN AN ERA OF CLIMATE CHANGE: HOW CAN CITIES AND BUILDINGS ADAPT?, 2019, 294
  • [22] Preliminary study of indoor air quality and childhood asthma in the UK
    Stewart, L
    Gee, IL
    Watson, AFR
    PROCEEDINGS OF THE SECOND NSF INTERNATIONAL CONFERENCE ON INDOOR AIR HEALTH: TRENDS AND ADVANCES IN RISK ASSESSMENT AND MANAGEMENT, 2001, : 69 - 76
  • [23] Enhancing indoor air quality in office buildings: Insight from a field study
    Torriani, Giulia
    Lara-Ibeas, Irene
    Babich, Francesco
    53RD AICARR INTERNATIONAL CONFERENCE FROM NZEB TO ZEB: THE BUILDINGS OF THE NEXT DECADES FOR A HEALTHY AND SUSTAINABLE FUTURE, 2024, 523
  • [24] Comparative study on the indoor environment quality of green office buildings in China with a long-term field measurement and investigation
    Pei, Zufeng
    Lin, Borong
    Liu, Yanchen
    Zhu, Yingxin
    BUILDING AND ENVIRONMENT, 2015, 84 : 80 - 88
  • [25] Perceived Indoor Environment and Occupants' Comfort in European "Modern" Office Buildings: The OFFICAIR Study
    Sakellaris, Ioannis A.
    Saraga, Dikaia E.
    Mandin, Corinne
    Roda, Celina
    Fossati, Serena
    de Kluizenaar, Yvonne
    Carrer, Paolo
    Dimitroulopoulou, Sani
    Mihucz, Victor G.
    Szigeti, Tamas
    Hanninen, Otto
    Fernandes, Eduardo de Oliveira
    Bartzis, John G.
    Bluyssen, Philomena M.
    INTERNATIONAL JOURNAL OF ENVIRONMENTAL RESEARCH AND PUBLIC HEALTH, 2016, 13 (05):
  • [26] Indoor Tracking to Understand Physical Activity and Sedentary Behaviour: Exploratory Study in UK Office Buildings
    Spinney, Richard
    Smith, Lee
    Ucci, Marcella
    Fisher, Abigail
    Konstantatou, Marina
    Sawyer, Alexia
    Wardle, Jane
    Marmot, Alexi
    PLOS ONE, 2015, 10 (05):
  • [27] Do Spatially Distributed Sensor Measurements Provide Better Representation of Indoor Environment than Single Sensor Measurements? A Mechanically Ventilated Office Space Case Study
    Khan, Donya Sheikh
    Kolarik, Jakub
    Hviid, Christian A.
    Weitzmann, Peter
    INDOOR ENVIRONMENTAL QUALITY PERFORMANCE APPROACHES (IAQ 2020), PT 1, 2021,
  • [28] Developing an Assessment Tool to Measure the Readiness of Office Buildings Design to Mitigate the Spread of Infectious Diseases
    Alsulami, Nada N.
    Fageha, Mohammed K.
    MAN AND PLACE, 2024, : 523 - 552
  • [29] Developing a Building Energy Efficiency Assessment Tool for Office Buildings in Ghana: Delphic Consultation Approach
    Nii, Addy Michael
    Emmanuel, Adinyira
    Joshua, Ayarkwa
    8TH INTERNATIONAL CONFERENCE ON SUSTAINABILITY IN ENERGY AND BUILDINGS, SEB-16, 2017, 111 : 639 - 648
  • [30] Indoor Environmental Quality in Portuguese Office Buildings: Influencing Factors and Impact of an Intervention Study
    Felgueiras, Fatima
    Mourao, Zenaida
    Moreira, Andre
    Gabriel, Marta F.
    SUSTAINABILITY, 2024, 16 (21)