An accurate scheme for fault location in combined overhead line with underground power cable

被引:0
|
作者
Gilany, M [1 ]
El Din, EST [1 ]
Aziz, MMA [1 ]
Ibrahim, DK [1 ]
机构
[1] Cairo Univ, Cairo, Egypt
来源
2005 IEEE POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS, 1-3 | 2005年
关键词
combined overhead lines; fault location; modal transformation; phasor extraction; synchronized measurements; power cables;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper presents an accurate fault location scheme for transmission systems consisting of an overhead line in combination with an underground power cable. The algorithm requires phasor measurements data from one end of the transmission line and the synchronized measurements at the most far end of the power cable. Fault location is derived using distributed line model, modal transformation theory and Discrete Fourier Transform. The technique can be used on-line or off-line using the data stored in the digital transient recording apparatus. The proposed scheme has the ability to locate the fault whether it is in the overhead fine or in the underground power cable. Extensive simulation studies carried out using MATLAB show that the proposed scheme provides a high accuracy in fault location under various system and fault conditions.
引用
收藏
页码:2521 / 2527
页数:7
相关论文
共 50 条
  • [31] Algorithm improvement to predict fault location of simultaneous fault in underground cable
    Apisit, Chaowat
    Ngaopitakkul, Atthapol
    IEEJ Transactions on Power and Energy, 2013, 133 (11): : 799 - 805
  • [32] Wavelet analysis based scheme for fault detection and classification in underground power cable systems
    Zhao, W
    Song, YH
    Min, Y
    ELECTRIC POWER SYSTEMS RESEARCH, 2000, 53 (01) : 23 - 30
  • [33] An accurate fault location scheme for connected aged cable lines in double-fed systems
    Eldin, E. M. Tag
    Gilany, M. I.
    Abdelaziz, M. M.
    Ibrahim, D. K.
    ELECTRICAL ENGINEERING, 2006, 88 (05) : 431 - 439
  • [34] Fault location for overhead and cable hybrid transmission line in VSC-HVDC systems based on EMTR
    Zhang Y.
    Li T.
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2024, 44 (03): : 180 - 186and224
  • [35] An accurate fault location scheme for connected aged cable lines in double-fed systems
    E. M. Tag Eldin
    M. I. Gilany
    M. M. Abdelaziz
    D. K. Ibrahim
    Electrical Engineering, 2006, 88 : 431 - 439
  • [36] Study on Accuracy Traveling Wave Fault Location Method of Overhead line - Cable Hybrid Line and Its Influencing Factors
    Li Xun
    Liu Shungui
    Huang Ronghui
    Ai Jingwen
    An Yunzhu
    Chen Ping
    Xin Zhengxiang
    2017 CHINESE AUTOMATION CONGRESS (CAC), 2017, : 4593 - 4597
  • [37] Fault Location System for Underground Transmission Line
    Yang, Jun-Zhe
    Lin, Hung-Yu
    IEEE INTERNATIONAL SYMPOSIUM ON NEXT-GENERATION ELECTRONICS 2013 (ISNE 2013), 2013,
  • [38] Accurate one-end fault location for overhead transmission lines in interconnected power systems
    Eisa, Amir A. A.
    Ramar, K.
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2010, 32 (05) : 383 - 389
  • [39] Deep Learning-Based Fault Classification and Location for Underground Power Cable of Nuclear Facilities
    Said, Abdelrahman
    Hashima, Sherief
    Fouda, Mostafa M.
    Saad, Mohamed H.
    IEEE ACCESS, 2022, 10 : 70126 - 70142
  • [40] A fault location algorithm for high voltage overhead power transmission line based on line parameter estimation
    Liang, Jun
    Ma, Chang-Hui
    Yun, Zhi-Hao
    Power System Technology, 2004, 28 (04) : 60 - 63