Modelling and performance of fixed-speed induction generators in power system oscillation stability studies

被引:25
|
作者
Zhang, Jian [2 ]
Dysko, Adam [1 ]
O'Reilly, John [3 ]
Leithead, William E. [1 ]
机构
[1] Univ Strathclyde, Dept Elect & Elect Engn, Glasgow G1 1XW, Lanark, Scotland
[2] Mott MacDonald Ltd, Generat Business Div, Brighton BN1 4FY, E Sussex, England
[3] Univ Glasgow, Dept Elect & Elect Engn, Glasgow G12 8LT, Lanark, Scotland
基金
英国工程与自然科学研究理事会;
关键词
power system oscillation stability; fixed-speed induction generators; simulation;
D O I
10.1016/j.epsr.2008.01.003
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper describes the modelling and performance effects of induction generator-based wind. farms on the oscillation stability of power systems. For groups of 5, 10 and 20 induction generators, it is established that the basic dynamic properties of each group of generators are similar to those of a third-order equivalent machine model whether the generators are evenly loaded or unevenly loaded. The paper analyses the impact of induction-based wind generation, on oscillation stability for multi-machine systems as applied to the standard IEEE 30 bus system. The effects of load model representation, system loading, generator output and transmission line network parameters are considered. In general, the multi-machine system is shown to be well damped under all normal operating conditions. (C) 2008 Elsevier B.V. All rights reserved.
引用
收藏
页码:1416 / 1424
页数:9
相关论文
共 50 条
  • [21] Use of STATCOM in wind farms with fixed-speed generators for grid code compliance
    Ramirez, Dionisio
    Martinez, Sergio
    Blazquez, Francisco
    Carrero, Carmelo
    RENEWABLE ENERGY, 2012, 37 (01) : 202 - 212
  • [22] Fixed-speed wind-generator and wind-park modeling for transient stability studies
    Trudnowski, DJ
    Gentile, A
    Khan, JM
    Petritz, EM
    IEEE TRANSACTIONS ON POWER SYSTEMS, 2004, 19 (04) : 1911 - 1917
  • [23] Long-Term Voltage Instability Detections of Multiple Fixed-Speed Induction Generators in Distribution Networks Using Synchrophasors
    Liu, Jian-Hong
    Chu, Chia-Chi
    IEEE TRANSACTIONS ON SMART GRID, 2015, 6 (04) : 2069 - 2079
  • [24] Improved control strategy for fixed-speed compressors in parallel system
    Jung, Jaeheum
    Lee, Won Je
    Park, Sangmin
    Kim, Younghun
    Lee, Chul-Jin
    Han, Chonghun
    JOURNAL OF PROCESS CONTROL, 2017, 53 : 57 - 69
  • [25] EXPERIMENTAL ANALYSIS OF A FIXED-SPEED AND A VARIABLE-SPEED AIR CONDITIONING SYSTEM
    Fenech, G.
    Farrugia, M.
    ENGINEERING MECHANICS 2014, 2014, : 168 - 171
  • [26] Effect of induction generators in the transient stability of an electric power system
    Santos, E.
    Asiain, T.I.
    Ruiz, D.
    Olguin, D.
    Proceedings of the Universities Power Engineering Conference, 1999, 1 : 26 - 29
  • [27] Reduced-Order Models of Squirrel-Cage Induction Generators for Fixed-Speed Wind Turbines Under Unbalanced Grid Conditions
    Rolan, Alejandro
    Corcoles Lopez, Felipe
    Bogarra, Santiago
    Monjo, Lluis
    Pedra, Joaquin
    IEEE TRANSACTIONS ON ENERGY CONVERSION, 2016, 31 (02) : 566 - 577
  • [28] Dynamic maximum available power of fixed-speed wind turbine at islanding operation
    Reza, Najafi Hamid
    Farshad, Dastyar
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2013, 47 : 147 - 156
  • [29] Comparison Among Stabilization Methods of Fixed-Speed Wind Generator System
    Ali, Mohd. Hasan
    Wu, Bin
    2009 IEEE ENERGY CONVERSION CONGRESS AND EXPOSITION, VOLS 1-6, 2009, : 2927 - +
  • [30] Electrical signals dataset from fixed-speed and variable-speed synchronous generators under healthy and faulty conditions
    Tominaga, Rafael Noboro
    Sousa, Luan Andrade
    Rocha, Rodolfo Varraschim
    Monaro, Renato Machado
    Avila, Sergio Luciano
    Salles, Mauricio Barbosa de Camargo
    Carmo, Bruno Souza
    DATA IN BRIEF, 2024, 57