UHF partial discharge monitoring in GIS and signal processing

被引:2
|
作者
Li, ZM [1 ]
Feng, YP [1 ]
Chen, JQ [1 ]
Zhang, XZ [1 ]
机构
[1] Xian Jiao Tong Univ, Sch Elect Engn, Xian 710049, Peoples R China
关键词
PD (partial discharge); UHF (ultra high frequency); wavelet; multiscale;
D O I
10.1109/ISEIM.1998.741686
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this paper the experiments of detection partial discharges in GIS using ultra high frequency technique is described. The sensors are put outside the GIS so they do not bring extra requirements to the fabrication and operation of GIS. Some steps are taken to resist the external noises. The results show that UHF method is effective in detecting PD in GIS and avoiding the disturbance of coronas outside the GIS. Nevertheless very large corona, fluorescent tube or radio frequency noise nearby can still disturb the measurement. A method of signal processing by software is presented in this paper. Through the procedure of signal wavelet transform, signal noise extraction and signal reconstruction, the signal is analyzed to determine the magnitude of PD in GIS and avoid false alarm. And the modulus maxima and their positions gotten from the wavelet transform can be used as the base of PD pattern recognition in GIS.
引用
收藏
页码:67 / 70
页数:4
相关论文
共 50 条
  • [31] Comparative test of effective height of UHF sensor for partial discharge in GIS
    Shu S.
    Chen J.
    Chen B.
    Ye Z.
    Chen M.
    You H.
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2017, 37 (07): : 166 - 170and197
  • [32] Design of UHF-SHF Sensor for the Detection of GIS Partial Discharge
    Wang, Shiqiang
    Hu, Haiyan
    Wang, Wei
    Li, Fangyi
    Yan, Xiaoyu
    Wang, Yuhang
    Wang, Lin
    2016 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), 2016, : 350 - 353
  • [33] Research on the Typical Partial Discharge Using the UHF Detection Method for GIS
    Gao, Wensheng
    Ding, Dengwei
    Liu, Weidong
    IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (04) : 2621 - 2629
  • [34] An External UHF Composite Spiral Antenna for Partial Discharge Detection in GIS
    Liang, Haozhe
    Lu, Hongda
    Liu, Yong
    Zhen, Pengfei
    Lv, Xin
    2022 INTERNATIONAL CONFERENCE ON MICROWAVE AND MILLIMETER WAVE TECHNOLOGY (ICMMT), 2022,
  • [35] A Novel Composite Sensor for Overvoltage and UHF Partial Discharge Measurement in GIS
    Wang, Haotian
    Zhang, Xuanrui
    Han, Xutao
    Sun, Yuan
    Chen, Huan
    Li, Junhao
    IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (06) : 5476 - 5479
  • [36] Design and Development of Internal UHF Sensor for Partial Discharge Detection in GIS
    Zhang, Jia-Ning
    Zhu, Ming-Xiao
    Liu, Qing
    Shao, Xian-Jun
    He, Wen-Lin
    Yao, Hui
    Deng, Jun-Bo
    Zhang, Guan-Jun
    2016 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (CMD), 2016, : 709 - 712
  • [37] Mathematical model of four typical defects for UHF partial discharge in GIS
    Zhou Qian
    Tang Ju
    Bai Yunqing
    Xie Yanbin
    Tang Ming
    2006 INTERNATIONAL CONFERENCE ON POWER SYSTEMS TECHNOLOGY: POWERCON, VOLS 1- 6, 2006, : 1279 - +
  • [38] Sensitivity of the internal UHF coupler used for partial discharge detection in GIS
    Zhang G.
    Xu Y.
    Liu W.
    Zhang J.
    Gao W.
    Gaodianya Jishu/High Voltage Engineering, 2016, 42 (11): : 3683 - 3688
  • [39] Frequency response characteristics of the UHF sensors for partial discharge detection in GIS
    Wang, Jiansheng
    Qiu, Yuchang
    Wu, Xianghua
    Sun, Xiaobin
    2000, Chinese Soc of Electrical Engineering, China (20):
  • [40] Development Simulation and Experiment Study on UHF Partial Discharge Sensor in GIS
    Li, Tianhui
    Rong, Mingzhe
    Zheng, Chen
    Wang, Xiaohua