Experimental study on a new internally cooled/heated dehumidifier/regenerator of liquid desiccant systems

被引:135
|
作者
Yin, Yonggao [1 ]
Zhang, Xiaosong [1 ]
Wang, Geng [1 ]
Luo, Lei [1 ]
机构
[1] Southeast Univ, Sch Energy & Environm, Nanjing 210096, Jiangsu, Peoples R China
基金
中国国家自然科学基金;
关键词
air conditioning; dehumidifier; desiccant; design; heat exchanger; regenerator; finned tube; experiment;
D O I
10.1016/j.ijrefrig.2007.10.004
中图分类号
O414.1 [热力学];
学科分类号
摘要
For providing good performance of dehumidifier and regenerator with certain dimensions, a new type of internally cooled/heated dehumidifier/regenerator based on the plate-fin heat exchanger (PFHE) was designed. To investigate the behavior of the new equipment, an experimental setup was established in an environment chamber with regulable temperature and humidity air. By the internally cooled dehumidification testing, effects of the cooling waiter temperature, the air flow rate and the desiccant temperature on the dehumidification performance and the cooling efficiency were presented. The behavior of internally cooled dehumidification process was compared with that of the adiabatic dehumidification process. The results suggested that the cooling efficiency decreased with the increasing of the cooling water temperature and desiccant with low temperature could bring more mass transfer coefficients. There is an optimal air flow rate to achieve the maximum absolute humidity decrease of the air. By the internally heated regeneration testing, effects of the air flow rate and the desiccant inlet temperature on the regeneration performance and air outlet parameters were discussed and also compared with those of the adiabatic regeneration process. It was concluded that the regeneration efficiency of internally heated regeneration was more than that of the adiabatic regeneration, and the internally heated regenerator could offer better thermal performance. (C) 2007 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:857 / 866
页数:10
相关论文
共 50 条
  • [31] Experimental and theoretical analysis of heat and mass transfer in a packed column dehumidifier/regenerator with liquid desiccant
    Longo, GA
    Gasparella, A
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2005, 48 (25-26) : 5240 - 5254
  • [32] Development of simplified prediction model for internally cooled/heated liquid desiccant dehumidification system
    Qi, Ronghui
    Lu, Lin
    Yang, Hongxing
    ENERGY AND BUILDINGS, 2013, 59 : 133 - 142
  • [33] Experimental and numerical investigation on the performance of an internally cooled dehumidifier
    Turgut, Oguz Emrah
    Coban, Mustafa Turhan
    HEAT AND MASS TRANSFER, 2016, 52 (12) : 2707 - 2722
  • [34] Experimental and numerical investigation on the performance of an internally cooled dehumidifier
    Oguz Emrah Turgut
    Mustafa Turhan Çoban
    Heat and Mass Transfer, 2016, 52 : 2707 - 2722
  • [35] Heat and mass transfer in an adjacent internally-cooled membrane-based liquid desiccant dehumidifier (AIMLDD)
    Yang, Yu
    Yang, Minlin
    Huang, Weihao
    Huang, Si-Min
    Ye, Wei-Biao
    Hong, Yuxiang
    Qin, Frank G. F.
    Shao, Youyuan
    PROCEEDINGS OF THE 9TH INTERNATIONAL CONFERENCE ON APPLIED ENERGY, 2017, 142 : 3990 - 3997
  • [36] Conjugate heat and mass transfer in an internally-cooled membrane-based liquid desiccant dehumidifier (IMLDD)
    Huang, Si-Min
    Zhong, Zhanrong
    Yang, Minlin
    JOURNAL OF MEMBRANE SCIENCE, 2016, 508 : 73 - 83
  • [37] Experimental study on a new internally cooled dehumidifier using LiCl-H2O
    Yin, Yonggao
    Zhang, Xiaosong
    PROCEEDINGS OF ISES SOLAR WORLD CONGRESS 2007: SOLAR ENERGY AND HUMAN SETTLEMENT, VOLS I-V, 2007, : 857 - 861
  • [38] Performance analysis of an internally-cooled plate membrane liquid desiccant dehumidifier (IMLDD): An analytical solution approach
    Huang, Si-Min
    Yang, Minlin
    Hu, Bing
    Tao, Shi
    Qin, Frank G. F.
    Weng, Wanliang
    Wang, Wenhao
    Liu, Jian
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2018, 119 : 577 - 585
  • [39] Experimental study on the performance of the internally-heated ultrasonic atomization liquid desiccant regeneration system
    Yang, Zili
    Lian, Zhiwei
    Tao, Ruiyang
    Ni, Hui
    Zhong, Ke
    APPLIED THERMAL ENGINEERING, 2019, 163
  • [40] Experimental study on performance of celdek packed liquid desiccant dehumidifier
    Rakesh Kumar
    A. K. Asati
    Heat and Mass Transfer, 2016, 52 : 1821 - 1832