A Method for Fans' Potential Malfunction Detection of ONAF Transformer Using Top-Oil Temperature Monitoring

被引:4
|
作者
Wang, Lujia [1 ,2 ,3 ]
Zuo, Wanwan [1 ]
Yang, Zhi-Xin [2 ,3 ]
Zhang, Jianwen [1 ]
Cai, Zhenlu [1 ]
机构
[1] China Univ Min & Technol, Sch Elect & Power Engn, Xuzhou 221116, Jiangsu, Peoples R China
[2] Univ Macau, State Key Lab Internet Things Smart City, Macau, Peoples R China
[3] Univ Macau, Dept Electromech Engn, Macau, Peoples R China
关键词
Oils; Fans; Power transformers; Oil insulation; Cooling; Monitoring; Atmospheric modeling; Power transformer; cooling system; fan; top-oil temperature; condition monitoring; oil exponent; PERFORMANCE; CONVECTION; MODEL;
D O I
10.1109/ACCESS.2021.3114301
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
The fan is one of the key components of the power transformer cooling system. The operating condition of fans determines transformers' internal temperature rise and long-term reliability. However, at present, the fans' condition monitoring only includes switch status (online) and regular maintenance (offline), online direct monitoring of the fans' operating condition is lacking due to economic costs. In view of the above-mentioned problem, this paper proposes a transformer fan early fault detection method based on the oil exponent, which is monitored by the existing transformer top-oil temperature data, thereby detecting the abnormality of the fans. In this method, the oil exponent was chosen as the characteristic criterion. First, to obtain the range of oil exponent in different cooling modes, a set of physical models describing global oil flow and its interaction with air was established based on fluid dynamics and heat transfer principle. Then, regarding the constantly changing top-oil temperature, ambient temperature and load current, an oil exponent tracking algorithm using particle swarm optimization (PSO) was proposed within an improved IEC dynamic thermal model. The operation data from an oil-immersed transformer with a rated capacity of 120-MVA and rated voltage of 220-kV was selected to verify the above methods under two different scenarios.
引用
收藏
页码:129881 / 129889
页数:9
相关论文
共 43 条
  • [41] Finite element method-based modelling of flow rate and temperature distribution in an oil-filled disc-type winding transformer using COMSOL multiphysics
    Das, Anu Kumar
    Chatterjee, Saibal
    IET ELECTRIC POWER APPLICATIONS, 2017, 11 (04) : 664 - 673
  • [42] A two-stage temperature-driven method for detection of fault sensors and abnormal stress using structural health monitoring data
    Gong, Xiaoyu
    Song, Xiaodong
    Zhu, Yichen
    Feng, Libo
    Lu, Xian
    Cai, C. S.
    STRUCTURAL HEALTH MONITORING-AN INTERNATIONAL JOURNAL, 2025,
  • [43] Advanced treatment of transformer mineral oils contaminated with aroclor mixtures using a combined UV-Visible irradiation and adsorption method: Effects of temperature and oil color according to ASTM D1500
    Gherdaoui, Chems Eddine
    Alaoui, Chakib
    Oumeddour, Hanene
    Bouchikhi, Nouria
    Elmeliani, Mohamed El Amine Elaissaoui
    Aldoori, Hussam
    Benoit, Olivier
    Lahlaf, Reda Zoheir
    Lerari, Djahida
    Delbarre, Jean-Philippe
    CHEMICAL ENGINEERING JOURNAL, 2024, 497