Retrofitting of an air-cooled data center for energy efficiency

被引:24
|
作者
Kuzay, Mustafa [1 ,4 ]
Dogan, Aras [1 ,4 ]
Yilmaz, Sibel [1 ]
Herkiloglu, Oguzhan [2 ]
Atalay, Ali Serdar [2 ]
Cemberci, Atilla [2 ]
Yilmaz, Cagatay [3 ]
Demirel, Ender [1 ,4 ]
机构
[1] Design & Simulat Tech Inc, TR-26480 Eskisehir, Turkey
[2] Radius Solut Ctr, Bahar Arkasi St 11, TR-34692 Istanbul, Turkey
[3] Lande Ind Met Prod Inc Co, Organized Ind Zone, 20th St 14, Eskisehir, Turkey
[4] Eskisehir Osmangazi Univ, TR-26480 Eskisehir, Turkey
关键词
Data center; Thermal efficiency; Cooling efficiency; CFD modeling; Open-source; MANAGEMENT;
D O I
10.1016/j.csite.2022.102228
中图分类号
O414.1 [热力学];
学科分类号
摘要
Small-scale data centers suffering from low cooling efficiency consume an intense power for reliable operation of IT equipment. In this study, thermal distribution in an air-cooled data center is simulated using an open source Computational Fluid Dynamics (CFD) model to examine the underlying mechanism that reduces thermal and cooling efficiencies. The numerical model is validated with the temperature measurements conducted in the data center. Numerical simulations have revealed that recirculating hot flows observed at the top of the racks increased the air temperature beyond the allowable maximum temperature. To this end, the data center has been retrofitted by creating a hot aisle with the implementation of a moving baffle at the rear of the rack. Numerical simulations conducted for two working scenarios have demonstrated that such a minor modification could result in remarkable enhancement in the cooling efficiency. Efficiency of the data center has improved by 47.2% and 22.7% with respect to the RCI (Rack Cooling Index) and RHI (Return Heat Index), respectively. The present numerical model can capture distributions of the efficiency metrics over the racks. Present methodology can be used to reduce power consumption by the cooling and ventilation systems in existing data centers.
引用
收藏
页数:14
相关论文
共 50 条
  • [31] Reducing the condensing temperature to improve the efficiency of air-cooled chillers
    Fu, WY
    Kwok, TC
    PROCEEDINGS OF THE 3RD INTERNATIONAL SYMPOSIUM ON HEAT TRANSFER ENHANCEMENT AND ENERGY CONSERVATION, VOLS 1 AND 2, 2004, : 180 - 185
  • [32] Raising cycle efficiency by intercooling in air-cooled gas turbines
    Caniere, H.
    Willockx, A.
    Dick, E.
    De Paepe, M.
    APPLIED THERMAL ENGINEERING, 2006, 26 (16) : 1780 - 1787
  • [33] 90.1 Proposal Boosts Efficiency Of Air-Cooled Chiller in 2015
    不详
    ASHRAE JOURNAL, 2013, 55 (01) : 14 - 14
  • [34] Robust design of air-cooled server cabinets for thermal efficiency
    Rolander, Nathan
    Rambo, Jeffrey
    Joshi, Yogendra
    Mistree, Farrokh
    Advances in Electronic Packaging 2005, Pts A-C, 2005, : 1649 - 1659
  • [35] PREDICTIONS OF AIRSIDE ECONOMIZATION-BASED AIR-COOLED DATA CENTER ENVIRONMENTAL BURDEN REDUCTION
    Chen, Li
    Wemhoff, Aaron P.
    PROCEEDINGS OF ASME 2022 INTERNATIONAL TECHNICAL CONFERENCE AND EXHIBITION ON PACKAGING AND INTEGRATION OF ELECTRONIC AND PHOTONIC MICROSYSTEMS, INTERPACK2022, 2022,
  • [36] Vortex-enhanced thermal environment for air-cooled data center: An experimental and numerical study
    Xiong, Xin
    Lee, Poh Seng
    ENERGY AND BUILDINGS, 2021, 250
  • [37] An Alternative Reinforcement Learning (ARL) control strategy for data center air-cooled HVAC systems
    Lu, Ruyuan
    Li, Xin
    Chen, Ronghao
    Lei, Aimin
    Ma, Xiaoming
    ENERGY, 2024, 308
  • [38] Comprehensive energy and economic assessment of CRAH bypass method in air-cooled data centers
    Erden, Hamza Salih
    SUSTAINABLE ENERGY TECHNOLOGIES AND ASSESSMENTS, 2022, 52
  • [39] Applying condensing-temperature control in air-cooled reciprocating water chillers for energy efficiency
    Chan, KT
    Yu, FW
    APPLIED ENERGY, 2002, 72 (3-4) : 565 - 581
  • [40] Comparative Study of Energy Performance between Chip and Inlet Temperature-Aware Workload Allocation in Air-Cooled Data Center
    Bai, Yan
    Gu, Lijun
    Qi, Xiao
    ENERGIES, 2018, 11 (03):