MODELLING AND OPTIMIZATION OF A CHILLED-WATER COOLING SYSTEM WITH MULTIPLE CHILLERS

被引:3
|
作者
Du, Jiamin [1 ]
Li, Shuhong [1 ]
Li, Xinmei [2 ]
机构
[1] Southeast Univ, Sch Energy & Environm, Nanjing, Peoples R China
[2] Nanjing Fuca Automat Technol Co Ltd, Nanjing, Peoples R China
来源
THERMAL SCIENCE | 2021年 / 25卷 / 05期
关键词
chilled-water cooling system; modelling and optimization; cooling load distribution; energy conservation; PREDICTION;
D O I
10.2298/TSCI200606328D
中图分类号
O414.1 [热力学];
学科分类号
摘要
In order to reduce energy consumption of the centralized chilled-water cooling system in large buildings, a dynamic control strategy was proposed for cooling plants by modelling and optimization. Combined with the chilled water flow model, this paper analyzed the parallel operation characteristics of the chillers and takes the load distribution as one of the control parameters. Based on the measured data of a typical cooling system that has undergone preliminary energy-saving transformation, the residual neural network is applied to model the relationship among energy consumption, controllable parameters and environmental parameters, and the residual neural network outperforms multi-layer perceptron and support vector regression. To minimize the total energy consumption, the gray wolf optimizer was introduced to optimize the controllable variables of the cooling system. Compared with the energy consumption before optimization, the simulation energy consumption after optimization decreased 10.45% on average, while the energy saving rate is only 7.9% with equal chilled water supply temperature of parallel chillers.
引用
收藏
页码:3873 / 3888
页数:16
相关论文
共 50 条
  • [21] Achieving high chilled-water delta Ts
    Fiorino, DP
    ASHRAE JOURNAL, 1999, 41 (11) : 24 - 30
  • [22] Energy use and economic comparison of chilled-water pumping system alternatives
    Bahnfleth, William P.
    Peyer, Eric B.
    ASHRAE TRANSACTIONS 2006, VOL 112, PT 2, 2006, 112 : 198 - +
  • [23] Cellular glass protects chilled-water lines
    Goss, DK
    McCallion, J
    CHEMICAL PROCESSING, 1997, 60 (04): : 51 - &
  • [24] Performance of the chiller with variable chilled-water flow
    Zhang, Mouxiong
    Nuantong Kongtiao/HV & AC, 2000, 30 (06): : 56 - 58
  • [25] SPECIAL PROBLEMS OF CHILLED-WATER CIRCUITS.
    Harvey, Phil
    Tomlinson, Mark
    Australian refrigeration, Air conditioning and heating, 1986, 40 (10):
  • [26] ENERGY-CONSERVATION WITH CHILLED-WATER STORAGE
    FIORINO, D
    ASHRAE JOURNAL-AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR-CONDITIONING ENGINEERS, 1993, 35 (05): : 22 - &
  • [27] Measurement and Verification of Efficiency Upgrades in Chilled-Water Systems
    Mohammed, Abdul Qayyum
    Tatari, Mohamed
    Seryak, John
    Brown, Shawn
    ASHRAE TRANSACTIONS 2017, VOL 123, PT 1, 2017, 123 : 230 - 243
  • [28] Modeling Hybrid Nuclear Systems With Chilled-Water Storage
    Misenheimer, Corey T.
    Terry, Stephen D.
    JOURNAL OF ENERGY RESOURCES TECHNOLOGY-TRANSACTIONS OF THE ASME, 2017, 139 (01):
  • [29] Laminar flow efficiency of stratified chilled-water storage tanks
    Homan, KO
    Soo, SL
    INTERNATIONAL JOURNAL OF HEAT AND FLUID FLOW, 1998, 19 (01) : 69 - 78
  • [30] CORRELATIONS FOR PREDICTING THE AIR-SIDE NUSSELT NUMBERS AND FRICTION FACTORS IN CHILLED-WATER COOLING COILS
    MIRTH, DR