MODELLING AND OPTIMIZATION OF A CHILLED-WATER COOLING SYSTEM WITH MULTIPLE CHILLERS

被引:3
|
作者
Du, Jiamin [1 ]
Li, Shuhong [1 ]
Li, Xinmei [2 ]
机构
[1] Southeast Univ, Sch Energy & Environm, Nanjing, Peoples R China
[2] Nanjing Fuca Automat Technol Co Ltd, Nanjing, Peoples R China
来源
THERMAL SCIENCE | 2021年 / 25卷 / 05期
关键词
chilled-water cooling system; modelling and optimization; cooling load distribution; energy conservation; PREDICTION;
D O I
10.2298/TSCI200606328D
中图分类号
O414.1 [热力学];
学科分类号
摘要
In order to reduce energy consumption of the centralized chilled-water cooling system in large buildings, a dynamic control strategy was proposed for cooling plants by modelling and optimization. Combined with the chilled water flow model, this paper analyzed the parallel operation characteristics of the chillers and takes the load distribution as one of the control parameters. Based on the measured data of a typical cooling system that has undergone preliminary energy-saving transformation, the residual neural network is applied to model the relationship among energy consumption, controllable parameters and environmental parameters, and the residual neural network outperforms multi-layer perceptron and support vector regression. To minimize the total energy consumption, the gray wolf optimizer was introduced to optimize the controllable variables of the cooling system. Compared with the energy consumption before optimization, the simulation energy consumption after optimization decreased 10.45% on average, while the energy saving rate is only 7.9% with equal chilled water supply temperature of parallel chillers.
引用
收藏
页码:3873 / 3888
页数:16
相关论文
共 50 条
  • [1] CHILLED-WATER FREE COOLING
    WELSH, JW
    ASHRAE JOURNAL-AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR-CONDITIONING ENGINEERS, 1984, 26 (03): : 49 - 50
  • [2] Design issues of variable chilled-water flow through chillers
    Hartman, TB
    ASHRAE TRANSACTIONS 1996, VOL 102, PT 2, 1996, 102 : 679 - 683
  • [3] Performance of chilled-water cooling coils
    Owens-Corning, Granville, United States
    HVAC R Res, 2 (160-172):
  • [4] Chilled-water storage: a suite of benefits for district cooling
    Andrepont, John S.
    District Energy, 81 (01):
  • [5] EXTREMUM SEEKING BASED CONTROL STRATEGY FOR A CHILLED-WATER PLANT WITH PARALLEL CHILLERS
    Mu, Baojie
    Li, Yaoyu
    Salsbury, Timothy I.
    House, John M.
    PROCEEDINGS OF THE ASME 8TH ANNUAL DYNAMIC SYSTEMS AND CONTROL CONFERENCE, 2015, VOL 2, 2016,
  • [6] Chilled-Water VAV System Configuration And Design
    Nassif, Nabil
    ASHRAE JOURNAL, 2022, 64 : 12 - 18
  • [7] Chilled-Water VAV System Configuration And Design
    Nassif, Nabil
    ASHRAE Journal, 2022, 64 (03) : 12 - 18
  • [8] Chilled-Water VAV System Configuration And Design
    Nassif, Nabil
    ASHRAE JOURNAL, 2022, 64 : 40 - 46
  • [9] Chilled-Water VAV System Configuration and Design
    Kryksman, Charles
    ASHRAE Journal, 2022, 64 (04) : 8 - 9
  • [10] Retrofitting conventional chilled-water system to a solar-assisted absorption cooling system: Modeling, polynomial regression, and grasshopper optimization
    Alrbai, Mohammad
    Alahmer, Hussein
    Alahmer, Ali
    Al-Rbaihat, Raed
    Aldalow, Abdulkareem
    Al-Dahidi, Sameer
    Hayajneh, Hassan
    JOURNAL OF ENERGY STORAGE, 2023, 65