FROST SIMULATION ANALYSIS OF THE LIQUID REFRIGERANT DEFROST SYSTEM

被引:0
|
作者
Wang, Meng [1 ]
Zang, Runqing [1 ]
Feng, Hai [1 ]
机构
[1] Tianjin Univ Commerce, Tianjin Refrigerat Engn Technol Ctr, Minist Educ Peoples Republ China, Tianjin Key Lab Refrigerat Technol,Refrigerat Eng, Tianjin 300134, Peoples R China
关键词
Liquid Refrigerant Defrost; Simulation; Relative Humidity; Frost Mass; HEAT-PUMP;
D O I
10.18462/iir.iccc.2018.0035
中图分类号
TH [机械、仪表工业];
学科分类号
0802 ;
摘要
The liquid refrigerant defrost process is continuous during the defrost. The temperature fluctuation of the cold storage is small and the additional energy consumption isn't needed. In order to solve the difficulty of measuring the frost mass and frost thickness in the experiment process, and to investigate the law of the frost formation, a thermodynamic model of the duplex air cooler was established. The results showed that when the environment temperature was 25 degrees C and the cold storage temperature was -20 degrees C, the part of the pipe behind the 4.5m didn't frost when the frost time was within 48h. This is because the air relative humidity of the rear row pipe was low and the frost temperature difference increased, it was hard to frost, which was basically the same as the experimental results.
引用
收藏
页码:264 / 269
页数:6
相关论文
共 50 条
  • [21] Simulation Calculation of Spiral Condenser about Refrigerant System
    Bai, Jing
    ELECTRICAL POWER & ENERGY SYSTEMS, PTS 1 AND 2, 2012, 516-517 : 1192 - 1195
  • [22] Investigation of Control Process in Liquid Refrigerant Defrosting System
    Wang, Meng
    Zang, Runqing
    Li, Yanhe
    Li, Wenqing
    INTERNATIONAL JOURNAL OF THERMODYNAMICS, 2018, 21 (04) : 214 - 219
  • [23] HOT GAS DEFROST SYSTEM.
    Cooke, Greg
    Australian refrigeration, Air conditioning and heating, 1984, 38 (12): : 32 - 33
  • [24] THE LOGAS HOT GAS DEFROST SYSTEM
    Jensen, Stefan S.
    Nitschke, Tobias
    13TH IIR GUSTAV LORENTZEN CONFERENCE ON NATURAL REFRIGERANTS: NATURAL REFRIGERANT SOLUTIONS FOR WARM CLIMATE COUNTRIES, 2018, : 1053 - 1060
  • [25] GAS-LIQUID FLOW SIMULATION IN REFRIGERANT DISTRIBUTOR FOR AIR CONDITIONER
    Ishii, Eiji
    Yoshimura, Kazuki
    INTERNATIONAL JOURNAL OF AIR-CONDITIONING AND REFRIGERATION, 2013, 21 (03)
  • [26] Experimental investigation of frost and defrost performance of microchannel heat exchangers for heat pump systems
    Xu, Bo
    Han, Qing
    Chen, Jiangping
    Li, Feng
    Wang, Nianjie
    Li, Dong
    Pan, Xiaoyong
    APPLIED ENERGY, 2013, 103 : 180 - 188
  • [27] Real-Time Monitoring of Frost/Defrost Processes Using a Tapered Optical Fiber
    Tai, Yi-Hsin
    Kamal, A. Syazwan A.
    Park, Young-Jae
    Tsai, Po-Cheng
    Ho, Ya-Lun
    Wei, Pei-Kuen
    Daiguji, Hirofumi
    Delaunay, Jean-Jacques
    IEEE SENSORS JOURNAL, 2021, 21 (05) : 6188 - 6194
  • [28] Thermodynamic analysis of an absorption refrigeration system with ionic-liquid/refrigerant mixture as a working fluid
    Kim, Yoon Jo
    Kim, Sarah
    Joshi, Yogendra K.
    Fedorov, Andrei G.
    Kohl, Paul A.
    ENERGY, 2012, 44 (01) : 1005 - 1016
  • [29] Frost formation and defrost control parameters for open multideck refrigerated food display cabinets
    Tassou, SA
    Datta, D
    Marriott, D
    PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART A-JOURNAL OF POWER AND ENERGY, 2001, 215 (A2) : 213 - 222
  • [30] Dynamic simulation and performance investigation of no-frost refrigerator: Part II. System simulation and performance analysis
    Su X.-P.
    Chen J.-P.
    Chen Z.-J.
    Zhou X.-T.
    J. Shanghai Jiaotong Univ. Sci., 2009, 2 (229-232): : 229 - 232