Remote Monitoring of Joints Status on In-Service High-Voltage Overhead Lines

被引:1
|
作者
Olivieri, Carlo [1 ]
de Paulis, Francesco [1 ]
Orlandi, Antonio [1 ]
Giannuzzi, Giorgio [2 ]
Salvati, Roberto [2 ]
Zaottini, Roberto [2 ]
Morandini, Carlo [2 ]
Mocarelli, Lorenzo [2 ]
机构
[1] Univ Aquila, Dept Ind & Informat Engn & Econ, UAq EMC Lab, I-67100 Laquila, Italy
[2] TERNA SpA, I-00100 Rome, Italy
关键词
dynamic rating; midspan joints; TDR technique; high-voltage; overhead line; fault-detection; CVT; live-line coupling; signal processing; oxidation; TRANSMISSION-LINES; POWER; SYSTEM; DISCONTINUITIES; LOCATION;
D O I
10.3390/en12061004
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This work presents the feasibility study of an on-line monitoring technique aimed to discover unwanted variations of longitudinal impedance along the line (also named "impedance discontinuities") and, possibly, incipient faults typically occurring on high voltage power transmission lines, like those generated by oxidated midspan joints or bolted joints usually present on such lines. In this paper, the focus is placed on the application and proper customization of a technique based on the time-domain reflectometry (TDR) technique when applied to an in-service high-voltage overhead line. An extensive set of numerical simulations are provided in order to highlight the critical points of this particular application scenario, especially those that concern the modeling of both the TDR signal injection strategy and the required high-voltage coupling devices, and to plan a measurement activity. The modeling and simulation approach followed for the study of either the overhead line or the on-line TDR system is fully detailed, discussing three main strategies. Furthermore, some measurement data that were used to characterize the specific coupling device selected for this application at high frequency-that is, a capacitive voltage transformer (CVT)-are presented and discussed too. This work sets the basic concepts underlying the implementation of an on-line remote monitoring system based on reflectometric principles for in-service lines, showing how much impact is introduced by the high-voltage coupling strategy on the amplitude of the detected reflected voltage waves (also named "voltage echoes").
引用
收藏
页数:17
相关论文
共 50 条
  • [21] Air ion concentrations under overhead high-voltage transmission lines
    Jayaratne, E. R.
    J-Fatokun, F. O.
    Morawska, L.
    ATMOSPHERIC ENVIRONMENT, 2008, 42 (08) : 1846 - 1856
  • [22] An experimental stand for investigating protective devices for high-voltage overhead lines
    Budin, A. V.
    Pinchuk, M. E.
    Pilschikov, V. E.
    Leks, A. G.
    Leont'ev, V. V.
    INSTRUMENTS AND EXPERIMENTAL TECHNIQUES, 2016, 59 (05) : 673 - 677
  • [23] Determinants of homeowners' attitudes to the installation of high-voltage overhead transmission lines
    Elliott, Peter
    Wadley, David
    Han, Jung Hoon
    JOURNAL OF ENVIRONMENTAL PLANNING AND MANAGEMENT, 2016, 59 (04) : 666 - 686
  • [24] Optimization of Hellenic overhead high-voltage transmission lines lightning protection
    Christodoulou, C. A.
    Ekonomou, L.
    Fotis, G. P.
    Harkiolakis, N.
    Stathopulos, I. A.
    ENERGY, 2009, 34 (04) : 502 - 509
  • [25] Monitoring of Actual Thermal Condition of High Voltage Overhead Lines
    Halasz, Balint G.
    Nemeth, Balint
    Racz, Levente
    Szabo, David
    Gocsei, Gabor
    TECHNOLOGICAL INNOVATION FOR RESILIENT SYSTEMS (DOCEIS 2018), 2018, 521 : 265 - 273
  • [26] Corrosion Conditions Analysis of In-service ACSR Overhead Lines
    Deng, Yuanjing
    Yu, Junchao
    Xia, Kaiquan
    Yang, Lin
    ADVANCED RESEARCH IN MATERIAL SCIENCE AND MECHANICAL ENGINEERING, PTS 1 AND 2, 2014, 446-447 : 753 - +
  • [27] Distributed Thermal Monitoring of High-Voltage Power Lines
    Racz, Levente
    Szabo, David
    Gocsei, Gabor
    Nemeth, Balint
    SENSORS, 2023, 23 (05)
  • [28] Remote in-service monitoring the status of coatings and materials using Flash technique
    Troitsky, OY
    Medvedev, VV
    KORUS '99: THIRD RUSSIAN-KOREAN INTERNATIONAL SYMPOSIUM ON SCIENCE AND TECHNOLOGY, VOLS 1 AND 2, 1999, : 378 - 381
  • [29] PIPELINE VOLTAGE HAZARDS DUE TO PROXIMITY TO OVERHEAD HIGH-VOLTAGE AC TRANSMISSION-LINES
    CHERNEY, EA
    CARRIGAN, DJ
    MATERIALS PERFORMANCE, 1974, 13 (07) : 10 - 12
  • [30] High-voltage overhead power lines and property values: A residential study in the UK
    Sims, S
    Dent, P
    URBAN STUDIES, 2005, 42 (04) : 665 - 694