Effect of inclination on heat transfer and flow regimes in large flattened-tube steam condensers

被引:11
|
作者
Davies, William A., III [1 ]
Kang, Yu [1 ]
Hrnjak, Pega [1 ,2 ]
Jacobi, Anthony M. [1 ]
机构
[1] Univ Illinois, Dept Mech Sci & Engn, ACRC, Urbana, IL 61801 USA
[2] CTS Creat Thermal Solut Inc, Urbana, IL USA
基金
美国国家科学基金会;
关键词
Air-cooled condenser; Inclination; Heat transfer coefficient; Flattened tube; Condensation; CONVECTIVE CONDENSATION; PATTERN TRANSITIONS; PREDICTING FLOW; MODEL; PERFORMANCE; DIAMETER; FLUID;
D O I
10.1016/j.applthermaleng.2018.11.078
中图分类号
O414.1 [热力学];
学科分类号
摘要
An experimental study of convective steam condensation inside a large, inclined, flattened tube used in air-cooled condensers for power plants is presented. This is the fourth of a four-part group of papers. The first three parts (Kang et al., 2017; Davies et al., 2017, 2018) published in the same journal present the facility, pressure drop, void fraction, flow regime and heat transfer results, while this study presents the effects of inclination on heat transfer and flow regimes. The condenser is a flattened steel tube with brazed aluminum fins. The full tube has dimensions 10.72 m x 214 mm x 18 mm. The condenser tube is cut in half lengthwise and covered with a polycarbonate window to perform visualization simultaneously with the heat transfer measurements. The steam is condensed at atmospheric pressure, and cooled by air at a uniform velocity profile. The angle of inclination is varied from horizontal (0 degrees) to 75 degrees downward. Condenser performance is also predicted with a model. The majority of the condenser is found to be in the stratified flow regime for all inclinations tested, with only a short annular section at the inlet of the condenser. The tubes inclined greater than 60 degrees are also found to have stratified-wavy flow near the condenser outlet. Overall condenser U is found to increase with increasing downward inclination angle of the condenser, with a maximum increase of approximately 4% at 75 degrees inclination. This improvement is found to be the result of improved drainage and increased void fraction near the condenser outlet. Mean steam-side heat transfer coefficient(1) (HTC) is found to remain constant along the tube, and for the entire condenser, with changes in tube inclination angle. Commonly-used inclined condensation HTC correlations are found to underpredict the magnitude of the experimentally-determined steam-side HTC.
引用
收藏
页码:999 / 1006
页数:8
相关论文
共 50 条
  • [41] FLOW REGIMES AND HEAT REMOVAL MECHANISMS IN A SINGLE INVERTED U-TUBE STEAM CONDENSER
    NGUYEN, QT
    BANERJEE, S
    TRANSACTIONS OF THE AMERICAN NUCLEAR SOCIETY, 1982, 43 : 788 - 789
  • [42] HEAT TRANSFER WITH STEAM CONDENSING ON A HORIZONTAL TUBE AND WITH A FLOW OF CONDENSATE FROM ABOVE
    ISACHENK.VP
    GLUSHKOV, AF
    THERMAL ENGINEERING, 1969, 16 (06) : 120 - &
  • [43] Effect of heat transfer tube leak on dynamic characteristic of steam generator
    Sun, Bao-Zhi
    Shi, Jian-Xin
    Lei, Yu
    Li, Na
    Zheng, Lu-Song
    Liu, Shang-Hua
    Yuanzineng Kexue Jishu/Atomic Energy Science and Technology, 2015, 49 (04): : 680 - 687
  • [44] Impacts of tube support plate on flow and heat transfer characteristics of steam generator
    Yang, Yuan-Long
    Sun, Bao-Zhi
    Zhang, Guo-Lei
    Zhang, Peng
    Sun, B.-Z. (sunbaozhi@163.com), 1600, Shanghai Jiaotong University (48): : 205 - 209
  • [45] HEAT TRANSFER WITH FLATTENED TUBES IN TRANSVERSE FLOW.
    Baklastov, A.M.
    Yefimov, A.L.
    Gorbenko, V.A.
    1600, (09):
  • [46] Effect of inclination on flooding and heat transfer during reflux condensation in a small diameter tube
    Fiedler, S
    Auracher, H
    Winkelmann, D
    INTERNATIONAL COMMUNICATIONS IN HEAT AND MASS TRANSFER, 2002, 29 (03) : 289 - 302
  • [47] Determination of optimum aspect ratio for laminar flow heat transfer of dilute viscoelastic solutions in flattened tube heat exchangers
    Ismail, Z.
    Karim, R.
    HEAT AND MASS TRANSFER, 2012, 48 (08) : 1319 - 1331
  • [48] Determination of optimum aspect ratio for laminar flow heat transfer of dilute viscoelastic solutions in flattened tube heat exchangers
    Z. Ismail
    R. Karim
    Heat and Mass Transfer, 2012, 48 : 1319 - 1331
  • [49] A parametric study on heat transfer and pressure drop characteristics of circular tube with alternating flattened flow path
    Farsi, Mahdi
    Khoshvaght-Aliabadi, Morteza
    Alimoradi, Ashkan
    INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2021, 160
  • [50] A heat transfer correlation for natural draft wire-and-tube condensers
    Melo, Claudio
    Hermes, Christian J. L.
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2009, 32 (03): : 546 - 555