Analysis of Turn-to-Turn Fault on Split-Winding Transformer Using Coupled Field-Circuit Approach

被引:6
|
作者
Yang, Cunxiang [1 ]
Ding, Yiwei [1 ]
Qiu, Hongbo [1 ]
Xiong, Bin [2 ,3 ]
机构
[1] Zhengzhou Univ Light Ind, Elect & Informat Engn Inst, Zhengzhou 450002, Peoples R China
[2] Chinese Acad Sci, Inst Elect Engn, Beijing 100080, Peoples R China
[3] Univ Chinese Acad Sci, Beijing 100039, Peoples R China
基金
中国国家自然科学基金;
关键词
split-winding transformer; turn-to-turn fault; short circuit; three-dimensional finite element; FINITE-ELEMENT-METHOD; PERFORMANCE; 2D;
D O I
10.3390/pr9081314
中图分类号
TQ [化学工业];
学科分类号
0817 ;
摘要
The turn-to-turn faults (TTF) are also inevitable in split-winding transformers. The distorted leakage field generated by the TTF current results in large axial forces and end thrusts in the fault windings as well as affecting other branch windings normal operation, so it is of significance to study TTF of split-winding transformers. In this paper, the characteristics analysis of the split-winding transformer under the TTFs of the low voltage winding at different positions are presented. A 3600 KVA four split-windings transformer is taken as an example. Then, a simplified three-dimensional simplified model is established, taking into account the forces of the per-turn coil. The nonlinear-transient field-circuit coupled finite element method is used for the model. The leakage field distribution under the TTFs of the low voltage winding at different positions is studied. The resultant force of the short-circuit winding and the force of the per-turn coil are obtained. Subsequently, the force and current relationship between the branch windings are analyzed. The results show that the TTF at the specific location has a great influence on the axial windings on the same core, and the distorted leakage magnetic field will cause excessive axial force and end thrust of the normal and short-circuit windings. These results can provide a basis for the short-circuit design of split-winding transformer.
引用
收藏
页数:13
相关论文
共 50 条
  • [21] Electromagnetic-Thermal-Coupled Fault Analysis of PMASynRM With Turn-to-Turn Short-Circuit Involving a Few Strands
    Shi, Yanwen
    Wang, Jiabin
    Wang, Bo
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2022, 58 (01) : 294 - 303
  • [22] Short-Circuit Performance Analysis of a Distribution Transformer Using Coupled Field-Circuit Approach
    Al-Dori, Osamah
    Donuk, Atilla
    ELECTRIC POWER COMPONENTS AND SYSTEMS, 2024, 52 (04) : 629 - 640
  • [23] Winding turn-to-turn short-circuit diagnosis using FRA method: sensitivity of measurement configuration
    Devadiga, Anurag A.
    Harid, Noureddine
    Griffiths, Huw
    Al Sayari, Naji
    Barkat, Braham
    Jayaram, Sheshakamal
    Ikeda, Hisatoshi
    Koshizuka, Tadashi
    Taniguchi, Yasuhiko
    IET SCIENCE MEASUREMENT & TECHNOLOGY, 2019, 13 (01) : 17 - 24
  • [24] Synchronous Machines Field Winding Turn-to-Turn Fault Severity Estimation Through Machine Learning Regression Algorithms
    Gonzalez Guillen, Carlos Eduardo
    De Porras Cosano, Antonio Mateo
    Tian, Pengfei
    Colmenares Diaz, Javier
    Zarzo, Alejandro
    Antonio Platero, Carlos
    IEEE TRANSACTIONS ON ENERGY CONVERSION, 2022, 37 (03) : 2227 - 2235
  • [25] Design and Analysis on the Turn-to-Turn Fault Protection Scheme for the Control Winding of a Magnetically Controlled Shunt Reactor
    Zheng, Tao
    Zhao, Yanjie J.
    Jin, Ying
    Chen, Peilu L.
    Zhang, Fenfen F.
    IEEE TRANSACTIONS ON POWER DELIVERY, 2015, 30 (02) : 967 - 975
  • [26] Feasibility Analysis of Fault-tolerant Technology for Stator Winding Turn-to-turn Short-circuit Fault of Offshore Doubly-fed Induction Generator
    Wei S.
    Wu R.
    Fu Y.
    Zhang K.
    Zhang Z.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2019, 43 (05): : 114 - 120and128
  • [27] An Intelligent Approach using SVM to Enhance Turn-to-Turn Fault Detection in Power Transformers
    Elsamahy, M.
    Babiy, M.
    2012 IEEE ELECTRICAL POWER AND ENERGY CONFERENCE (EPEC), 2012, : 255 - 260
  • [28] Turn-to-Turn Fault Diagnosis on Three-Phase Power Transformer Using Hybrid Detection Algorithm
    Liu, Chien-Hsun
    Muda, Willybrordus H. P.
    Kuo, Cheng-Chien
    APPLIED SCIENCES-BASEL, 2021, 11 (06):
  • [29] Reduction of Short Circuit Current using DC Transmission and Split-Winding Power Transformer
    Krakhmalin, Igor
    Chivenkov, Alexandr
    Vagapov, Yuriy
    Anuchin, Alecksey
    2019 54TH INTERNATIONAL UNIVERSITIES POWER ENGINEERING CONFERENCE (UPEC), 2019,
  • [30] Brushless Synchronous Generator Turn-to-Turn Short Circuit Fault Detection Using Multilayer Neural Network
    Tun, Pyae Phyo
    Kumar, Padmanabhan Sampath
    Pratama, Ryan Arya
    Liu Shuyong
    2018 ASIAN CONFERENCE ON ENERGY, POWER AND TRANSPORTATION ELECTRIFICATION (ACEPT), 2018,