Air quality in rooms conditioned by chilled ceiling and mixed displacement ventilation for energy saving

被引:26
|
作者
Chakroun, W. [1 ]
Ghali, K. [2 ]
Ghaddar, N. [2 ]
机构
[1] Kuwait Univ, Dept Mech Engn, Safat 13060, Kuwait
[2] Amer Univ Beirut, Dept Mech Engn, Beirut 11072020, Lebanon
关键词
Contaminant transport in plumes; Indoor air quality with mixed return air; Chilled ceiling displacement ventilation; SYSTEM; OPERATION; DESIGN; MODEL;
D O I
10.1016/j.enbuild.2011.06.019
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
A transient-contaminant-transport model is developed for assessing IAQ in the breathing zone when introducing return air into rooms conditioned by CC/DV system to save energy. The steady state transport model of [1] is extended to transient conditions while accounting for significant wall plumes associated with external loads. Experiments are performed to validate the extended model predictions of IAQ expressed in the level of CO2 concentration. Experiments are conducted in a chamber with two external walls in Kuwait Climate. Measurements are recorded in time of the air temperature and CO2 concentration at selected locations in the room and compared with values predicted by the model. Experimental results agreed well with model predictions. The maximum errors in predicted CO2 concentrations are less than +/- 25 ppm in presence of external load. 60% fresh air fraction resulted in 37% less energy consumption compared with 100% fresh air CC/DV system. The validated model is applied to a case study in Kuwait to evaluate energy saving over the cooling season for a typical office space while using mixed DV air. Energy savings of up to 20.6% can be realized using mixed supply air while maintaining IAQ compared with energy used for the 100% fresh air. (C) 2011 Elsevier B.V. All rights reserved.
引用
收藏
页码:2684 / 2695
页数:12
相关论文
共 50 条
  • [31] Experimental and computational investigation into suppressing natural convection in chilled ceiling/displacement ventilation environments
    Taki, A. H.
    Jalil, L.
    Loveday, D. L.
    ENERGY AND BUILDINGS, 2011, 43 (11) : 3082 - 3089
  • [32] Effectiveness of intermittent personalized ventilation assisting a chilled ceiling for enhanced thermal comfort and acceptable indoor air quality
    Al Assaad, Douaa
    Ghali, Kamel
    Ghaddar, Nesreen
    BUILDING AND ENVIRONMENT, 2018, 144 : 9 - 22
  • [33] Study on Indoor Air Quality of Ceiling Radiant Cooling Panel System Integrated with Displacement Ventilation
    Du, Jing
    Li, Nianping
    PROCEEDINGS OF THE 8TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, VOL 1: INDOOR AND OUTDOOR ENVIRONMENT, 2014, 261 : 497 - 505
  • [34] Low-energy cooling of rooms with chilled ceilings and ceiling-mounted devices
    Misirlioglu, A
    Gulcat, U
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2005, 29 (08) : 767 - 779
  • [35] Numerical investigation of airborne transmission in low-ceiling rooms under displacement ventilation
    Wang, Changchang
    Hong, Jiarong
    PHYSICS OF FLUIDS, 2023, 35 (02)
  • [36] NUMERICAL INVESTIGATION OF OFFICE ROOM VENTILATION BY ADOPTING DISPLACEMENT VENTILATION AND CHILLED CEILING SYSTEM IN A HOT AND DRY CLIMATE
    Shbeeb, Ali A.
    Mahdi, Ala'a A.
    Hussein, Ahmed K.
    JOURNAL OF ENGINEERING SCIENCE AND TECHNOLOGY, 2022, 17 (04): : 2958 - 2982
  • [37] Thermal comfort in chilled ceiling and displacement ventilation environments: Vertical radiant temperature asymmetry effects
    Hodder, SG
    Loveday, DL
    Parsons, KC
    Taki, AH
    ENERGY AND BUILDINGS, 1998, 27 (02) : 167 - 173
  • [38] Simplified thermal model of spaces cooled with combined positive displacement ventilation and chilled ceiling system
    Ayoub, Mohamad
    Ghaddar, Nesreen
    Ghali, Kamel
    HVAC&R RESEARCH, 2006, 12 (04): : 1005 - 1030
  • [39] Optimized Strategy for Combined Liquid Desiccant Dehumidification Membrane with Chilled Ceiling and Displacement Ventilation System
    Muslmani, Mohamad
    Ghaddar, Nesreen
    Ghali, Kamel
    6TH INTERNATIONAL CONFERENCE ON ENERGY RESEARCH AND DEVELOPMENT, 2016, : 25 - 32
  • [40] Air Distribution and Ventilation Effectiveness in a Room with Floor/Ceiling Heating and Mixing/Displacement Ventilation
    Wu, Xiaozhou
    Fang, Lei
    Olesen, Bjarne W.
    Zhao, Jianing
    PROCEEDINGS OF THE 8TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, VOL 1: INDOOR AND OUTDOOR ENVIRONMENT, 2014, 261 : 59 - 67