Producing a better performance for the under floor air distribution system in a dense occupancy space

被引:8
|
作者
Fathollahzadeh, Mohammad Hassan [1 ]
Heidarinejad, Ghassem [1 ]
Pasdarshahri, Hadi [1 ]
机构
[1] Tarbiat Modares Univ, Fac Mech Engn, POB 14115-143, Tehran, Iran
关键词
Under floor air distribution (UFAD); Dense occupied space; Thermal comfort; Local thermal discomfort; Indoor air quality (IAQ); SUPPLY DISPLACEMENT VENTILATION; DISTRIBUTION UFAD SYSTEM; THERMAL COMFORT; ENERGY-CONSUMPTION; OFFICE; ENVIRONMENT; PREDICTION; IAQ;
D O I
10.1016/j.enbuild.2016.05.008
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This study deals with the possibility of the under floor air distribution system usage in a dense occupied space (80 occupants) regarding to the general thermal comfort conditions of occupants, local thermal discomfort, and indoor air quality. Computational fluid dynamics methods are used to predict general thermal comfort conditions of occupants, local thermal discomfort, and indoor air quality in this space. Different locations for the diffusers and velocities of the supply air are varied to determine what produces a better performance for the under floor air distribution system. It is found that when the diffusers are installed under seats, higher temperatures are measured at relatively lower heights due to the impedance in the injection of the fresh air supply. Moreover, the mean local age of air, as indoor air quality index, is increased by reducing the supply air velocity, which means that there is a less fresh air in the breathing zone of occupants. However, general thermal comfort conditions and local thermal discomfort should be considered as determining factors in each study. Based on the overall results of the study, under floor air distribution system is capable of creating a comfortable indoor environment in a dense occupied space. (C) 2016 Elsevier B.V. All rights reserved.
引用
收藏
页码:230 / 238
页数:9
相关论文
共 50 条
  • [21] Model for Indoor Air Vertical Temperature Distribution under Nozzle Air Supply System in Large Space Building
    Cai, Ning
    Huang, Chen
    10TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, ISHVAC2017, 2017, 205 : 1079 - 1086
  • [22] Effect of air change rate upon indoor inhalable particles concentration in under-floor distribution system
    Li, Can
    Li, Nian-Ping
    Yao, Guo-Cai
    Hunan Daxue Xuebao/Journal of Hunan University Natural Sciences, 2007, 34 (12): : 26 - 29
  • [23] A techno-economical study of a solar-assisted under-floor air distribution system for buildings in the tropics
    Yau, Yat Huang
    Poh, Kai Sin
    Badarudin, Ahmad
    SUSTAINABLE ENERGY TECHNOLOGIES AND ASSESSMENTS, 2022, 51
  • [24] An experimental study on a full-scale indoor thermal environment using an Under-Floor Air Distribution system
    Lin, Y. J. P.
    Tsai, T. Y.
    ENERGY AND BUILDINGS, 2014, 80 : 321 - 330
  • [25] Thermal comfort assessment of an office building served by under-floor air distribution (UFAD) system - A case study
    Alajmi, Ali F.
    Baddar, Faisal A.
    Bourisli, Raed I.
    BUILDING AND ENVIRONMENT, 2015, 85 : 153 - 159
  • [26] Effect of floor space allowance on the performance of finishing pigs under tropical condition
    Sharma, PK
    Saikia, S
    Baruah, KK
    Bora, MC
    INDIAN JOURNAL OF ANIMAL SCIENCES, 2005, 75 (10): : 1194 - 1195
  • [27] Thermal comfort and IAQ assessment of under-floor air distribution system integrated with personalized ventilation in hot and humid climate
    Li, Ruixin
    Sekhar, S. C.
    Melikov, A. K.
    BUILDING AND ENVIRONMENT, 2010, 45 (09) : 1906 - 1913
  • [28] Performance of Free Space Optical Terrestrial Link under Dense Fog Conditions
    Yasir, S. M.
    Khan, M. S.
    Wahid, A.
    Mushtaq, M. T.
    Memon, M. I.
    Siraj, M.
    Iqbal, M. S.
    ACTA PHYSICA POLONICA A, 2018, 134 (01) : 268 - 270
  • [29] Cooling performance comparison of radiant floor system and all-air system with solar radiation
    Xiang, Xiangjian
    Zhao, Kang
    Liu, Xiaohua
    Jiang, Yi
    6TH INTERNATIONAL BUILDING PHYSICS CONFERENCE (IBPC 2015), 2015, 78 : 2322 - 2327
  • [30] Uniformity of Supply Air in the Plenum for Under-Floor Air Distribution Ventilation in a Circular Conference Room: A CFD Study
    Fan, Xiaolei
    Yu, Tao
    Liu, Peng
    Li, Xiangdong
    ENERGIES, 2022, 15 (17)