Mitigating the Impacts of Uncertain Geomagnetic Disturbances on Electric Grids: A Distributionally Robust Optimization Approach

被引:5
|
作者
Ryu, Minseok [1 ]
Nagarajan, Harsha [2 ]
Bent, Russell [2 ]
机构
[1] Argonne Natl Lab, Math & Comp Sci Div, Lemont, IL 60439 USA
[2] Los Alamos Natl Lab, Appl Math & Plasma Phys Grp T5, Los Alamos, NM 87545 USA
关键词
Mathematical models; Switches; Reactive power; Power transmission lines; Earth; Costs; Power transformers; Geomagnetic disturbance; E-field; distributionally robust optimization; AC power flow;
D O I
10.1109/TPWRS.2022.3147104
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Severe geomagnetic disturbances (GMDs) increase the magnitude of the electric field on the Earth's surface (E-field) and drive geomagnetically-induced currents (GICs) along the transmission lines in electric grids. These additional currents can pose severe risks, such as current distortions, transformer saturation and increased reactive power losses, each of which can lead to system unreliability. Several mitigation actions (e.g., changing grid topology) exist that can reduce the harmful GIC effects on the grids. Making such decisions can be challenging, however, because the magnitude and direction of the E-field are uncertain and non-stationary. In this paper, we model uncertain E-fields using the distributionally robust optimization (DRO) approach that determines optimal transmission grid operations such that the worst-case expectation of the system cost is minimized. We also capture the effect of GICs on the nonlinear AC power flow equations. For solution approaches, we develop an accelerated column-and-constraint generation (CCG) algorithm by exploiting a special structure of the support set of uncertain parameters representing the E-field. Extensive numerical experiments based on "epri-21" and "uiuc-150" systems, designed for GMD studies, demonstrate (i) the computational performance of the accelerated CCG algorithm, (ii) the superior performance of distributionally robust grid operations that satisfy nonlinear, nonconvex AC power flow equations and GIC constraints, in comparison with standard stochastic programming-based methods during the out-of-sample testing.
引用
收藏
页码:4258 / 4269
页数:12
相关论文
共 50 条