Accurate fault location technique for distribution system using fault-generated high-frequency transient voltage signals

被引:100
|
作者
Bo, ZQ [1 ]
Weller, G
Redfern, MA
机构
[1] ALSTOM T&D Protect & Control Ltd, St Leonards Works, Stafford ST17 4LX, England
[2] Univ Bath, Dept Elect & Elect Engn, Bath BA2 7AY, Avon, England
关键词
D O I
10.1049/ip-gtd:19990074
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A technique is presented for accurate fault location on distribution overhead lines and underground cables. A specially designed fault locator unit is used to capture the high-frequency voltage transient signal generated by faults on the distribution line/cable. The travelling time of the high-frequency components is used to determine the fault position. The technique is insensitive to fault type, fault resistance, fault inception angle and system source configuration, and is able to offer very high accuracy in fault location in a distribution system.
引用
收藏
页码:73 / 79
页数:7
相关论文
共 50 条
  • [41] EMTR-based fault location for DC line in VSC-MTDC system using high-frequency currents
    Zhang, Xipeng
    Tai, Nengling
    Wang, Yanhong
    Liu, Jian
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2017, 11 (10) : 2499 - 2507
  • [42] Support vector classification and regression for fault location in distribution system using voltage sag profile
    Gururajapathy, Sophi Shilpa
    Mokhlis, Hazlie
    Bin Illias, Hazlee Azil
    Awalin, Lilik Jamilatul
    IEEJ TRANSACTIONS ON ELECTRICAL AND ELECTRONIC ENGINEERING, 2017, 12 (04) : 519 - 526
  • [43] Application of Optimized Technique for Identification of Location and Recognition of Fault in Distribution System
    Kumar, U. Kamal
    Reddy, Nimmakayala Siva Prasad
    Daram, Suresh Babu
    Janamala, Varaprasad
    HELIX, 2020, 10 (02): : 130 - 135
  • [44] An approach to improve high-frequency resonance technique for bearing fault diagnosis
    Mishra, Sitesh Kumar
    Shakya, Piyush
    Babureddy, Vimaleswar
    Vignesh, S. Ajay
    MEASUREMENT, 2021, 178
  • [45] A PRACTICAL APPROACH TO ACCURATE FAULT LOCATION ON EXTRA-HIGH-VOLTAGE TEED FEEDERS
    AGGARWAL, RK
    COURY, DV
    JOHNS, AT
    KALAM, A
    NILSSON, SL
    IEEE TRANSACTIONS ON POWER DELIVERY, 1993, 8 (03) : 874 - 883
  • [46] Fault location in microgrids: a communication-based high-frequency impedance approach
    Beheshtaein, Siavash
    Cuzner, Robert
    Savaghebi, Mehdi
    Golestan, Saeed
    Guerrero, Josep M.
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2019, 13 (08) : 1229 - 1237
  • [47] Extension of the Accurate Voltage-Sag Fault Location Method in Electrical Power Distribution Systems
    Menchafou, Youssef
    Zahri, Mustapha
    Habibi, Mohamed
    El Markhi, Hassane
    JOURNAL OF ELECTRICAL SYSTEMS, 2016, 12 (01) : 33 - 44
  • [48] New technique for fault location in distribution systems using sincrophasor voltages
    Crespo, Diego L. C.
    Moreto, Miguel
    ELECTRIC POWER SYSTEMS RESEARCH, 2022, 212
  • [49] An On-line Fault Location Technique for DC Microgrid Using Transient Measurements
    Meghwani, Anju
    Chakrabarti, Saikat
    Srivastava, S. C.
    2017 7TH INTERNATIONAL CONFERENCE ON POWER SYSTEMS (ICPS), 2017, : 386 - 391
  • [50] Fault location considering nonlinear profile of bus voltage sag for distribution system
    Zheng, Tianwen
    Xiao, Xianyong
    Zhang, Wenhai
    Yang, Honggeng
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2012, 32 (11): : 115 - 120